POWER-ONE NHC3011-5

NHC3000 AC-DC Series Data Sheet
Features
• Single-phase AC input
• 3U height
• Active current share
• Power Factor Correction (PFC)
Meets EN61000-3-2
• Remote voltage adjust, and current monitoring
• Overtemperature, overload, and overvoltage
protection
• Power supply status indicators
• Output current meter (bar graph)
• MTBF> 700,000 hours
Description
The NHC3000 Series of chassis-mounted power systems provides AC front-end capability to telecom, data
communications and other distributed power designs. The NHC3000 can also be used for many other applications
requiring bulk power.
NHC3000 power supplies provide excellent protection against input voltage transients. A connector at the rear of the
supply provides access to interfaces for remote sensing, remote voltage adjust, current sharing, power supply status,
standby logic voltage, remote on/off, and power connections.
Airflow for the NHC3000 is from the front through the rear. The output is floating with respect to the chassis and may
be used as a positive or negative polarity supply.
Model Selection
MODEL
OUTPUT
VOLTAGE
ADJUSTMENT
RANGE
MAXIMUM OUTPUT
CURRENT
LINE
REGULATION
LOAD
REGULATION (NOTE 1)
RIPPLE & NOISE
%p-p (NOTE 2)
INITIAL SETTING
ACCURACY
24V
28V
48V
21.6V to 26.4V
25.2V to 30.8V
43.2V to 52.8V
125A
107A
62.5A
0.2%
0.2%
0.2%
0.4%
0.4%
0.4%
1%
1%
1%
23.95V to 24.05V
27.92V to 28.08V
47.90V to 48.10V
NHC3011-5
NHC3011-6
NHC3021-8
NOTES: 1) With Remote Sense connected.
2) Maximum peak-to-peak noise expressed as a percentage of output voltage, 20 MHz bandwidth.
Input Specifications
PARAMETER
CONDITIONS/DESCRIPTION
MIN
Input Voltage - AC
Input Frequency
Hold-up Time
Input Current
Inrush Surge Current
Power Factor
Single-phase continuous input range.
AC input.
AC turn-off to output greater than or equal to 95%.
At full rated load per module.
180
47
16
Operating Frequency
at 230 VAC
NOM
MAX
UNITS
264
63
VAC
Hz
ms
ARMS
APK
15.0
30
Per EN61000-3-2 at full load.
At half load.
Switching frequency
JUN 03, 2004 revised to MAY 26, 2006
0.99
0.98
W/VA
140
Page 1 of 4
kHz
www.power-one.com
NHC3000 AC-DC Series Data Sheet
Output Specifications
PARAMETER
CONDITIONS/DESCRIPTION
Efficiency
Minimum Loads
Output Power
Overshoot / Undershoot
Transient Response
Full rated load.
Minimum loading required to maintain regulation.
Per module.
Output voltage overshoot/undershoot at turn-on.
Maximum recovery time, to within 1% of initial set point due to a
50-100-50% load change, 1A/µs, ±3.0% max. deviation.
AC turn-on to output >95%.
Time required for output voltage to rise from 10% to 90%.
Turn-On Delay Time
Turn-on Rise Time
MIN
NOM
MAX
UNITS
3000
±3.0
500
%
A
Watts
%
µs
88
0
1.2
100
2.0
Sec
ms
MAX
UNITS
Interface Signals and Internal Protection
PARAMETER
CONDITIONS/DESCRIPTION
Overvoltage Protection
Latch style overvoltage protection.
Overcurrent Protection
Short Circuit Protection
Overtemperature
DC OK, Output Good (Module)
Input Power Fail Warning
Current Monitor
Current Share Accuracy
Remote Sense
Auxiliary Power (Logic Power)
Output Margin
Power Fail Signal
& PF Warning Time
Output Voltage and
Current Programming
MIN
24V model
28V model
48V model
Constant current limit, as a percentage of maximum rated load.
Short circuit current, as a percentage of maximum rated load.
Output recovers automatically after removal of short.
Module shuts down when internal temperature reaches an unsafe level.
Output low threshold measured at output studs. Form C contacts,
rating is 500 mA at 30 VDC.
Relay closes >5 ms before output drops to <95%. Relay opens after
output is in regulation. Form C contacts, pull-up to +5 V through a
1 k⍀ resistor.
Signal provides an output of 0-10V which applies
over 10-100% of rated load. At 50% load:
Applies over 10-100% load as a percentage of full load.
Total voltage compensation for cable losses with respect to the main output.
Referenced to negative output terminal and derived from the internal 5.1 VDC.
Margin High - Connect Margin input to Margin Ref.
Margin Low - Connect Margin input to Logic Common.
PF drops to “0” before output drops to 95% due to loss of AC.
PF goes to “1” (logic high) after +5 V is in regulation. Form C Warning Time:
contacts pull up to +5 V through a 1 k⍀ resistor.
Optional - Consult factory for details..
NOM
26.4
30.8
52.8
100
105
±2
±5
27.6
33.8
55.2
110
110
%
%
±8
%
5
V
ms
4.5
5.5
±5
0.5
50
+5
-5
VDC
%
V
mA
%
5
ms
Mechanical Specifications
PARAMETER
CONDITIONS/DESCRIPTION
Input Connector
Output Connector
Signal Connector J1
Visual Indicators
Cooling
Terminal block.
Copper bus bar blade with single round hole for 5/16 screw.
Power-One P/N 10X0172-001, Amp 247846-4, ITT Common ZEDBL25SBA
Mates with Power=One P/N 10X0105-000, Amp 202208-1, ITT Common DBA25-K87-F0
Mating Pin P/N 12X0005-000, Amp 66506-8
AC-OK LED and DC-OK LED located on the connector end of the supply.
Internal fan; approximately 100 CFM.
Mounting
See outline drawing.
JUN 03, 2004 revised to MAY 26, 2006
MIN
Page 2 of 4
NOM
MAX
UNITS
www.power-one.com
NHC3000 AC-DC Series Data Sheet
Safety, Regulatory, and EMI Specifications
PARAMETER
CONDITIONS/DESCRIPTION
Agency Approvals
Electromagnetic Interference
Conducted & Radiated
ESD Susceptibility
UL 60950-1 (UL), CSA C22.2 No. 60950-1, EN60950-1 (TÜV), CE Mark, and CB Report
FCC CFR title 47 Part 15 Sub-Part B.
A
EN55022 / CISPR 22.
A
Per EN61000-4-2, level 3, direct discharge.
8
Per EN61000-4-2, level 3, air discharge.
15
Per EN61000-4-3, level 3.
10
Per EN61000-4-4, level 3, @ 5 kHz.
2
Per EN61000-4-5, level 3.
Line to Line
2
Per EN61000-4-6, level 3; 10V from 150 Hz to 80 MHz.
Per EN60950.
at 240 VAC
Radiated Susceptibility
EFT/Burst
Input Transient Protection
Conducted Susceptibility
Leakage Current
MIN
NOM
MAX
UNITS
Class
kV
V/m
kV
kV
1.5
mA
MAX
UNITS
85
50
°C
°C
%/°C
%
ft
Environmental Specifications
PARAMETER
Storage Temperature
Operating Temperature
Temperature Coefficient
Humidity, Non-Condensing
Altitude
Shock
Vibration
Acoustics
Weight
CONDITIONS/DESCRIPTION
MIN
NOM
-40
0
Derate linearly to 60% at 70 °C
After 15-minute warmup.
0.008
5
Derate at 7°C/1000 ft above 8000 ft.
Operating: half-sine 10 ms, 3 axis.
Non-operating: half-sine 10 ms, 3 axis.
Operating: swept sine 5-2000-5 Hz, 5-32 Hz, 0.02îDA, 32-2000 Hz.
Non-operating: random 10-2000 Hz.
Sound pressure level at 1 meter.
95
13,000
+20
+40
1
6.15
57
12.1
5.49
GPK
GPK
Grms
dbA
lb
kg
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components
in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective
divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.
JUN 03, 2004 revised to MAY 26, 2006
Page 3 of 4
www.power-one.com
NHC3000 AC-DC Series Data Sheet
NHC3000 OVERALL SIZE: 12.25" x 5.00" x 5.00" (311.2mm x 127.0mm x 127.0mm)
B
A
D
AIRFLOW DIRECTION
C
F
N
G
L
P
E
N
K
H
M
0.25"
T
R
U
S
V
J1
W
J1 Connector Pinout
Callout
Inches
Millimeters
Pin
A
12.25
311.2
1
DC OK N/C
13
CURRENT SHARE
B
1.50
38.1
2
DC OK COM
14
+5V LOGIC
C
0.12
3.1
3
DC OK N/O
15
(-) SENSE
D
5.00
127.0
4
POWER FAIL PULL UP
16
(+) SENSE
E
5.00
127.0
5
ENABLE PULL UP
17
N/U
F
3.98
101.1
6
POWER FAIL
18
N/U
Description
Pin
Description
G
2.86
72.6
7
POWER FAIL RTN
19
I PROGRAM (OPTIONAL
H
0.49
12.5
8
REMOTE ON/OFF
20
LOGIC COM
K
1.17
29.7
9
REMOTE ON/OFF RTN
21
N/U
M
2.19
55.6
10
CURRENT MONITOR
22
N/U
N
1.36
34.5
11
MARGIN REF
23
N/U
P
2.16
54.9
12
MARGIN
24
N/U
R
Ø 0.34
Ø 8.6
25
RESERVED FOR OPTIONS
S
0.80
20.3
T
0.650
16.51
U
3.700
93.98
V
0.825
21.0
W
9.425
239.4
JUN 03, 2004 revised to MAY 26, 2006