Thermatel® TD1/TD2 - Magnetrol International

THERMATEL®
TD1/TD2
Thermal
dispersion switch
DESCRIPTION
Thermatel® TD1/TD2 switches can easily be adjusted to
detect flow (gases and liquids), level or liquid-liquid interface. The TD1 is a 24 V DC line powered unit with integral
electronics and a built-in DPDT relay. The TD2 is either
V DC or V AC line powered, has integral or remote electronics and offers additionally LED indication, time delay
and mA output for diagnostics and trending.
With continuous diagnostics, automatic temperature compensation, narrow hysteresis and fast response time,
TD1/TD2 bring you the latest in thermal dispersion
technology.
For FLOW/LEVEL/INTERFACE applications
F E AT U R E S
• Easy field calibration
•
•
•
•
•
•
•
•
•
•
•
– pre-calibration from factory at
request.
Variable flow or Flow/No flow detection of gases and
liquids.
Excellent low flow sensitivity.
Automatic temperature compensation for repeatable
alarm under varying process temperatures.
Continuous diagnostics detect sensor fault.
Continuous monitoring of flow rate versus setpoint via
LED (TD2).
mA output provides repeatable indication of flow rate
and fault detection (TD2).
Flow can be measured over test points (TD2).
Optional retractable fitting for dismantling under process
conditions.
Process conditions up to +450 °C (+850 °F) and 414 bar
(6000 psi).
Integral or remote electronics up to 150 m (500 ft).
Suited for SIL1 and SIL2 loops (full FMEDA report available).
FE T Y I
NT
SA
EGRITY
V EL
LE
MEDIA: all types of gases and liquids.
VESSELS: pipe sizes down to 1/4". Max sensor length up to
3,3 m. Can be installed at any angle vertically/horizontally –
flanged, threaded or with compression fitting with or without
hot or cold tap – ask for bulletin 41-103.
CONDITIONS: Can be used on conductive and non conductive media, very light density to heavy viscous media (up
to 10.000 cP). Can be set to ignore foam, aeration, turbulence, and cavitation.
A P P L I C AT I O N S
Spherical type sensor
Twin tip type sensor
A G E N C Y A P P R O VA L S Œ
Agency
ATEX
IEC
Approval
For TD1 & TD2: II 1/2 G Ex d+ib, d [ib] IIC T5..T4 Ga/Gb,
flameproof enclosure with intrinsically safe probe circuitry (not valid for hermetically sealed relay option)
For TD2 only: II 2 G Ex d IIC T5..T4 Gb, flameproof
enclosure (zone 1)
For TD1 & TD2: Ex d + ib, d [ib] IIC T5/T4 Gb/Ga
For TD2 only: Ex d IIC T5/T4 Gb
FM/CSA
Russian Authorisation Standards
Other approvals are available, consult factory for more details
ΠRefer to bulletin BE 54-105 for ATEX intrinsically safe units.
 Consult factory for proper model numbers and classifications.
Worldwide level and flow solutions
TECHNOLOGY
The unit utilises Magnetrol’s proven thermal dispersion technology. The sensor consists of two RTD (Resistance Temperature
Detector) elements. One is the reference and the second is heated to a temperature above the process temperature. The electronics detect the temperature difference between the two elements. The temperature difference is greatest in air, then decreases when cooling occurs due to a change in media. An increase in the flow rate further decreases the temperature difference.
The set point is adjusted for the switch to alarm at the desired temperature difference. Once the set point is reached, the relay
will change state.
Flow
No Flow/Low Flow
In the absence of flow/low flow,
the self-heated sensor creates a
temperature differential between
the two sensors.
Flow
As media flow increases across
the sensing assembly, heat is
dissipated and temperature differential decreases .
Level
Low Level
In the absence of media, the
self-heated sensor tip creates a
temperature differential
between the two sensors.
High Level
As media contacts the
sensing assembly, heat
is absorbed by the fluid,
decreasing the temperature differential.
A D VA N C E D F E A T U R E S
TEMPERATURE COMPENSATION (TD1 & TD2)
The alarm point of thermal dispersion switches has previously been affected by changing temperatures. With the TD1/TD2, the
effect of changing process temperature has been greatly reduced.
With temperature compensation
Signal
Signal
No temperature compensation
flow
+20 °C (+70 °F)
+65 °C (+150 °F)
+120 °C (+250 °F)
flow
FACTORY CALIBRATION (TD1 & TD2)
TD1/TD2 can be delivered pre-calibrated at a fixed setpoint.
TD2 can be delivered with a complete calibration curve, allowing the customer to field adjust the setpoint by using a voltmeter
at the test points.
2
A D VA N C E D F E A T U R E S ( C O N T. )
FAULT DETECTION (TD1 & TD2)
One of the major concerns is questioning if the switch will
operate when an alarm condition occurs. The TD1/TD2 is
equipped with advanced diagnostics which continuously
monitor the signal from the sensor and indicate if the signal
has gone out of range. In the event of a fault, the alarm relay
will de-energize and the red LED will blink.
In the TD2 the mA output will change to 3,6 mA (Low Level
Fail-safe) or 22 mA (High Level Fail-safe) to indicate a fault.
Relay
Power
LED
NC
C
NO
NC
C
NO
Alarm
LED
POWER
HEATER
TEMP COMP
MEDIA
RANGE
FAILSAFE
FAULT
O G
F A
F S E
O
H F
L F
O L S
N I
Q
L O
L N
Calibration
ALARM
MODEL TD1
TD1
mA OUTPUT (TD2 only)
- for trending: the calibrated setpoint corresponds with a
specific mA value but although not linear, it provides
important process information. With increasing flow or
immerged sensor, the mA signal increases.
- for diagnostics: either 3,6 mA (Low Level Fail-safe) or
22 mA (High Level Fail-safe) output, indicates for an
instrument failure (sensor).
Typical mA signals
20
18
16
14
mA 12
10
8
6
4
Dry
Oil
Water
0
0,3
0,6
TEST POINTS (TD2 only)
Allow the user to periodically check the setpoint and verify
for set point drift. The setpoints read voltage units.
Relay
LED INDICATION (TD2 only)
The LED’s show progressively actual flow/level versus the
calibrated setpoint.
REMOTE ELECTRONICS (TD2 only)
The sensor can be mounted away for 150 m (500 ft). The
order code for the remote electronics includes the sensor
housing.
Πnot for all models - see electronics part number on page 7
0,9
Water Flow - m/s
1,2
1,5
mA Œ
Testpoints Œ
L1
L2
NC
C
NO
NC
TIME
DELAY
C
NO
ALARM
TP2
TP1
Calibration
MODEL TD2
Damping
LED indication
TD2
3
A P P L I C AT I O N S
FLOW
Thermatel® TD1/TD2 switches may be installed in a variety
of flow applications as shown in the illustration below.
Flow/No Flow can be detected in an input line to a primary
tank, or in an output line. They may be installed for overflow
detection in a pipe connected to an overflow tank or
installed in a drain line for Wet/Dry indication. In addition,
due to the capability to detect liquids or gases, the
Thermatel® flow switch may be installed in a gas vent to
detect off-gas from the primary tank.
Flow / No flow
Off gas
Gas vent
Overflow
Input line
Additive flow
Overflow
tank
Leak detection
- Liquid or Gas flow detection
- Maintain a minimum flow rate
- Pump protection
- Cooling air/water
- Lubrication systems
- Chemical feed pumps
- Detect presence of flow
- Relief valves
- Flare lines
Pump Protection
Lubrication Systems
High level
alarm
Low level alarm
Switch at set flow rate
Output line
4
LEVEL
Thermatel® TD1/TD2 switches can be installed in a variety
of level applications as shown in the illustration below. High
or low level alarm applications can be installed in either vertical or horizontal mountings.
output line
Interface
Low Flow
Body
Overflow
tank
Pump protection
- High level
- Low level
- Interface between different media
- Oil/water
- Liquid/foam
- Suitable for any liquid level detection including:
- High viscosity
- High solids content
- Aeration
- Foam
- Insensitive to dielectric, specific gravity, viscosity
Chemical Feed Pump
Relief Valve Monitoring
Cooling Water / Cooling Air
SENSOR DESIGNS
Thermatel offers two sensor tip designs: the twin tip and the
unique spherical tip. Both designs have similar operating
ranges. Both detect flow or level at approximately the same
rate. However, the spherical tip responds faster to a loss of
flow or a dry condition.
Twin tip
Spherical tip
SPHERICAL TIP
The sensing elements are bonded directly to the wall of the tip, providing protection of the sensors.
The spherical tip is recommended for all types of applications: general purpose use, liquid flow applications, high viscosity and
applications where buildup can occur. The spherical tip is suitable for process pressures up to 41,4 bar (600 psi) and can handle process temperatures up to +200 °C (+400 °F).
TWIN TIP
The sensing elements are mounted at the end of each tip.
The twin tip is preferred for air flow applications and is available in corrosion resistant materials including Hastelloy C and
Monel. The twin tip is suitable for process pressures up to 207 bar (3000 psi) and can handle process temperatures up to
+200 °C (+400 °F).
HIGH TEMPERATURE/HIGH PRESSURE (TMH)
This twin tip sensor is suitable for process pressures up to 414 bar (6000 psi) and can handle process temperatures up to
+450 °C (+850 °F).
MINI SENSOR (TMM)
This twin tip sensor is suitable for installing in a tee in smaller pipe sizes. Available with 1/2", 3/4" and 1" NPT connections for
use with appropriate tee connection. The twin tip design provides minimal blockage of the pipe.
LOW FLOW BODY (TML)
This version is used for even lower flow rates with 1/4" and 1/2" connections.
Typical air flow
Typical water flow
18.00
15.00
16.00
14.00
13.00
12.00
10.00
mA
mA
14.00
8.00
6.00
12.00
11.00
10.00
4.00
0
15
Twin Tip
30
45
Spherical Tip
60 m/s
Hastelloy
9.00
8.00
0,0
0,3
0,6
Spherical Tip
0,9
1,2
Twin Tip
1,5 m/s
Hastelloy
Model
Sensor design
Recommended for
TMB
Spherical tip
Same as TMA but can be used with integral electronics up to +200 °C (+400 °F)
TMA
TMC
TMD
TMH
TMM
TML
Spherical tip
Twin tip
Twin tip
Twin tip
Mini twin tip
Low flow body
Best sensitivity for liquid flows / suitable for gas flow – resists heavy coating
Best sensitivity for air/gas flows – resists light coating
Same as TMC but can be used with integral electronics up to +200 °C (+400 °F)
High temperature and/or high pressure conditions – resists light coating
Direct mounting in “T” pieces on small pipe sizes – resists light coating
Detection/control of extreme low flows – resists light coating
5
EXPEDITE SHIP PLAN (ESP)
Several models are available for quick shipment, within max. 4 weeks after factory receipt of purchase order, through the
Expedite Ship Plan (ESP).
Models covered by ESP service are conveniently colour coded in the selection data charts.
To take advantage of ESP, simply match the colour coded model number codes (standard dimensions apply).
ESP service may not apply to orders of ten units or more. Contact your local representative for lead times on larger volume
orders, as well as other products and options.
A complete measuring system consists of:
S E L E C T I O N D ATA
1. THERMATEL® electronics
2. Connecting cable (only applicable for remote mount TD2 units)
3. THERMATEL® sensor
4. Optional: Order code for thread-on mounting flanges
5. Optional: Retractable probe assembly, consult factory for details
6. Optional: Factory calibration, consult factory
TD1
TD2
1. Order code for Thermatel® TD1 electronics
T D 1 - 2 D 0
0 - 0
Integral mount electronics for 24 V DC power supply and with 1 DPDT
8 A DPDT output relay
3
C
APPROVAL
Weatherproof
ATEX/IEC flameproof enclosure with intrinsically safe probe circuitry
0
1
T D 1
2 D 0 0
0
HOUSING / CABLE ENTRY
IP66, Cast aluminium, 3/4" NPT cable entry (2 entries - 1 plugged)
IP66, Cast aluminium, M20 x 1,5 cable entry (2 entries - 1 plugged)
complete order code for Thermatel® TD1 electronics
X = product with a specific customer requirement
6
S E L E C T I O N D A T A ( C O N T. )
1. Order code for Thermatel® TD2 electronics
T D 2
Electronics with continuous LED indication and mA output
7
8
POWER SUPPLY
240 V AC (100-264 V AC)
24 V DC (± 20 %)
OUTPUT
D 0
8 A DPDT relay
H 0
1 A Hermetically sealed DPDT relay
0
1
ACCESSORIES
Blind housing cover
Housing cover with glass window (for aluminium housings only)
0
1
MOUNTING CONFIGURATION
Integral electronics
Remote electronics
APPROVAL Œ
3
C
G
Weatherproof
Zone 0 – for level applications
ATEX/IEC flameproof enclosure with intrinsically safe probe circuitry
- no mA output available
- only available with 8 A DPDT relay option
Zone 1 – for level and flow applications
ATEX/IEC flameproof enclosure
ΠConsult factory for zone 0 applications in combination with hermetically sealed relay.
0
1
2
3
T D 2
0
HOUSING / CABLE ENTRY
IP66, Cast aluminium, 3/4" NPT cable entry (2 entries - 1 plugged)
IP66, Cast aluminium, M20 x 1,5 cable entry (2 entries - 1 plugged)
IP66, Cast stainless steel, 3/4" NPT cable entry (2 entries - 1 plugged)
IP66, Cast stainless steel, M20 x 1,5 cable entry (2 entries - 1 plugged)
complete order code for Thermatel® TD2 electronics
X = product with a specific customer requirement
2. Order code for connecting cable used with weatherproof remote mount TD2 electronics (6-wire cable/shielded).
Consult factory for cable suitable for flameproof enclosure.
0 3 7
3 1 9 8
0 0 3 - 1 5 0 From 3 m (10 ft) min. to 150 m (500 ft) max. Specify in increments of 1 m (3.28 ft)
complete order code for connecting cable
7
CONNECTIONS
Insertion
length
NPT connection
Insertion
length
BSP connection
Insertion
length
Welded flange ANSI - EN (DIN)
Threaded
DIMENSIONS IN mm (inches) – TMA/TMB/TMC/TMD
Standard: 46 (1.81)
With heat extension: 223 (8.78)
Standard: 60 (2.36)
With heat extension: 223 (8.78)
Insertion length
NPT connection
Insertion length
BSP connection
Insertion
length
ø 22,5 (0.88)
ø 22,5 (0.88)
Threaded Sensor
Flanged Sensor
P R E S S U R E / T E M P E R AT U R E R AT I N G – T M A / T M B / T M C / T M D
Sensor
Material
code
TMC, TMD
A, D
TMC, TMD
B
TMC, TMD
C
TMA, TMB
A
Insertion length
All
@ +40 °C (+100 °F)
41,4 bar (600 psi)
Maximum process pressure
@ +120 °C (+250 °F)
@ +200 °C (+400 °F)
33,8 bar (490 psi)
= minimum length
207 bar (3000 psi)
170 bar (2460 psi)
= minimum length
207 bar (3000 psi)
181 bar (2627 psi)
> minimum length
> minimum length
= minimum length
> minimum length
128 bar (1850 psi)
28,6 bar (415 psi)
148 bar (2140 psi)
105 bar (1517 psi)
91,0 bar (1320 psi)
103 bar (1500 psi)
90,6 bar (1313 psi)
80,7 bar (1170 psi)
82,8 bar (1200 psi)
70,3 bar (1020 psi)
65,5 bar (950 psi)
172 bar (2500 psi)
TMA/TMB sensors
147 bar (2125 psi)
161 bar (2340 psi)
137 bar (1980 psi)
TMC/TMD sensors with material code A or D
Insertion length = minimum length
8
Process pressure (bar)
Process pressure (bar)
Insertion length > minimum length
Process temperature (°C)
Process temperature (°C)
S E L E C T I O N D A T A ( C O N T. )
3. Order code for Thermatel® TD1/TD2 – STANDARD SENSOR
T
T
T
T
M
M
M
M
A
B
C
D
Spherical tip
Spherical tip
Twin tip
Twin tip
-
standard
with heat extension
standard
with heat extension
max
max
max
max
+120
+200
+120
+200
°C
°C
°C
°C
(+250
(+400
(+250
(+400
Œ TMA/TMC sensors can handle process temperatures up to +200 °C (+400 °F) with remote electronics.
°F)Œ
°F)
°F)Œ
°F)
MATERIAL OF CONSTRUCTION FOR SENSOR AND PROCESS CONNECTIONŒ
A
B
C
D
316/316L (1.4401/1.4404) stainless steel
Hastelloy® C (2.4819)
Monel® (2.4360)
316/316L (1.4401/1.4404) stainless steel
– TMC/TMD only
– TMC/TMD only
– TMC/TMD only
ΠSensors with material code B or C are not available with retractable probe assembly.
 Not suitable for zone 0 applications in combination with hermetically sealed relay.
PROCESS CONNECTION – SIZE/TYPE
Threaded
1
2
2
1 0
1 0
2 0
3/4" NPT
1" NPT
1" BSP (G 1")
2
2
2
3
3
3
4
4
4
3
4
5
3
4
5
3
4
5
0
0
0
0
0
0
0
0
0
1"
1"
1"
1 1/2"
1 1/2"
1 1/2"
2"
2"
2"
150
300
600
150
300
600
150
300
600
lbs
lbs
lbs
lbs
lbs
lbs
lbs
lbs
lbs
B
B
C
C
D
D
D
D
B
C
B
C
A
B
D
E
0
0
0
0
0
0
0
0
DN
DN
DN
DN
DN
DN
DN
DN
PN
PN
PN
PN
PN
PN
PN
PN
16/25/40
63/100
16/25/40
63/100
16
25/40
63
100
ANSI flanges
EN (DIN) flanges
25
25
40
40
50
50
50
50
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
RF
RF
RF
RF
RF
RF
RF
RF
RF
EN
EN
EN
EN
EN
EN
EN
EN
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
Type
Type
Type
Type
Type
Type
Type
Type
A
B2
A
B2
A
A
B2
B2
INSERTION LENGTH – Specify per cm (0.39") increment
0 0 5
0 0 8
3 3 0
T M
0
Minimum 5 cm (2")
Minimum 8 cm (3.15")
Maximum 330 cm (130")
– sensors with NPT/flanged connection
– sensors with BSP connection
complete order code for Thermatel® TD1/TD2 STANDARD SENSOR
X = product with a specific customer requirement
9
DIMENSIONS IN mm (inches) – TMH
203
(8.00)
Insertion
length
BSP
connection
273
(10.75)
Insertion
length
NPT
connection
Insertion length
Flanged
connection
Ø 21,5
(0.85)
Ø 21,5
(0.85)
P R E S S U R E / T E M P E R AT U R E R AT I N G – T M H
@ +40 °C (+100 °F)
@ +120 °C (+250 °F)
339 bar (4920 psi)
@ +200 °C (+400 °F)
295 bar (4280 psi)
Process pressure (bar)
414 bar (6000 psi)
Maximum process pressure
Process temperature (°C)
10
@ +450 °C (+850 °F)
233 bar (3380 psi)
S E L E C T I O N D A T A ( C O N T. )
3. Order code for Thermatel® TD1/TD2 – HIGH TEMPERATURE / HIGH PRESSURE SENSOR
T M H
High temperature / high pressure twin tip – max +450 °C (+850 °F) / max 414 bar (6000 psi)Œ
ΠNot available with retractable probe assembly.
MATERIAL OF CONSTRUCTION FOR SENSOR AND PROCESS CONNECTION
A
B
D
316/316L (1.4401/1.4404) stainless steelŒ
Hastelloy® C (2.4819)
316/316L (1.4401/1.4404) stainless steel
ΠNot suitable for zone 0 applications in combination with hermetically sealed relay.
PROCESS CONNECTION – SIZE/TYPE
Threaded
1
2
2
1 0
1 0
2 0
3/4" NPT
1" NPT
1" BSP (G 1")
2
2
2
2
3
3
3
3
3
4
4
4
4
4
3
4
5
7
3
4
5
7
8
3
4
5
7
8
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1"
1"
1"
1"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2"
2"
2"
2"
2"
150 lbs
300 lbs
600 lbs
900/1500 lbs
150 lbs
300 lbs
600 lbs
900/1500 lbs
2500 lbs
150 lbs
300 lbs
600 lbs
900/1500 lbs
2500 lbs
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
B
B
B
C
C
C
C
D
D
D
D
D
D
B
C
G
B
C
G
J
A
B
D
E
G
J
0
0
0
0
0
0
0
0
0
0
0
0
0
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
DN
PN
PN
PN
PN
PN
PN
PN
PN
PN
PN
PN
PN
PN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
ANSI flanges
EN (DIN) flanges
25
25
25
40
40
40
40
50
50
50
50
50
50
16/25/40
63/100
250
16/25/40
63/100
250
400
16
25/40
63
100
250
400
RF
RF
RF
RF
RF
RF
RF
RF
RF
RF
RF
RF
RF
RF
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
1092-1
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
Type
A
B2
B2
A
B2
B2
B2
A
A
B2
B2
B2
B2
INSERTION LENGTH – Specify per cm (0.39") increment
0 0 5
0 0 8
0 9 1
T M H
0
Minimum 5 cm (2")
Minimum 8 cm (3.15")
Maximum 91 cm (36")
– sensors with NPT/flanged connection
– sensors with BSP connection
complete order code for Thermatel® TD1/TD2
HIGH TEMPERATURE /HIGH PRESSURE SENSOR
X = product with a specific customer requirement
11
S E L E C T I O N D A T A ( C O N T. )
3. Order code for Thermatel® TD1/TD2 – MINI SENSOR
T M M
Mini twin tip – max +120 °C (+250 °F)Œ
Œ TMM sensors can handle process temperatures up to +200 °C (+400 °F) with remote electronics.
MATERIAL OF CONSTRUCTION FOR SENSOR AND PROCESS CONNECTION
A
316/316L (1.4401/1.4404) stainless steelŒ
ΠNot suitable for zone 0 applications in combination with hermetically sealed relay.
PROCESS CONNECTION – SIZE/TYPE
Threaded
0
1
2
1 0
1 0
1 0
1/2" NPT
3/4" NPT
1" NPT
INSERTION LENGTH – STANDARD
0 0 3
2,5 cm (1")
0 0 5
3 3 0
Minimum 5 cm (2")
Maximum 330 cm (130")
INSERTION LENGTH – SELECTABLE – Specify per cm (0.39") increment
T M M
A
1 0
complete order code for Thermatel® TD1/TD2 MINI SENSOR
X = product with a specific customer requirement
D I M E N S I O N S I N m m ( i n c h e s ) & P R E S S U R E / T E M P E R AT U R E R AT I N G – T M M
46
(1.81)
Insertion length
= 2,5 cm (1")
@ +40 °C (+100 °F)
> 2,5 cm (1")
Insertion
length
207 bar (3000 psi)
Maximum process pressure
@ +120 °C (+250 °F)
@ +200 °C (+400 °F)
105 bar (1517 psi)
91,0 bar (1320 psi)
170 bar (2460 psi)
128 bar (1850 psi)
148 bar (2140 psi)
Insertion length = minimum length
Insertion length > minimum length
Process pressure (bar)
ø 16
(0.63)
Process temperature (°C)
RECOMMENDED FLOW RANGES – TMM
Size
Water
Air
1" “T”
3,8 to 1600 l/h (1 to 420 GPH)
5 to 290 Nm3/h (3 to 170 SCFM)
1/2"
3/4"
12
“T”
“T”
0,75 to 680 l/h (0.2 to 180 GPH)
2 to 900 l/h (0.5 to 240 GPH)
0,85 to 120 Nm3/h (0.5 to 70 SCFM)
2,5 to 170 Nm3/h (1.5 to 100 SCFM)
S E L E C T I O N D A T A ( C O N T. )
3. Order code for Thermatel® TD1/TD2 – LOW FLOW BODY SENSOR
T M L
Low flow body – max +120 °C (+250 °F)Œ / max 400 bar (5800 psi)
Œ TML sensors can handle process temperatures up to +200 °C (+400 °F) with remote electronics.
MATERIAL OF CONSTRUCTION FOR SENSOR AND PROCESS CONNECTION
A
316/316L (1.4401/1.4404) stainless steel
Œ
ΠNot suitable for zone 0 applications in combination with hermetically sealed relay.
PROCESS CONNECTION – SIZE/TYPE
Threaded
T
V
T
V
1
1
0
0
0
0
0
0
1/4"
1/2"
1/4"
1/2"
NPT-F
NPT-F
BSP (G 1/4")
BSP (G 1/2")
MOUNTING BRACKET
0 0 0
1 0 0
T M L
A
0 0
0
None
With carbon steel mounting bracket
complete order code for Thermatel® TD1/TD2 LOW FLOW BODY SENSOR
X = product with a specific customer requirement
D I M E N S I O N S I N m m ( i n c h e s ) & P R E S S U R E / T E M P E R AT U R E R AT I N G – T M L
optional mounting
bracket
2 holes
ø 9,5 (0.37)
51
(2.00)
70
(2.75)
Maximum process pressure
@ +40 °C (+100 °F)
400 bar (5800 psi)
76
(3.00)
89
(3.50)
328 bar (4760 psi)
@ +200 °C (+400 °F)
283 bar (4100 psi)
32
(1.25)
95
(3.75)
Process pressure (bar)
1/4" or 1/2"
NPT or BSP
@ +120 °C (+250 °F)
51 (2.0)
Process temperature (°C)
RECOMMENDED FLOW RANGES – TML
Size
1/4"
1/2"
flow body
flow body
Water
0,02 to 5,7 l/h (0.0055 to 1.5 GPH)
0,04 to 11,5 l/h (0.01 to 3 GPH)
Air
0,006 to 5,75 Nm3/h (0.21 to 200 SCFH)
0,015 to 11,5 Nm3/h (0.53 to 400 SCFH)
13
S E L E C T I O N D A T A ( C O N T. )
4. Optional sensor mounting flanges
Thread-on mounting flanges can only be used in combination with 3/4" NPT process connection sensor.
Consult factory for other sizes or materials.
Thread-on flanges for use with 3/4" NPT-M connections
ANSI B16.5 flanges
316/316L SST
004-5867-022
004-5867-002
1"
150 lbs RF
004-5867-041
3"
150 lbs RF
004-5867-023
1 1/2"
2"
4"
6"
1"
1 1/2"
2"
3"
4"
6"
1"
1 1/2"
2"
150 lbs RF
150 lbs RF
150 lbs RF
150 lbs RF
300 lbs RF
300 lbs RF
300 lbs RF
300 lbs RF
300 lbs RF
300 lbs RF
600 lbs RF
600 lbs RF
600 lbs RF
004-5867-021
Power supply
Alarm
Continuous
Time delay
Error
User interface
Display
Approvals
SIL (Safety Integrity Level)
Housing material
Net weight
14
004-5867-033
004-5867-044
004-5867-026
004-5867-006
004-5867-027
004-5867-007
004-5867-028
004-5867-008
004-5867-029
004-5867-009
004-5867-030
004-5867-010
004-5867-051
004-5867-050
004-5867-046
004-5867-045
004-5867-049
004-5867-048
TD1
004-5867-031
004-5867-032
004-5867-034
004-5867-035
004-5867-053
004-5867-036
004-5867-037
004-5867-038
004-5867-039
004-5867-040
consult factory
consult factory
consult factory
TD2
19,2 to 28,8 V DC
100 to 264 V AC, 50-60 Hz
3,5 W @ 24 V DC
4 W @ 24 V DC or 5 W @ 264 V AC
TMA-A, TMB-A, TMC-A, TMD-A, TMM: 0,003 to 1,5 m/s (0.01 to 5.0 FPS) – water
0,03 to 150 m/s (0.1 to 500 FPS) – air
Power consumption
Flow range
Output
004-5867-003
004-5867-005
004-5867-042
19,2 to 28,8 V DC
004-5867-052
004-5867-004
004-5867-025
Hastelloy C
004-5867-043
004-5867-001
004-5867-024
E L E C T R O N I C S S P E C I F I C AT I O N S
Description
Part No.
Carbon steel
TMM installed in a“T”-piece:
see table on page 12
TML:
see table on page 13
TMC-B, TMC-C, TMC-D, TMD-B,
TMD-C,TMD-D, TMH:
DPDT relay:
0,003 to 0,3 m/s (0.01 to 1.0 FPS) – water
0,03 to 150 m/s (0.1 to 500 FPS) – air
8 A @ 120 V AC / 250 V AC
8 A @ 30 V DC; 0,5 A @ 125 V DC
Hermetically sealed relay not available
Hermetically sealed DPDT relay:
1A @ 28 V DC; 0,5 A @ 125 V DC
Not applicable
non linear mA for trending (not for all models
- see electronics part number on page 7)
Via alarm relay
3,6 mA (Low Level Fail-safe) – 22 mA (High
Level Fail-safe) and alarm relay
Not available
0 to 100 s adjustable (in addition to sensor
response time)
- Local switches for gain setting, function setting and High/Low Level Fail-safe
- Calibration and time delay via potentiometer
LED’s for Power/Alarm status
2 green LED’s (safe condition),
1 yellow LED (alarm setpoint being approached)
1 red LED (alarm condition)
ATEX II 2 G Ex d IIC T5..T4 Gb, flameproof enclosure - TD2 for zone 1
ATEX II 1/2 G Ex d+ib, d [ib] IIC T5..T4 Ga/Gb, flameproof enclosure - TD1 & TD2
(TD2 only with 8A DPDT relay)
IEC Ex d + ib, d [ib] IIC T5/T4 Gb/Ga - TD1 & TD2
IEC Ex d IIC T5/T4 Gb - TD2 only
Other approvals are available, consult factory for more details
Functional safety to SIL1 as 1oo1 / SIL2 as 1oo2 in accordance to IEC 61508 – SFF of
69,3 % (TD1) and 73 % (TD2) – full FMEDA reports and declaration sheets available
IP66/Aluminium A356T6 (<0.20 % copper) or stainless steel
Aluminium: 1,1 kg (2.4 lbs) - integral electronics only
Stainless steel: 2,6 kg (5.7 lbs) - integral electronics only
PERFORMANCE
Description
Specification
Ambient temperature
ATEX/IEC Ex d - T4 & non Ex: -40 °C to +70 °C (-40 °F to +160 °F)
ATEX/IEC Ex d - T5: -40 °C to +40 °C (-40 °F to +104 °F)
Storage: -50 °C to +75 °C (-58 °F to +170 °F)
0-99 %, non-condensing
Meets CE requirements (EN 61326: 1997 + A1 + A2)
Response time
Repeatability
1-10 s typical (dependent on sensor type, application and set point)
< 1 % @ constant temperature
Humidity
Electromagnetic compatibility
S E N S O R S P E C I F I C AT I O N S
Description
Materials
Sensor diameter
Process connection
Sensor length
Process temperature
Max process pressure
Spherical tip - Twin tip sensors
TMA/TMB - TMC/TMD
316/316L (1.4401/1.4404)
Hastelloy® C (2.4819) – TMC/TMD only
Monel® (2.4360) – TMC/TMD only
22,5 mm (0.88")
Threaded: NPT or BSP
Flanged: various ANSI or EN (DIN) flanges
5 - 330 cm (2" - 130")
TMA/TMCŒ: -70 °C to +120 °C (-100 °F to +250 °F)
TMB/TMD: -70 °C to +200 °C (-100 °F to +400 °F)
See info on page 8
HTHP sensor
TMH
316/316L (1.4401/1.4404)
Hastelloy® C (2.4819)
21,5 mm (0.85")
5 - 91 cm (2" - 36")
-70 °C to +450 °C (-100 °F to +850 °F)
See info on page 10
Œ Use remote electronics (TD2) for temperatures > +120 °C (+250 °F) up to max +200 °C (+400 °F) or sensors with heat extension (TMB/TMD) when using
integral electronics.
Description
Mini twin tip sensor
TMM
Materials
316/316L (1.4401/1.4404)
Process temperature
-70 °C to +120 °C (-100 °F to +250 °F)Œ
Sensor diameter
Process connection
Sensor length
Max process pressure
16 mm (0.63")
Threaded: 1/2", 3/4" or 1" NPT
2,5 - 330 cm (1" - 130")
See info on page 12
1/4"
Low flow body
TML
or 1/2" pipe size
Threaded: 1/4" or 1/2" NPT-F or BSP
Not applicable
See info on page 13
Œ Use remote electronics (TD2) for temperatures > +120 °C (+250 °F) up to max +200 °C (+400 °F).
15
DIMENSIONS IN mm (inches)
102
(4.00)
102
(4.00)
without window
113 (4.43)
with window
123 (4.85)
100
(3.95)
Threaded:
46 (1.81)
Welded flange: 60 (2.36)
Heat extension: 223 (8.78)
Threaded:
46 (1.81)
Welded flange: 60 (2.36)
Heat extension: 223 (8.78)
Insertion
length
Insertion
length
max. Ø 22,5 (0.88)
Ø 22,5 (0.88)
Model TD1 with TMC/TMD twin tip sensor
Model TD2 with integral electronics
and TMA/TMB spherical tip sensor
102
(4.00)
102
(4.00)
without window
113 (4.43)
with window
123 (4.85)
19
(0.37)
100
(3.95)
60 (2.36)
70
(2.75)
89
(3.50)
102
(4.00)
2 holes
Ø 9,5
(0.37)
Insertion
length
95
(3.75)
max 150 m (500 ft)
cable is ordered separately
Ø 22,5 (0.88)
Model TD2 with remote electronics
Remote TMA spherical tip sensor
with flanged connection
QUALITY ASSURANCE - ISO 9001:2008
THE QUALITY ASSURANCE SYSTEM IN PLACE AT MAGNETROL GUARANTEES THE HIGHEST LEVEL OF QUALITY DURING THE DESIGN,
THE CONSTRUCTION AND THE SERVICE OF CONTROLS.
OUR QUALITY ASSURANCE SYSTEM IS APPROVED AND CERTIFIED TO ISO 9001:2008 AND OUR TOTAL COMPANY IS COMMITTED TO
PROVIDING FULL CUSTOMER SATISFACTION BOTH IN QUALITY PRODUCTS AND QUALITY SERVICE.
PRODUCT WARRANTY
:2008
ALL MAGNETROL ELECTRONIC AND ULTRASONIC LEVEL CONTROLS ARE WARRANTED FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR ONE FULL YEAR FROM THE DATE OF ORIGINAL FACTORY SHIPMENT. IF RETURNED WITHIN THE WARRANTY PERIOD; AND, UPON FACTORY INSPECTION OF THE CONTROL, THE CAUSE OF THE CLAIM IS DETERMINED TO BE COVERED UNDER THE WARRANTY; THEN, MAGNETROL INTERNATIONAL WILL REPAIR OR
REPLACE THE CONTROL AT NO COST TO THE PURCHASER (OR OWNER) OTHER THAN TRANSPORTATION.
MAGNETROL SHALL NOT BE LIABLE FOR MISAPPLICATION, LABOR CLAIMS, DIRECT OR CONSEQUENTIAL DAMAGE OR EXPENSE ARISING FROM THE INSTALLATION
OR USE OF THE EQUIPMENT. THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED, EXCEPT, SPECIAL WRITTEN WARRANTIES COVERING SOME MAGNETROL
PRODUCTS.
®
UNDER RESERVE OF MODIFICATIONS
Heikensstraat 6, 9240 Zele, België -Belgique
Tel. +32 (0)52.45.11.11 • Fax. +32 (0)52.45.09.93 • E-Mail: [email protected]
DEUTSCHLAND
Alte Ziegelei 2-4, D-51491 Overath
Tel. +49 (0)2204 / 9536-0 • Fax. +49 (0)2204 / 9536-53 • E-Mail: [email protected]
INDIA
C-20 Community Centre, Janakpuri, New Delhi - 110 058
Tel. +91 (11) 41661840 • Fax +91 (11) 41661843 • E-Mail: [email protected]
ITALIA
Via Arese 12, I-20159 Milano
Tel. +39 02 607.22.98 • Fax. +39 02 668.66.52 • E-Mail: [email protected]
RUSSIA
198095 Saint-Petersburg, Marshala Govorova street, house 35A, office 343
Tel. +7-812.702.70.87 • E-Mail: [email protected]
U.A.E.
UNITED
KINGDOM
DAFZA Office 5EA 722 • PO Box 293671 • Dubai
Tel. +971-4-6091735 • Fax +971-4-6091736 • E-Mail: [email protected]
Unit 1 Regent Business Centre, Jubilee Road Burgess Hill West Sussex RH 15 9TL
Tel. +44 (0)1444 871313 • Fax +44 (0)1444 871317 • E-Mail: [email protected]
www.magnetrol.com
BENELUX
FRANCE
BULLETIN N°:
EFFECTIVE:
SUPERSEDES:
OUR NEAREST REPRESENTATIVE
BE 54-110.6
OCTOBER 2013
June 2012