68-3091-02 - AquaPUMP Hydronic Circulating Pumps

AquaPUMP™ Hydronic
Circulating Pumps
SUBMITTAL SHEET
APPLICATION
VALVE MATERIALS
The PC3F in-line, wet rotor circulator with universal flange is
designed for applications in closed-loop hydronic heating and
cooling systems, as well as in solar-powered systems. The
pump is non-submersible and for use in dry, frost-free, wellventilated installations.
Casing: Cast Iron
SPECIFICATIONS
Bearings: Ceramic
Motor Housing: Aluminum
Impeller: PP GF50
Shaft: Ceramic
O-Ring/Flange Gaskets: EPDM Rubber
Bearings Plate: Stainless Steel
Control: 3-step switch with manual speed selection.
Motor Protection: The motor includes an internal thermal
overload protection. External motor protection is not required.
Motor Cap: Stainless Steel
Speed Switching: Three speed, with manual selector.
Standards:
Insulation Class F
Temperature Class: TF95
L5
L1
Approvals: UL/cUL 778, File number 4MX8
Temperature, electrical, and pressure specifications are available on
reverse side (ADDITIONAL SPECIFICATIONS).
L3
L2
M32832A
L4
Max. Flow
Max.
Pressure Head
Connections
GMP
LPM
Feet Meters
Bolt Hole
Spacing
Bolt Hole
Weight
lbs.
(kg)
PC3F1558IUF00
15
55.6
19.4
6
3-5/32 in.
1/2 in.
(80.2 mm) (12.7 mm)
PC3F2699IUF00
34
92.7
31
9
PC3F4344IUF00
59
170
17
5.2
Product
Number
Job Name
Engineer
Mechanical Contractor
Contractor’s P.O. No.
Representative
Notes
Dimensions
L1
in. (mm)
L2
in. (mm)
L3
in. (mm)
L4
in. (mm)
L5
in. (mm)
7.8
(3.54)
6.5 (165.5)
5.5 (140)
4.7 (118)
6.6 (167)
3.2 (80.2)
3-5/32 in.
1/2 in.
(80.2 mm) (12.7 mm)
9.5
(4.32)
6.5 (165.5)
6.1 (155)
6.5 (165.5) 7.75 (197)
3.2 (80.2)
3-7/16 in.
1/2 in.
(87.3 mm) (12.7 mm)
11
(5)
8.5 (216)
6.1 (155)
Model(s)
PC3F1558IUF00
PC3F2699IUF00
PC3F4344IUF00
Qty.
6.9 (174)
GPM
8.9 (227)
Head
3.4 (87.3)
Speed
Approval
Service
Tag No.
68-3091-02
FLOW CHART DESCRIPTION
FLOW CURVES
Electrical Data
PC3F1558IUF00
22
Speed 1
Speed 2
Speed 3
Power Current Power Current Power Current
PC3F1558IUF00 32W
0.28A 55W
0.48A 85W
0.74A
Model
PC3F2699IUF00 125W
1.09A
175W
1.52A
205W
1.78A
PC3F4344IUF00 145W
1.26A
185W
1.61A
210W
1.83
Optional and Replacement Parts
20
18
WITHOUT CHECK VALVE
WITH CHECK VALVE
16
14
H 12
(FEET)
10
3
8
Pump Model
Check Valve
Gasket
6
PC3F1558IUF00
PCV100
PCG100
4
PC3F2699IUF00
PCV125
PCG100
2
PC3F4344IUF00
PCV150
PCG150
0
2
1
0
6
4
2
ADDITIONAL SPECIFICATIONS
Temperature Range:
Ambient: 32ºF to 104ºF (0º to 40ºC)
Storage: -40ºF to 100ºF (-40º to 38ºC)
Water: 14ºF to 230ºF (-10º to 110ºC)
[to 200ºF (95ºC) with optional check valve installed]
Electrical:
115VAC +/- 10% 60Hz
Internal thermal overload protection
Amperage: See Electrical Data Table above.
Max. Pressure: 145 psi (at room temperature);
50 psi at 200ºF (93ºC)
10
12
14
18
16
M32852A
PC3F2699IUF00
30
WITHOUT CHECK VALVE
WITH CHECK VALVE
25
20
3
H 15
(FEET)
10
2
1
1
5
0
Min. Inlet Pressure:
167ºF (75ºC): 0.73 psi
194ºF (90ºC): 4.1 psi
Sound: Less than 43 dB(A) at 3.3 feet (1 meter)
8
US GPM
0
5
10
15
20
US GPM
25
30
35
M32833A
PC3F4344IUF00
18
16
WITHOUT CHECK VALVE
WITH CHECK VALVE
14
12
10
H
(FEET) 8
3
6
2
1
4
2
0
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
0
5
® U.S. Registered Trademark
© 2012 Honeywell International Inc.
68-3091—02 M.S. 10-12
Printed in United States
10
15
20
25
30 35 40
US GPM
45
50
55
60
65
M32851A