Grayhill 72-OPT-4100 datasheet

OpenDAC® I/O System
NETWORK INTERFACES
OpenLT™ (Optomux)
FEATURES
• Each Unit Controls/Monitors up to 32
Analog and/or Digital I/O using OpenLine®
Modules
• Executes On-Board Programs Created
With Borland C
• Network up to 64 OpenLTs per Host Serial
Port, Spanning as Much as 4000 Feet
• Communicate Over RS422 /485 at
Speeds from 9600 Baud to 115.2 KB
• 100% Optomux Compatible, With
Expanded Command Set
• I/O Update Rates of 500 µSec per 32
Digital I/O, and 2 mS per Analog Input
or 2 Analog Outputs
• 64-Bit Floating Point Math
• DIN Rail or Panel Mountable
• CE Certified
APPLICATIONS
Stand Alone Control
Local Control & I/O
Central Processing: Remote I/O
Distributed Processing: Remote I/O
SCADA
OpenDAC® I/O System
RTU
GENERAL DESCRIPTION
The OpenLT™ Optomux™ controller is a remote
slave that responds to Optomux™ commands
from the master or host PC. The 72-OPT-4100
version has memory for Embedded Control
Programs (ECPs) which are control or data
acquisition routines which run locally on the
OpenLT™ and off-load some responsibilities
from the host. ECP routines written for MicroDAC
can be easily transferred to OpenLT™ and vice
versa. By combining MicroDAC, OpenLT™ and
ProMux® the cost/performance of a distributed
control or data acquisition network is optimized
for price and performance.
L-61
OPENLT® UNIT ON OPENDAC® SYSTEM
ANALOG & DIGITAL I/O
EMBEDDED CONTROL PROGRAMS
OpenLT® connects directly to one or two
OpenLine® racks (part number 70LRCK16-48).
Any combination of OpenLine® analog and digital
I/O modules may be used. OpenLTs™ can be
networked to a host PC which execute programs
that monitor the input signals and control the
outputs. In addition to simple ON/OFF
instructions, commands are included which
permit you to:
• Sample analog signals at 2 mS per input
• Flag values above or below prescribed levels
• Capture min/max values
• Calculate the average input signal levels
• Provide linearized thermocouple and
RTD temperature values
• Determine the width of input pulses
• Count pulses at frequencies up to 1000Hz
• Detect rising or falling edges
• Latch momentary input events
• Set the level of analog outputs
• Provide delayed-on or delayed-off outputs
By specifying OpenLT(s)® with the optional 64
KB of flash memory, you can develop and
download C language programs to any of the
networked controllers.
COMMUNICATIONS
™
The host computer and OpenLT(s)
communicate serially over one or two pair of
twisted wires per RS-422/485 in a multi-drop
configuration. They use Optomux™ ASCII format
to code the command and the response
messages. Application programs running on
the host computer issue commands and then
await responses from the OpenLT ™. The
communications speed is selectable between
9.6 and 115.2 KBaud. Each controller on the
network is assigned a unique base address.
The entire network can span 4000 feet.
Diagnostic LEDs show traffic on the network.
Even while an ECP is running on OpenLT®, any
Optomux™ command it receives from the host
will be processed as usual, which allows you to
delegate some or all of the control and data
acquisition responsibility from the host computer.
This reduces communications time and improves
system response.
For embedded or stand-alone applications,
downloaded ECP routines can be initiated on
power-up.
Libraries and the appropriate download utility
are included with the ECP Programmers Manual.
SOFTWARE
Software drivers are available which simplify
the task of interfacing host programs written in
Visual Basic or C to the Optomux network.
Sample programs, set-up and debug utilities
are included on the disk with the drivers. Interface
drivers for most third party software packages
are available through their distributors. Our
Optomux DDE Server dramatically simplifies
data sharing between OpenLTs™ and Windows
applications, such as Microsoft EXCEL (see
Controller Software). Our DLL will assist you in
building custom Windows Man-Machine
Interfaces using Visual Basic, Visual C/C++, or
Borland compilers.
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
OpenDAC® I/O System
DIMENSIONS
In inches (and millimeters)
4.1(104.26)
1.1
(28.22)
3.9 (99.56)
DIN RAIL LATCH
1.0
(25.86)
3.0
(75.69)
2.6
(65.48)
2.3 (57.17)
TO CENTERLINE OF
DIN RAIL CHANNEL
PIN 1
SPECIFICATIONS
ORDERING INFORMATION
Part Number
Description
OpenLT® Network Interface
72-OPT-4000
72-OPT-4100
Analog/Digital OpenLT®
Analog/Digital OpenLT® with 64K flash for C ECP storage
OpenLT® User’s Manuals and Software
72-UMM-D
72-UMM-DDE
72-UMM-DLL
72-UMM-DLL32
72-UMM-E
72-UMM-H
72-UM-OOPT
72-UOL
7W-UM-MDL32
Driver development and protocol definition (includes driver source code)
Optomux DDE server for Windows 3.1
Optomux DLL for Windows 3.1
Optomux DLL for Windows 95/98/NT
C language ECP manual with libraries
Programmer’s manual with Basic and C host drivers and examples
Hardware installation and setup. Includes setup and debug programs
OpenLine® configuration and product data
Windows ECP download Utility
Compatible Components
OpenDAC® I/O Racks
Digital OpenLine® I/O Modules
Analog OpenLine® I/O Modules
Power Supplies
Available from your local authorized Grayhill
Distributor. For prices and discounts, contact
your local sales office, an authorized Distributor or
Grayhill.
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
L-62
OpenDAC® I/O System
Power Supply: 4.75 to 5.25 Vdc
Supply Current (less modules): 300 mA max.
Operating Temperature: 0 to 60°C
Humidity: 95% non-condensing
Microprocessor: V25 @ 10 MHz
Housing Material: ABS/Polycarbonate blend
Connections:
RS-422/485: 5 position pluggable terminal block
Rack: 48-pin Euro DIN (male)
Serial Data:
Format: 10-Bit ASCII, 1 Start, 1 Stop, 8 Data
Integrity: Message Checksum or 4 Pass + CS
Range of Network: Compliant with EIA/TIA
RS485-A (1 standard load per controller).
Operates in multi-drop mode. 64 DIP switch
selectable addresses. May require RS485
repeaters for lengths over 4000 feet or more
than 32 controllers. Consult factory for special
configurations.