Bulletin 700-HNK
Plug-in Timing Relays
Overview/Product Selection
Bulletin 700-HNK
Table Of Contents
•
•
•
•
•
Product Selection . . . . . .
Accessories . . . . . . . . . . .
Specifications . . . . . . . . .
Approximate
Dimensions . . . . . . . . . . .
The Ultra-Slim Timing Relay is The Smallest Relay Available
It is Perfect for Converting 700-HK Relays Into a Timing Relay
SPDT and DPST-NO Contact Output
Socket Mounted
Timing Range From 0.1 s…10 h
133
133
134
138
Bulletin 700-HNK Miniature Timer with Multiple Time Ranges
Output Modes
Sockets
Outputs
Timing Range
0.1 s…10 min.
700-HN121
SPDT ➊
On-Delay
One Shot
Repeat Cycle, OFF-start
0.1 min…10 h
Repeat Cycle, ON-start
0.1 s…10 min.
700-HN122
DPST-NO ➋
0.1 min…10 h
Cat. No. 700-HNK
SPDT, DPST-NO
Input Voltage
Cat. No.
12V DC
24V DC
24V AC
12V DC
24V DC
24V AC
12V DC
24V DC
24V AC
12V DC
24V DC
700-HNK41AZ12
700-HNK41AZ24
700-HNK41AA24
700-HNK41BZ12
700-HNK41BZ24
700-HNK41BA24
700-HNK42AZ12
700-HNK42AZ24
700-HNK42AA24
700-HNK42BZ12
700-HNK42BZ24
24V AC
700-HNK42BA24
Factorystocked
Item
✔
✔
✔
✔
✔
✔
✔
➊ 5-blade terminal type only.
➋ 6-blade terminal type only.
General Timer Functions
Run/Power Indicator (Green)
(Lit: Power ON)
Main Dial
Set the desired time according to time
range selectable by DIP switch
Output Indicator (Orange)
(Lit: Output ON)
Accessories
Pkg.
Qty.
Cat. No.
Factory-stocked
Item
Screw Terminal Socket — Panel or DIN Rail Mounting
5-blade miniature socket for use with 1-pole, Type 700-HNK41 timers.
Order must be for 10 sockets or multiples of 10.
10
700-HN121
✔
Screw Terminal Socket – Panel or DIN Rail Mounting
8-blade miniature socket for use with 2-pole, Bulletin 700-HNK42 timers.
This socket includes a retainer clip. Order must be for 10 sockets or
multiples of 10.
10
700-HN122
✔
Description
Cat. No. 700-HN121
Cat. No. 700-HN122
Timing Relay, Socket, Retainer Clip Reference Chart
Timer Type
700-HNC
Socket Cat. No.
700-HN121
700-HN122
Retainer Clip Cat. No.
Provided
Provided
133
Bulletin 700-HNK
Plug-in Timing Relays
Specifications ➊
Ratings
Item
Pilot Duty Rating
Rated supply voltage
Pin type
Operating mode
Operating voltage range
Power consumption
Control outputs
120V AC
Make
240V AC
120V AC
Break
240V AC
Hp at 240V AC
Accuracy of operating time
Setting error
Reset time
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
Impulse withstand voltage
Noise immunity
Static immunity
Enclosure rating
Weight
EMC
Approved standards
NEMA B300
24V AC; 12, 24V DC
Plug-in
ON-delay, One Shot, Repeat Cycle OFF start, or Repeat Cycle ON start selectable with DIP switch
85%…110% of rated supply voltage (12 VDC: 90%…110% of rated supply voltage) ➊
24V AC:Relay ON:approx. 0.8 VA (at 24 VAC, 60 Hz)
Relay OFF:0.5 VA (at 24V AC, 60 Hz)
12V DC:Relay ON:approx. 0.4 W (at 12V DC)
Relay OFF:0.1 W (at 12V DC)
24V DC:Relay ON:approx. 0.5 W (at 24V DC)
Relay OFF:0.2 W (at 24V DC)
5 A at 250V AC, resistive load (cosφ = 1)
The minimum applicable load is 10 mA at 5 VDC (P reference value).
Characteristics
30 A
15 A
3A
1.5 A
1/6 Hp
±1% FS max. (1 s range: +1%±10 ms max.)
±15%+50 ms FS max.
Min. power-opening time:
12, 24V DC: 0.1 s max. (including halfway reset)
24V AC: 0.5 s
max. (including halfway reset)
±2% FS max.
±2% FS max.
100 MΩ min. (at 500V DC)
2,000V AC, 50/60 Hz for 1 min. (between operating circuit and control output, or contacts of different poles)
1,000V AC, 50/60 Hz for 1 min. (between non-continuous contacts)
Malfunction:10…55 Hz, 0.5 mm single amplitude
Malfunction:100 m/s2 (approx. 10G)
Operating:-10°C…50°C (with no icing)
Storage:-25°C…65°C (with no icing)
Operating:35%…85%
Mechanical:10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:100,000 operations min. (3 A at 250V AC, resistive load at 1,800 operations/h)
Between power terminals: 1 kV
±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Destruction:8 kV
Malfunction:4 kV
IP20
Approx. 18 g
Emission Enclosure:EN55011 Group 1 class A
Emission AC Mains:EN55011 Group 1 class A
Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:ENV50140:10 V/m (amplitude modulated, 80 MHz…1GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance:ENV50141:10 V (0.15…80 MHz) (level 3)
Immunity Burst:EN61000-4-4:2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
UL508, CSA 22.2 No. 14
Conforms to VDE 0435/P2021 (for built-in use)
Conforms to EN50081-2, EN50082-2, ACA, CE-certified
➊ When using 700-HNK timer in any place where the ambient temperature is more than 50°C, supply 90%…110% of the rated voltages (12V DC: 95%…110% of the
rated voltage).
134
Bulletin 700-HNK
Plug-in Timing Relays
Timing Charts
Note: t: Set time
Rt: Reset time
Timing Chart
Operating Mode
700-HNK41…
t
ON-Delay
Power
t
Output
700-HNK42…
Rt
Rt
t
t
Power (1-5)
Power (1-8)
Time limit contact
NC (4-2)
Time limit contact
NO 4-3, 5-6
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Run/Power
Indicator (PW)
Output indicator
(OUT)
t
Output Indicator
(OUT)
Rt
t
Interval
Power
t
Output
t
Rt
t
Power (1-5)
Power (1-8)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3, 5-6)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Run/Power
indicator (PW)
Output indicator
(OUT)
t
Output indicator
(OUT)
t
Repeat Cycle OFF-Start
Power
t
t
t
Output
t
t
t
t
Power (1-5)
Power (1-8)
Time limit contact
NC (4-3)
Time limit contact
NO (4-3, 5-6)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Run/Power
indicator (PW)
Output indicator
(OUT)
t
t
t
Output indicator
(OUT)
t
Repeat Cycle ON-Start
Power
t
t
t
Output
t
t
t
t
Power (1-5)
Power (1-8)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3, 5-6)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Run/Power
indicator (PW)
Output indicator
(OUT)
t
t
t
Output indicator
(OUT)
Wiring Diagrams
Cat. No. 700-HNK41...
Timer
circuit
OUT
PW
Cat. No. 700-HNK42...
Timer
circuit
OUT
PW
135
Bulletin 700-HNK
Plug-in Timing Relays
Pulse Operation
A pulse output for a certain period can be obtained with a random external input signal. Use the 700-HNK in interval mode as shown in the following timing chart.
Power (3-8)
External short circuit (1-4)
External input (1-3)
Timer
circuit
50 ms
min.
Time limit contact
NO (6-5)
Run/Power indicator (PW)
Output indicator (OUT)
External input
Note:
136
t: Set time
Rt: Reset time
Mode
Terminals
Pulse Operation
Power supply between 3 and 8
Short-circuit between 4 and 1
Input signal between 3 and 1
Operating mode; One shot and all other modes
Power supply between 1 and 8
Bulletin 700-HNK
Plug-in Timing Relays
DIP Switch Settings
Time Ranges
Cat. No.
700-HNK41AZ12
700-HNK41AZ24
700-HNK41AA24
700-HNK42AZ12
700-HNK42AZ24
700-HNK42AA24
700-HNK41BZ12
700-HNK41BZ24
700-HNK41BA24
700-HNK42BZ12
700-HNK42BZ24
700-HNK42BA24
Time Range
Time Setting Range
Setting
Factory-Set
1s
0.1 s…1 s
Yes
10 s
1 s…10 s
No
1 min.
0.1 s…1 min.
No
10 min.
1 min…10 min.
No
1 min.
0.1 min…1 min.
Yes
10 min.
1 min…10 min.
No
1h
0.1 h…1 h
No
10 h
1 h…10 h
No
Note: The left two DIP switch pins are used to select the time ranges.
Operating Modes
Operating Mode
Setting
Factory-set
ON-delay
Yes
One Shot
No
Repeat Cycle OFF-start
No
Repeat Cycle ON-start
No
Note: The right two DIP switch pins are used to select the operating modes.
137
Bulletin 700-HNK
Plug-in Timing Relays
Approximate Dimensions
Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
47
(1.86)
46
(1.81)
12.8
(0.50)
47
(1.86)
46
(1.81)
12.8
(0.50)
6
(0.23)
28.8
31.2 (1.13)
(1.22)
31.2 28.8
(1.22) (1.13)
Bulletin 700-HNK41 SPDT Contact
Approximate Dimensions
Bulletin 700-HNK42 DPST-NO Contact
Approximate Dimensions
30.5
( 1-7/32)
30.5
( 1-7/32)
7.11
(9/32)
11
4
+)
5(+
(A1))
2.03
(5/64)
Five M3.5
x 0.315
➊
3.0 Dia. Holes
(1/8)
Use M3 Screws
87.3
(3-14/32)
7.11
(9/32)
11
4
4.06
(5/32)
12
2
14
3
14
3
39.5
(1-17/32)
35.5
(1-13/32)
+)
5(+
(A1))
54.1
(2-1/8)
4.06
(5/32)
➊
3.0 Dia. Holes
(1/8)
Use M3 Screws
87.3
(3-14/32)
39.5
(1-17/32)
35.5
(1-13/32)
1 (-1)
(A2)
3.5
(4/32)
15.6
(5/8)
2.03
(5/64)
Five M3.5
x 0.315
12
2
1 (-1)
(A2)
3.5
(4/32)
138
6
(0.23)
15.6
(5/8)
60.0
(2-11/32)
Cat. No. 700-HN121
Cat. No. 700-HN122
Wire Size: 2 x 2.5 mm2
Single Wire – Up to #12 AWG
Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG)
(Either Solid or Stranded)
Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb.-in.)
Wire Size: 2 x 2.5 mm2
Single Wire – Up to #12 AWG
Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG)
(Either Solid or Stranded)
Strip Length: 9 mm (3/8i n.) – Torque: 0.8 N•m (7 lb.-in.)
Total height: 700-HN121 + 700-HNK41 is 78.0 mm.
Total height: 700-HN122 + 700-HNK42 is 78.0 mm.
➊ Holes required for mounting [3 mm (1/8 in.) diameter].