Bulletin 1409 Arcing Ground Fault Detection System Specifications Technical Data Response Time 50 ms nominal plus the controller drop-out time Supply Voltage 120V AC, 60 Hz Power Input 3VA Temperature Range The operating ambient temperature range for the sensor is –40…+85°C (–40…+184°F) and for the relay is 0…+65°C (+32…+149°F) Output Contact Rating Make 30 A; Break 3 A; Continuous carrying current 5 A at 120V Typical Wiring Diagrams See Applicable Codes and Laws. Class II with High Current Inhibit Circuit ➊ Ground Fault Relay Internal Circuit Breaker On To Disconnect & Source of Power Pilot Device M NC Off Load NC Ind. C Light C Line L1 L2 L3 M M OL ’s N0 N0 L1 M To Source of 120V, 60Hz Control Voltage OL's L2 Test Winding CT4 CT4 CT3 CT3 GND Internal Printed Circuit Operate Winding CT2 CT2 CT1 CT1 Ground Fault Sensor Internal Coil Clearing Contact Class I without High Current Inhibit Circuit ➊ Motor Source of Power Circuit Breaker Ground Fault Relay Internal Circuit Breaker On Off Load N0 N0 NC NC C Line C L1 L2 Test Winding To 120V, 60Hz Shunt Trip Power Source Motor Controller Contacts CT4 CT4 CT3 CT3 GND Internal Printed Circuit Operate Winding Typical when used with shunt trip circuit breaker ➊ Wiring diagrams are shown in the tripped condition. 5-32 CT2 CT2 CT1 CT1 Ground Fault Sensor Motor Bulletin 1409 Arcing Ground Fault Detection System Approximate Dimensions Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Arcing Ground Fault Relay 4.8(3/16) 89(3-/12) 111(4-3/8) 79.5 (3-1/8) 20(25/32) 114 (4-1/2) 154(6-1/16) Use (4) #8–32 Screws for Mounting Arcing Ground Fault Sensors 4 Holes 10.3 (13/32) Dia. A K 4 Closed Slots 12.7(1/2) x 5.6 (7/32)Dia. (1409–N2 Only) J C C E B F 4 Open Slots 11.9 (15/32) X 5.6 (7/32) For #10 Screws F A E H Dia. D B F G 4 Open Slots Cat. No.1409-N1: 12.7 (1/2) x 7.1 dia.(9/32) Cat. No.1409-N2: 12.7 (1/2) x11.1dia.(7/16) H Dia. D G Cat. No.1409-N3 Cat. No.1409-N4 Cat. No. A B C D E F G H J K 1409-N1 92.6 (3-21/32) 88.9 (3-1/2) 104 (4-3/32) 74 (2-15/16) 67.3 (2-21/32) 56.4 (2-7/32) 92.9 (3-21/32) 39.6 (1-9/16) — — 1409-N2 91.4 (3-19/32) 115.8 (4-9/16) 131.8 (5-3/16) 77 (3-1/32) 88.9 (3-1/2) 88.9 (3-1/2) 120.6 (4-3/4) 63.5 (2-1/2) 69.8 (2-3/4) 54.9 (2-5/32) 1409-N3 73.2 (2-7/8) 144 (5-11/16) 157.2 (6-3/16) 54.9 (2-5/32) 96.8 (3-13/16) 119.4 (4-23/32) 146.1 (5-3/4) 82.6 (3-1/4) — — 1409-N4 77.2 (3-1/32) 169.9 (6-11/16) 182.6 (7-3/16) 59.5 (2-11/32) 123.7 (4-7/8) 138.2 (5-7/16) 171.5 (6-3/4) 108 (4-1/4) — — 5-33