ILI-E3 Series

ILI-E3 Series
Intelligent Loop
Interface-Main Board
Description
ILI-MB-E3
The Intelligent Loop Interface-Main Board (ILI-MB-E3) is
the main interface for the E3 Series® product line. With its
state-of-the-art 32 bit RISC processor, this compact “panel
on a board” provides a powerful addition to GamewellFCI’s single pair conductor solutions. The ILI-E3 Series is
used in the following systems.
• E3 Series Expandable Emergency Evacuation System
• E3 Series Combined Fire and Mass Notification System
This intuitive design provides the following features:
• 2 signaling line circuits
• auxiliary power output
• local energy city box output • auxiliary relay functions
• 2 notification application circuits
These features, combined with the built-in network and the
serial protocols, allow this module to support a host of new
and existing products, resulting in a building block
approach to the fire alarm panel design.
The ILI-MB-E3 is network ready and occupies 1 of 64
nodes operating at 625K baud. In addition, the Addressable Node Expander (ANX) board expands the network to
122 nodes. When this sub-assembly is integrated with
proven Broadband components, the result is a flexible yet
powerful integrated audio solution. When the system transmits to remote locations, the optional RPT-E3 provides the
ILI-MB-E3 with valuable signal boosting and transient protection, as well as connectivity using both wire and fiberoptic cables.
The ILI-MB-E3 provides 2 signaling line circuits and terminals for the connections to up to 159 detectors, 159 modules and 159 addressable sounder bases per SLC in
Velociti®. In CLIP™ mode, each SLC supports 99 detectors
and 99 modules. The RS-485 interface can support a variety of peripheral devices.
The ILI-MB-E3 relay outputs include system alarm, supervisory, and system trouble contacts. The ILI-MB-E3 provides output for a local energy city master box or remote
location which is non power-limited. All other wiring is
Class 2 power-limited.
Features
ILI-MB-E3
ILI-MB-E3 and ILI-S-E3:
Listed under UL® Standard 864, 9th Edition.
Listed under UL Standard UL2572 for Mass Notification.
Network ready integral 625K baud ARCNET.
Supports 115.2K baud RS-232.
Provides signaling line circuits with the following:
- Two Class A, Style 6, 7* or Class B, Style 4 circuits.
- 40 Character user-defined text per device.
- Capacity of 159 sensors, 159 addressable modules
and 159 addressable sounder bases per circuit.
• Includes 8100 Event History Log.
*Style 7 wiring requires the use of the System Sensor
M500X Isolator Modules.
•
•
•
•
•
ILI-MB-E3 Only:
• Automatically adjusts to any NAC End-of-Line Resistor
(EOL) value (1k-55k ohm) for legacy audible/visual
appliances.
• Two notification appliance circuits, Class “A”, Style Z or
Class B, Style Y rated at 2.0 amps. per circuit.
• RS-485 supporting 16 ASM-16 switch modules and/or
ANU-48 LED driver modules.
• Alarm, trouble, and supervisory dry contacts Form “C”,
rated at 2 amp. @ 30 VDC (resistive).
• Supports 1 LCD-SLP display via on-board ribbon cable
connector.
• RS-485 terminal supports an additional 14 LCD-SLP
displays/annunciators, 6 LCD-E3 displays/annunciators,
5 LCD-7100/RAN-7100 remote LED annunciators.
CLIP™ is a trademark of System Sensor.
®
®
®
E3 Series , NetSOLO and Velociti are registered trademarks of Honeywell International
Inc.
® is a registered trademark of Underwriters Laboratories Inc.
UL
SIGNALING
FM
FDNY #: 6175
3025415 COA # 231-06-E 7165-1703:0125
APPROVED
S1869
MEA
Approved
City of
Chicago
Approved
Class1
Class2
High Rise
City of
Denver
Approved
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0605 Rev. N1 page 1 of 2
©2015 by Honeywell International Inc. All rights reserved.
Specifications
ILI-MB-E3
Operating Current:
Alarm Current:
0.081 amp
0.150 amp max.
ILI-S-E3
Operating Current:
Alarm Current:
0.118 amp
0.119 amp
ILI-MB-E3 and ILI-S-E3
ILI-S-E3
Operating Voltage:
ILI-S-E3
The Intelligent Loop Interface - Expansion Board (ILI-S-E3)
provides the E3 Series control panel with 2 additional electrically isolated signaling line circuits. The layout is similar
to the ILI-MB-E3 except a number of components are omitted. The ILI-S-E3 occupies one node on the Broadband
network. The ILI-S-E3 provides 2 signaling line circuits and
terminals for the connections to up to 159 detectors, 159
modules and 159 addressable sounder bases per SLC in
Velociti mode. In CLIP mode, each SLC supports 99 detectors and 99 modules.
Installation
Typically, the ILI-MB-E3 or ILI-S-E3 can be mounted in the
following E3 Series cabinets:
• Cabinet B and D, backbox
• Cabinet B, B-Slim-E3 sub-assembly plate
• Cabinet C, E3-ILI-C sub-assembly plate
• Cabinet C, E3-INCC-C sub-assembly plate
• Cabinet C, E3-INX-C sub-assembly plate
• Cabinet D, E3-INCC-D sub-assembly plate
• Cabinet D, E3-INX-D sub-assembly plate
For instructions on the installation of the ILI-MB-E3 or
ILI-S-E3, refer to the following documents:
• E3 Series® Expandable Emergency Evacuation
Installation/Operation Manual, Part Number: 9000-0574
• ILI-MB-E3 Installation Instructions,
Part Number: 9000-0579
• ILI-S-E3 Installation Instructions,
Part Number: 9000-0569
For information on the ILI95-MB-E3 and ILI95-S-E3, refer
to the ILI95-E3 Series Data Sheet,
Part Number, 9021-60336.
For information on the ANX, refer to the ANX Data Sheet,
Part Number, 9021-60497.
24 VDC FWR (from the PM-9/
PM-9G Power Supply).
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity:
0 to 93%, non-condensing
at 90° F (32° C)
Supervised
Class 2 Power-Limited
SLC 40 Ohms maximum line impedance
0.5 µf maximum line capacitance
Ordering Information
Part Number Description
ILI-MB-E3
ILI-S-E3