GAMEWELL-FCI IDU

7200 SERIES
IDU
ADDRESSABLE INTERFACE UNIT
DESCRIPTION
The Addressable Interface Unit (IDU) is designed for retrofit purposes and provides the 7200 Series Fire Alarm Control
panel with the ability to communicate with FCI FC-ID Series addressable monitor or control modules. It mounts in any available module position.
The IDU provides two (2) signaling line circuits, each of which can be wired similar to NFPA Style 6 (Class “A”) or Style 4
(Class “B”). Each of these circuits can address up to 60 points, (50 monitor modules and 10 control modules for a maximum of
120 points per IDU. Up to five (5) IDU units can be accommodated by one 7200 Series control panel.
Signal processing for alarm verification is also available to provide a greater immunity to false alarms.
The IDU signaling line circuits each have a red “ALARM” LED and a yellow “TROUBLE” LED, along with a circuit “DISCONNECT” user switch, for individual circuit control and programming functions.
A pluggable terminal block is provided with each unit for the connection of field wiring. This block will accommodate wire
sizes up to 12 AWG.
The IDU will accommodate FCI model CPD-ID, 301ID, 2W-ID, RIM-U, SLM, RZM, RSM, RZST and EOL-E monitor
modules, or CPM control modules.
The IDU unit occupies a full-size space in the cabinet.
TECHNICAL INFORMATION
24 VDC (nominal)
0.065 amp. maximum
0.085 amp.
0.75 amp. max.
Voltage
Supervisory current
Alarm current
Short circuit current
ORDERING INFORMATION
Part No.
1100-0389
Model
IDU
Description
Addressable Interface Unit
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
1998 All Rights Reserved
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
An ISO 9001 Certified Company
9020-0462/Ver. 1.2