Visio-3 Wire-Start_Stop

I/O Terminal Block
Stop
27
Start
28
29
30
With Vector Control
31
Enable
32
26
24V Common
25
Digital In Common
24
+24V
24 Volt DC
User Supplied
Parameters that need to be
reprogrammed
File - Inputs & Outputs
Group - Digital Inputs
361 (Digital In1 Sel) = 4
362 (Digital In2 Sel) = 5
363 (Digital In3 Sel) = 0
364 (Digital In4 Sel) = 15
365 (Digital In5 Sel) = 16
366 (Digital In6 Sel) = 1
Hardware Enable Circuitry
By default, the user can program a digital input as an Enable input. The
status of this input is interpreted by drive software. If the application
requires the drive to be disabled without software interpretation, a
“dedicated” hardware enable configuration can be utilized. This is done
by removing a jumper and wiring the enable input to “Digital In 6” (see
image of jumper).
1. Remove the I/O Control Cassette & cover.
2. Locate & remove Jumper J10 on the Main Control Board.
3. Re-assemble cassette.
4. Wire Enable to “Digital In 6” (Terminal 32).
5. Verify that [Digital In6 Sel], parameter 366 is set to “1, Enable.”
U
V
Motor
W