MAGNETROL E3A-JA3A-H11

Digital E3 Modulevel®
Liquid Level Displacer
Transmitter
D E S C R I P T I O N
The Digital E3 Modulevel is an advanced, intrinsically
safe two-wire instrument utilizing simple buoyancy principle to detect and convert liquid level changes into a
stable output signal. The linkage between the level sensing element and output electronics provides a simple
mechanical design and construction. The vertical in-line
design of the transmitter results in low instrument weight
and simplified installation. The instrument comes in a
variety of configurations and pressure ratings for varied
applications.
The Digital E3 Modulevel has microprocessor-based
electronics with 4 –20 mA/HART® or FOUNDATION fieldbus™
output. E3 supports the FDT/DTM standard and a
PACTware™ PC software package allows for additional
configuration and trending capabilities.
T E C H N O L O G Y
Changing buoyancy forces caused by liquid level change
act upon the spring supported displacer causing vertical
motion of the core within a linear variable differential
transformer.
As the core position changes with liquid level, voltages
are induced across the secondary windings of the LVDT.
These signals are processed in the electronic
circuitry and converted to a useable output signal. The
enclosing tube acts as a static isolation barrier between
the LVDT and the process media.
A P P L I C A T I O N S
MEDIA: Liquids or slurries, clean or dirty, light hydrocarbons
to heavy acids (SG=0.23 to 2.20)
VESSELS: Process & storage, bridles, bypass chambers, interface, sumps & pits up to unit pressure & temperature ratings.
CONDITIONS: Most liquid level measurement and control
applications including those with varying dielectric, vapors,
turbulence, foam, buildup, bubbling or boiling and high
fill/empty rates. Also, liquid/liquid interface level measurement
or density control.
F E A T U R E S
• Two-wire, loop-powered, transmitter for level,
interface or density measurement
• No level change needed for configuration; no field
calibration necessary.
• Non-interacting zero and span
• Emission and immunity compliance to EN 61326
• Specific gravity adjustment without stopping process
• Signal damping adjustment
• Safety Integrity Level (SIL) value of 2, SFF value of
92.3%
• 15-unit multi-drop capability
• 4 –20 mA output signal
• Two-line, 8-character LCD and 3-button keypad
• Continuous self-test with 22 mA, 3.6 mA or Hold
fault indication fully compliant with NAMUR NE 43
• Comprehensive diagnostics with faults, warnings &
status history
• HART or FOUNDATION fieldbus digital communications
• PACTware PC program using HART communication
for advanced configuration and troubleshooting
(see bulletin 59-101)
• IS, XP and Non-incendive approvals by FM, CSA,
ATEX, IEC
I N T E R F A C E
E3 Modulevel is capable of tracking the interface level
of two immiscible liquids with different densities. Each
unit is custom-made with a displacer specially designed
for the user’s application. This allows it to detect the
position of a clean interface or an emulsion layer and
convert it into a stable 4 –20 mA signal. Contact the factory
for assistance in specifying an E3 for interface service.
Note that for proper interface detection, the entire
displacer must always be immersed in liquid.
D E N S I T Y
• Standard output range from 3.8 to 20.5 mA
• 11 VDC turn on voltage
• Maximum loop resistance of 620 ohms at 24 VDC
• Process temperatures to +600° F (+315° C) for
non-steam applications
• Level ranges from 14 to 120+ inches
(356 to 3048+ mm)
• Specific gravity as low as 0.23
• Cast aluminum or stainless steel, TYPE 4X,
Cl I Div 1 Groups B, C, D housing
• Field wiring in isolated junction box
• Head rotatable through 360°
• Accepted proven LVDT/range spring technology
• Range spring suppresses effects of turbulence to
produce stable output signal.
• Flanged top mounting or external cage with
side/side or side/bottom connections
• Special options, materials of construction and custom engineered features available (consult factory).
• Spring protector standard
• Signal sampling 15 times per second
2
Yet another capability of E3 Modulevel is to track the
changing density of a liquid over a known density range
and convert that into a stable 4–20 mA output signal.
As the density of the liquid changes, so does the mass
of the liquid displaced by the specially designed displacer. The resulting change in buoyancy force on the
displacer causes the movement of the LVDT core necessary to convert the density change to the 4–20 mA
signal.
PACTware™ P C
S O F T W A R E
PACTware PC software and the Field Device Tool (FDT)
standard take level measurement to a new degree of
setup efficiency and user-friendliness. PACTware adds a
graphical software interface for increased ease of use.
Simply connect your PC through a serial interface to the
HART loop and all functionality can be accessed conveniently, and safely. Refer to Magnetrol PACTware
bulletins 59-101 & 59-601 for more information.
S P E C I F I C A T I O N S
F U N C T I O N A L
System Design
Measurement Principle
Buoyancy – continuous displacement utilizing a precision range spring
Input
Measured Variable
Level, determined by LVDT core movement affected by
Physical Range
Up to 120" (300 cm) based on displacer length (consult factory for longer ranges)
buoyancy force changes on continuous displacer
Output
Type
4 to 20 mA with HART Version 5.x
3.8 to 20.5 mA useable (meets NAMUR NE 43)
FOUNDATION fieldbus, H1 (31.25 kbits⁄sec), Available blocks AI_1, PID_1, RB_1, TB_1
LAS capable, ITK 5.0 interoperability tested
Resolution
Analog: 0.01 mA, Display: 0.1%, Level Units: 0.01 inch
Loop Resistance (maximum)
620 ohms @ 24 VDC
Diagnostic Alarm
3.6, 22 mA or HOLD selectable (meets NAMUR NE 43)
Damping
Adjustable 0-45 seconds
Sampling Rate
Transmitter 15 times per second
User Interface
Keypad
Indication
3-button menu-driven data entry and system security
2-line × 8-character LCD display
Power
Measured at instrument terminals
11 to 36 VDC
FOUNDATION fieldbus (Direct Current)
HART, 9 to 32 VDC
This device provides only Functional Isolation.
Current
22.5 mA maximum HART, 17 mA (maximum current draw) FOUNDATION fieldbus
This device provides only Functional Isolation.
Housing
Material
Aluminum A356-T6 (<0.20% copper), optional 316 stainless steel
Cable Entry
3
Ingress Protection
TYPE 4X, IP66
⁄4" NPT and M20
Chamber
Materials
Carbon steel
Wetted parts
316/316L and Inconel® (spring)
Process connections
Tank Top:
3", 4", 6" ANSI Flange
Chambered:
11⁄2", 2" NPT, Socketweld, ANSI Flanges
316/316L stainless steel
Process Conditions
Process temperature range Steam applications: -20° to +500° F (-29° to +260° C)
Process pressure range
5150 psig @ +100° F (355 bar @ +38° C)
Non-steam applications: -20° to +600° F (-29° to +315° C) Environment
Electronics Operating Temperature
-40 to +176° F
(-40 to +80° C)
Display Function Operating Temperature
-5 to +160° F
(-20 to +70° C)
Storage Temperature
-50 to +185° F
(-40 to +85° C)
Humidity
0-99%, non-condensing
Electromagnetic Compatibility
Meets CE Requirement: EN 61326
Shock Class
Vibration Class
ANSI/ISA-S71.03 Class SA1 ANSI/ISA-S71.03 Class VC2 Altitude
≤2000 m
Pollution Degree
2
Maximum process temperatures are based on ambient temperatures less than or equal to
+120° F (+49° C). Higher ambient temperatures require reduced process temperatures.
Consult factory for low temperature applications down to -330° F (-200° C)
With aluminum housing only. Does
not apply to models with 316 SS
transmitter housings.
3
S P E C I F I C A T I O N S
P E R F O R M A N C E :
L E V E L
Reference Conditions
Water @ +70° F (+21° C) with 14" displacer, wet calibration
Linearity
±0.20% of full span
Repeatability
±0.05% of full span
Ambient temperature effect
Maximum zero shift is 0.017%/°F over ambient temperature range
Operating Temp. range:
-40° to +176° F (-40° to +80° C)
LCD Temp. Range:
-5° to +160° F (-20° to +70° C)
Hysteresis
±0.20% of full span
Response Time
<1 second
Warm-up Time
<5 seconds
SIL
Suitable for use in SIL 2 environments with SFF of 92.3%
P E R F O R M A N C E :
I N T E R F A C E
L E V E L
D E N S I T Y &
Linearity
±0.70% of full span
Repeatability
±0.40% of full span
Ambient temperature effect
Maximum zero shift is 0.017%/°F over ambient temperature range
1200
Allowable Loop Resistance
vs. Supply Voltage
The displacer must always be completely immersed
in process liquid when the E3 is used in interface or
density service. Top mounted models require liquid
level to exceed the top of the displacer by 2" at all
times to ensure optimal performance.
20.5 mA
1000
Ω
800
620
600
400
200
24 VDC
0
A G E N C Y
A P P R O V A L S
AGENCY
MODEL
FM
XEXX-XXXX
with transmitter codes:
11
0
10
20
30
40 VDC
APPROVAL
x11, x12, x13, x14
x21, x22, x23, x24
x31, x32, x33, x34
Explosion Proof Class I, Div. 1; Groups B, C, D
Class II, Div. 1; Groups E, F, G
x41, x42, x43, x44
Class III, T5
x51, x52, x53, x54
Type 4X, IP66
x61, x62, x63, x64
XEXX-XXXX
with transmitter codes:
x15, x16, x17, x18
x25, x26, x27, x28
x35, x36, x37, x38
x45, x46, x47, x48
XEXX-XXXX
with transmitter codes:
Class II, Div. 1; Groups E, F, G
Class III, T4
x55, x56, x57, x58
Entity x65, x66, x67, x68
Type 4X, IP66
x11, x12, x13, x14
Class I, Div. 2; Groups A, B, C, D
x21, x22, x23, x24
x31, x32, x33, x34
Non-Incendive
Class II, Div. 2; Groups E, F, G
x41, x42, x43, x44
Class III, Div. 2; T4
x51, x52, x53, x54
Type 4X, IP66
x61, x62, x63, x64
4
Intrinsically Safe
Class I, Div. 1; Groups A, B, C, D
A G E N C Y
A P P R O V A L S
AGENCY
MODEL
CSA
XEXX-XXXX
with transmitter codes:
APPROVAL
x11, x13
x21, x23
x31, x33
Explosion Proof Class I, Div. 1; Groups B, C, D
Class II, Div. 1; Groups E, F, G
x41, x43
Class III, T5
x51, x53
Type 4X, IP66
x61, x63
XEXX-XXXX
x15, x17
with transmitter codes:
x25, x27
x35, x37
x45, x47
x55, x57
XEXX-XXXX
with transmitter codes:
Intrinsically Safe
Class I, Div. 1; Groups A, B, C, D
Class II, Div. 1; Groups E, F, G
Class III, T4
Entity x65, x67
Type 4X, IP66
x11, x13
Suitable for:
x21, x23
x31, x33
Class I, Div. 2; Groups A, B, C, D
Class II, Div. 2; Groups E, F, G
x41, x43
Class III, T4
x51, x53
Type 4X, IP66
x61, x63
ATEX
XEXX-XXXX, EXX-XXXX
x1E, x1F, x1G, x1H
Flameproof
with transmitter codes
x2E, x2F, x2G, x2H
ATEX Ex II 1/2 G Ex d IIC T6
x3E, x3F, x3G, x3H
EN 60079-0, EN 60079-1,
EN 60079-26
94/9/EC
Intrinsically Safe XEXX-XXXX, EXX-XXXX
x1A, x1B, x1C, x1D
with transmitter codes
x2A, x2B, x2C, x2D
ATEX Ex II 1 G Ex ia IIC T4
x3A, x3B, x3C, x3D
EN 60079-0, EN 60079-11,
EN 60079-26, EN 60079-27
94/9/EC
XEXX-XXXX, EXX-XXXX
x1A, x1B, x1C, x1D
Non-Sparking
with transmitter codes
x2A, x2B, x2C, x2D
ATEX Ex II 3 G Ex ic II T6
x3A, x3B, x3C, x3D
EN 60079-0
EN 60079-11
94/9/EC
IEC
XEXX-XXXX, EXX-XXXX
with transmitter codes
x1E, x1F, x1G, x1H
Flameproof
x2E, x2F, x2G, x2H
IECEx Ex d IIC T6 Ga/Gb
x3E, x3F, x3G, x3H
IEC 60079-0, IEC 60079-1,
IEC 60079-26
XEXX-XXXX, EXX-XXXX
with transmitter codes
x1A, x1B, x1C, x1D
Intrinsically Safe x2A, x2B, x2C, x2D
IECEx Ex ia IIC T4 Ga
x3A, x3B, x3C, x3D
IEC 60079-0, IEC 60079-11,
IEC 60079-26, IEC 60079-27
See appropriate Installation & Operating Manual for entity parameters
for IS installation.
On remote electronics housing only, seal is required within 18 inches.
These units have been tested to
EN 61326 and are in compliance with
the EMC Directive 2004/108/EC.
5
D I M E N S I O N A L
STANDARD
I N C H E S
PRESSURE
S P E C I F I C A T I O N S
MODELS
E3A,
E3B,
E3C,
E3D,
E3E,
E3F
( M M )
4.02
(102)
4.02
(102)
¾" NPT
Dual Conduit
Entries
¾" NPT
Dual Conduit
Entries
4.02
(102)
¾" NPT
Dual Conduit
Entries
A
A
ANSI standard flange
B
D
C
0.87
(22)
2.81
(71)
3.86
(98)
Level range
3.95
(100)
H
10.32
(262)
J
8.10
(206)
4.04
(103)
E
70°
Dia.
F
HT Integral Side/Bottom Mount
Fourth Digit Codes A, B, C
E3A/E3B Series with Integral Top Mounting
Fourth Digit Codes J, K, L
Integral Transmitter Head
2.84 502
(72) (128)
3.99
(101)
¾" NPT Dual Conduit Entries
10.32
(262)
A minus 3.34 (85)
3.85
(98)
A minus 3.34 (85)
D
Level
range
Level
range
G
G
E
F
1" NPT drain
(plug not provided)
Remote Side/Side Mount
Fourth Digit Codes A, B, C
5.31
(135)
45°
6.25 (159)
D
4.02
(102)
3.96 (101)
8.73
(222)
15.95
(405)
6
6.28
(159)
5.42
(138)
6.48
(165)
2.39
(61)
Up to 75' (23 m) of connecting cable part
number 037-3226-0XX or 037-3227-0XX,
run in conduit.
Last 2 digits in part number are cable
length in feet.
Cable must be ordered separately.
E
F
1" NPT drain
(plug not provided)
Remote Side/Side Mount
Fourth Digit Codes A, B, C
15.95
(405)
D I M E N S I O N A L
I N C H E S
Cage Pressure
Rating
S P E C I F I C A T I O N S
( M M )
Process
Conn. Size
Spring
S.G. Range
C
D
E
F
G
H
J
0.23 – 0.54
6.75
(171)
9.31
(236)
9.31
(236)
3.19
(81)
7.00
(178)
3.00
(76)
3.00 + range
(76 + range)
5.43
(138)
0.55 – 1.09
4.75
(121)
7.31
(186)
7.31
(186)
3.19
(81)
7.00
(178)
3.00
(76)
3.00 + range
(76 + range)
5.43
(138)
1.10 – 2.20
4.75
(121)
7.31
(186)
7.31
(186)
3.19
(81)
7.00
(178)
3.00
(76)
3.00 + range
(76 + range)
5.43
(138)
0.23 – 0.54
6.75
(171)
9.31
(236)
9.31
(236)
3.31
(84)
7.13
(181)
3.00
(76)
3.00 + range
(76 + range)
5.43
(138)
0.55 – 1.09
4.75
(121)
7.31
(186)
7.31
(186)
3.31
(84)
7.13
(181)
3.00
(76)
3.00 + range
(76 + range)
5.43
(138)
1.10 – 2.20
4.75
(121)
7.31
(186)
7.31
(186)
3.31
(84)
7.13
(181)
3.00
(76)
3.00 + range
(76 + range)
5.43
(138)
11⁄2"
0.55 – 1.09
6.75
(171)
9.31
(236)
9.31
(236)
3.19
(81)
7.00
(178)
3.00
(76)
3.00 + range
(76 + range)
5.43
(138)
2"
0.55 – 1.09
6.75
(171)
9.31
(236)
9.31
(236)
3.31
(84)
7.13
(181)
3.00
(76)
3.00 + range
(76 + range)
5.43
(138)
11⁄2"
0.55 – 1.09
6.75
(171)
9.31
(236)
9.31
(236)
4.00
(102)
7.87
(200)
3.44
(87)
3.44 + range
(87 + range)
9.08
(231)
2"
0.55 – 1.09
6.75
(171)
9.31
(236)
9.31
(236)
4.38
(111)
8.81
(224)
3.44
(87)
3.44 + range
(87 + range)
10.08
(256)
11⁄2"
0.55 – 1.09
6.75
(171)
9.31
(236)
9.31
(236)
4.00
(102)
9.00
(229)
3.44
(87)
3.44 + range
(87 + range)
10.21
(259)
2"
0.55 – 1.09
6.75
(171)
9.31
(236)
9.31
(236)
4.38
(111)
9.81
(249)
3.44
(87)
3.44 + range
(87 + range)
11.08
(281)
11⁄2"
150#, 300# &
600# ANSI
2"
900# ANSI
1500# ANSI
2500# ANSI
'A' Dimension
Cage Press. Rating Head Flange Size
150# ANSI
300# ANSI
600# ANSI
900# ANSI
Dimension
B
Fourth Digit of Model Number
A, B, C
D, E, F
J, K, L
M, N, P
3"
16.97
(431)
24.97
(634)
12.97
(329)
20.97
(533)
4"
16.97
(431)
24.97
(634)
12.97
(329)
20.97
(533)
6"
17.03
(433)
25.03
(636)
13.03
(331)
21.03
(534)
3"
17.16
(436)
25.16
(639)
13.16
(334)
21.16
(537)
4"
17.28
(439)
25.28
(642)
13.28
(337)
21.28
(541)
6"
17.47
(444)
25.47
(647)
13.47
(342)
21.47
(545)
3"
17.53
(445)
25.53
(648)
13.53
(344)
21.53
(547)
4"
17.78
(452)
25.78
(655)
13.78
(350)
21.78
(553)
6"
18.16
(461)
26.16
(664)
14.16
(360)
22.16
(563)
3"
17.78
(452)
25.78
(655)
13.78
(350)
21.78
(553)
4"
18.03
(458)
26.03
(661)
14.03
(356)
22.03
(560)
6"
18.47
(469)
26.47
(672)
14.47
(368)
22.47
(571)
4"
18.41
(468)
26.41
(671)
14.41
(366)
22.41
(569)
6"
19.53
(496)
27.53
(699)
15.53
(394)
23.53
(598)
4"
19.28
(490)
27.28
(693)
15.28
(388)
23.28
(591)
6"
20.53
(521)
28.53
(725)
16.53
(420)
24.53
(623)
1500# ANSI
2500# ANSI
7
N O N - S T E A M
M O D E L
S E R V I C E
N U M B E R
Models available for quick shipment, usually within one week after factory
receipt of a complete purchase order, through the Expedite Ship Plan (ESP).
DESIGN TYPE
E3
Standard Construction Electronic Modulevel
MOUNTING AND CHAMBER MATERIALS
Flanged top steel
316 SS
A
B
Cage side/bottom
316 SS steel
C
D
Cage side/side
316 SS steel
E
F
Adjustable 8-foot hanger cable, part number 32-3110-001, required when
distance from flange face to top of displacer must be greater than 7.31".
Bolting material is alloy steel.
SPECIFIC GRAVITY AND PROCESS TEMPERATURE
1&4
Integral or Remote
1&4
1&4
1&4
Transmitter Mounting
Use with Mounting/Temp. codes (9th Digit)
3&6
+300° F +400° F
+450° F
+550° F
+600° F
maximum process temperature
(+150° C) (+200° C) (+230° C) (+290° C) (+315° C)
J
K
L
A
B
C
M
N
P
D
E
F
M
N
P
0.23 – 0.54 specific gravity (up to 600 lbs)
0.55 – 1.09 specific gravity (all pressures)
1.10 – 2.20 specific gravity (up to 600 lbs)
PROCESS CONNECTION SIZE & TYPE
External Cage
11⁄2"
2"
A
E
R
F
P
Q
3"
n/a
n/a
G
Top Mount
4"
n/a
n/a
H
Type
6"
n/a
n/a
K
NPT
SW
Flange
CHAMBER PRESSURE CLASS
ANSI Flange rating
150# RF
3
300# RF
4
600# RF
5
900# RF
6
1500# RF 2500# RF 7
8
Pressure rating limited by enclosing tube to 5150 psi @ +100° F
For stainless steel construction on 1500# and 2500# models, consult factory
LEVEL RANGE
14
356
A
All Pressures
32
48
813
1219
B
C
60
1524
D
72
1829
E
600# and below
84
96
108
2134
2438
2743
F
G
H
120
3048
I
TRANSMITTER – ELECTRONICS (see opposite page)
E
8
3
Inches
mm
Code
N O N - S T E A M
M O D E L
S E R V I C E
N U M B E R
OUTPUT/SIL RATING
H
F
4-20 mA/HART, SIL 2
FOUNDATION fieldbus Digital Communications (English only)
MOUNTING/TEMPERATURE
Integral Mount
Maximum Process Temperature
1
+550° F (+290° C)
3
+551° to +600° F (+291° to +315° C)
Remote Mount (FM & CSA only)
Maximum Process Temperature
4
6
+550° F (+290° C)
+551° to +600° F (+291° to +315° C)
Use with Specific Gravity and
Process Temperature codes (4th Digit):
J, K, L, A, B, C, M, N, P, D, E, F
M, N, P
Use with Specific Gravity and
Process Temperature codes:
J, K, L, A, B, C, M, N, P, D, E, F
M, N, P
HOUSING MATERIAL/CONDUIT ENTRY/APPROVAL
Housing Material/Conduit Entry/Approval
1 Cast aluminum, FM/CSA XP, 3⁄4" NPT
2 Cast aluminum, FM XP, M20
3 Cast stainless steel, FM/CSA XP, 3⁄4" NPT
4 Cast stainless steel, FM XP, M20
5 Cast aluminum, FM/CSA IS, 3⁄4" NPT
6 Cast aluminum, FM IS, M20
7 Cast stainless steel, FM/CSA IS, 3⁄4" NPT
8 Cast stainless steel, FM IS, M20
A Cast aluminum, ATEX/IEC IS, 3⁄4" NPT
B Cast aluminum, ATEX/IEC IS, M20
C Cast stainless steel, ATEX/IEC IS, 3⁄4" NPT
D Cast stainless steel, ATEX/IEC IS, M20
E Cast aluminum, ATEX/IEC XP, 3⁄4" NPT
F Cast aluminum, ATEX/IEC XP, M20
G Cast stainless steel, ATEX/IEC XP, 3⁄4" NPT
H Cast stainless steel, ATEX/IEC XP, M20
9th Digit
1,3,4,6
1,3,4,6
1,3,4,6
1,3,4,6
1,3,4,6
1,3,4,6
1,3,4,6
1,3,4,6
1,3
1,3
1,3
1,3
1,3
1,3
1,3
1,3
E3X-XXXX (see previous page)
E
3
9
S T E A M
M O D E L
S E R V I C E
N U M B E R
DESIGN TYPE
E3
Standard Construction Electronic Modulevel
MOUNTING AND CHAMBER MATERIALS
Flanged top steel
316 SS
A
B
Cage side/bottom
316 SS steel
C
D
Cage side/side
316 SS steel
E
F
Adjustable 8-foot hanger cable, part number 32-3110-001, required when
distance from flange face to top of displacer must be greater than 7.31".
Bolting material is alloy steel.
SPECIFIC GRAVITY AND PROCESS TEMPERATURE
Integral
or
Integral Remote
Remote
1&4
2
5
+300° F +400° F +400° F
(+150° C (+200° C) (+200° C)
K
B
K
Integral
or
Integral Remote Transmitter Mounting
Remote
2&5
3
6
Use with Mounting/Temp. codes (9th Digit)
+450° F +500° F +500° F
maximum process temperature
(+230° C) (+260° C) (+260° C)
N
E
N
0.55 - 1.09 specific gravity (all pressures)
PROCESS CONNECTION SIZE & TYPE
External Cage
11⁄2"
2"
A
E
R
F
P
Q
3"
n/a
n/a
G
Top Mount
4"
6"
n/a
n/a
n/a
n/a
H
K
Type
NPT
SW
Flange
CHAMBER PRESSURE CLASS
ANSI Flange rating
150# RF
3
300# RF
4
600# RF
5
900# RF
6
1500# RF 2500# RF 7
8
Pressure rating limited by enclosing tube to 5150 psi @ +100° F
For stainless steel construction on 1500# and 2500# models, consult factory
LEVEL RANGE
14
356
A
All Pressures
32
48
813
1219
B
C
60
1524
D
72
1829
E
600# and below
84
96
108
2134
2438
2743
F
G
H
120
3048
I
TRANSMITTER – ELECTRONICS (see opposite page)
E
10
3
Inches
mm
Code
S T E A M
M O D E L
S E R V I C E
N U M B E R
OUTPUT/SIL RATING
H
F
4-20 mA/HART, SIL 2
FOUNDATION fieldbus Digital Communications (English only)
MOUNTING/TEMPERATURE
Integral Mount
Maximum Process Temperature
1
+300° F (+150° C)
2
+301° to +450° F (+151° to +230° C)
3
+451° to +500° F (+231° to +260° C)
Remote Mount (FM & CSA only)
4
5
6
Use with Specific Gravity and
Process Temperature codes (4th Digit):
K
B, N
E
Maximum Process Temperature
Use with Specific Gravity and
Process Temperature codes (4th Digit):
+300° F (+150° C)
+301° to +450° F (+151° to +230° C)
+451° to +500° F (+231° to +260° C)
K
B, K, N
E, N
HOUSING MATERIAL/CONDUIT ENTRY/APPROVAL
Housing Material/Conduit Entry/Approval
1 Cast aluminum, FM/CSA XP, 3⁄4" NPT
2 Cast aluminum, FM XP, M20
3 Cast stainless steel, FM/CSA XP, 3⁄4" NPT
4 Cast stainless steel, FM XP, M20
5 Cast aluminum, FM/CSA IS, 3⁄4" NPT
6 Cast aluminum, FM IS, M20
7 Cast stainless steel, FM/CSA IS, 3⁄4" NPT
8 Cast stainless steel, FM IS, M20
A Cast aluminum, ATEX/IEC IS, 3⁄4" NPT
B Cast aluminum, ATEX/IEC IS, M20
C Cast stainless steel, ATEX/IEC IS, 3⁄4" NPT
D Cast stainless steel, ATEX/IEC IS, M20
E Cast aluminum, ATEX/IEC XP, 3⁄4" NPT
F Cast aluminum, ATEX/IEC XP, M20
G Cast stainless steel, ATEX/IEC XP, 3⁄4" NPT
H Cast stainless steel, ATEX/IEC XP, M20
9th Digit
1,2,3,4,5,6
1,2,3,4,5,6
1,2,3,4,5,6
1,2,3,4,5,6
1,2,3,4,5,6
1,2,3,4,5,6
1,2,3,4,5,6
1,2,3,4,5,6
1,2,3
1,2,3
1,2,3
1,2,3
1,2,3
1,2,3
1,2,3
1,2,3
E3X-XXXX (see previous page)
E
3
11
Q U A L I T Y
The quality assurance system in place at
Magnetrol guarantees the highest level of
quality throughout the company. Magnetrol
is committed to providing full customer
satisfaction both in quality products and
quality service.
The Magnetrol quality assurance system is
registered to ISO 9001 affirming its commitment to known international quality standards providing the strongest assurance of
product/service quality available.
Several Electronic Modulevel Displacer
Transmitters are available for quick shipment, usually within one week after factory
receipt of a complete purchase order,
through the Expedite Ship Plan (ESP).
To take advantage of ESP, simply match the
color coded model number codes (standard
dimensions apply).
E S P
Expedite
Ship
Plan
Models covered by ESP service are color
coded in the selection data charts.
ESP service may not apply to orders of ten
units or more. Contact your local representative for lead times on larger volume orders,
as well as other products and options.
W A R R A N T Y
All Magnetrol electronic level and flow
controls are warranted free of defects in materials or workmanship for one full year
from the date of original factory shipment.
If returned within the warranty period; and,
upon factory inspection of the control, the
cause of the claim is determined to be covered under the warranty; then, Magnetrol
will repair or replace the control at no cost
to the purchaser (or owner) other than
transportation.
Magnetrol shall not be liable for misapplication, labor claims, direct or consequential
damage or expense arising from the installation or use of equipment. There are no
other warranties expressed or implied, except special written warranties covering
some Magnetrol products.
For additional information, see Instruction Manual 48-635 or 48-640.
5300 Belmont Road • Downers Grove, Illinois 60515-4499 • 630-969-4000 • Fax 630-969-9489 • www.magnetrol.com
145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306
Heikensstraat 6 • B 9240 Zele, Belgium • 052 45.11.11 • Fax 052 45.09.93
Regent Business Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317
Copyright © 2011 Magnetrol International, Incorporated. All rights reserved. Printed in the USA.
Performance specifications are effective with date of issue and are subject to change without notice.
BULLETIN: 48-135.3
EFFECTIVE: July 2011
SUPERSEDES: June 2009