3234741_OE_spec_GN_4000_10

GAS SYSTEM
SERIES 4000 NATURAL GAS
10,5 kV / 50 Hz*
SYSTEM RATINGS
Natural gas genset without heat extraction (heat recovery unit not included in delivery)
MTU Onsite
Energy Type
GB 1165 N5
GB 1554 N5
GB 1948 N5
Former
Output
Genset Type
Elect.1) Therm.2) Low Temp.
AoE
kWel. kWth.
kWth. (°C)
L33 (Methane number 70)
12V 4000 L33
1165 (600)
80 (40)
16V 4000 L33
1554 (885)
99 (40)
20V 4000 L33
1948 (1050)
125 (40)
GB 1165 N5
GB 1554 N5
GB 1948 N5
L32 (High ambient temperatures)
12V 4000 L32
1165 (632)
16V 4000 L32
1554 (863)
20V 4000 L32
1948 (1035)
43 (53)
76 (53)
78 (53)
2747
3651
4577
42.4
42.6
42.6
(65.4)
(66.2)
(65.2)
≥ 80
≥ 80
≥ 80
4700x1800x2400
5500x1800x2400
6000x1800x2400
GB 1282 N5
GB 1707 N5
GB 2141 N5
L33 (Highest output)
12V 4000 L33
1282
16V 4000 L33
1707
20V 4000 L33
2141
88 (40)
113 (40)
142 (40)
2974
3991
4985
43.1
42.8
42.9
(65.4)
(67.2)
(66.2)
≥ 80
≥ 80
≥ 80
4700x1800x2400
5500x1800x2400
6000x1800x2400
(664)
(974)
(1158)
Energy
input4)
kW
Efficiency
Elect.
Total
nel. (%) ntot (%)
2731
3649
4560
42.7
42.6
42.7
(64.6)
(66.8)
(65.7)
≥ 70
≥ 70
≥ 70
4700x1800x2400
5500x1800x2400
6000x1800x2400
* NOx < 500 mg/mn3 (NOx < 250 mg/mn3 available)
1) Rated power at nominal voltage, power factor = 1 and nominal frequency
2) from jacket water, tolerance 8%
4) performance data in accordance with ISO 3046, tolerance 5%
5) referenced methane number
All data according to full load, indicated gas mixture cooler water inlet temperature and are subject to technical development.
Methane
Number5)
3) from jacket water and exhaust gas (120°C), tolerance 8%
6) dimensions without exhaust gas heat exchanger
Project specific data on request:
- Other gas types
- Container
Dimensions
(L x W x H)
mm
- Individual data (e.g. flow-/return-temperatures, hot cooling, methane number, assembly space, etc.)
- Gas Processing
GAS SYSTEM
SERIES 4000 NATURAL GAS
10,5 kV / 50 Hz*
SYSTEM RATINGS
Natural gas genset with heat extraction from jacket water (heat recovery unit included in delivery)
MTU Onsite
Energy Type
GR 1165 N5
GR 1554 N5
GR 1948 N5
Former
Output
KWK Type
Elect.1) Therm.2) Low Temp.
AE
kWel. kWth.
kWth. (°C)
L33 (Methane number 70)
12V 4000 L33
1165 600
80 (40)
16V 4000 L33
1554 885
99 (40)
20V 4000 L33
1948 1050
125 (40)
GR 1165 N5
GR 1554 N5
GR 1948 N5
L32 (High ambient temperatures)
12V 4000 L32
1165 632
16V 4000 L32
1554 863
20V 4000 L32
1948 1035
43 (53)
76 (53)
78 (53)
2747
3651
4577
42.4
42.6
42.6
65.4
66.2
65.2
≥ 80
≥ 80
≥ 80
6300x1850x2400
7100x1850x2400
7600x1850x2400
GR 1282 N5
GR 1707 N5
GR 2141 N5
L33 (Highest output)
12V 4000 L33
1282
16V 4000 L33
1707
20V 4000 L33
2141
88 (40)
113 (40)
142 (40)
2974
3991
4985
43.1
42.8
42.9
65.4
67.2
66.2
≥ 80
≥ 80
≥ 80
6300x1850x2400
7100x1850x2400
7600x1850x2400
664
974
1158
Energy
input4)
kW
Efficiency
Elect.
Total
nel. (%) ntot (%)
2731
3649
4560
42.7
42.6
42.7
64.6
66.8
65.7
≥ 70
≥ 70
≥ 70
6300x1850x2400
7100x1850x2400
7600x1850x2400
* NOx < 500 mg/mn3 (NOx < 250 mg/mn3 available)
1) Rated power at nominal voltage, power factor = 1 and nominal frequency
2) from jacket water, tolerance 8%
4) performance data in accordance with ISO 3046, tolerance 5%
5) referenced methane number
All data according to full load, indicated gas mixture cooler water inlet temperature and are subject to technical development.
Methane
Number5)
3) from jacket water and exhaust gas (120°C), tolerance 8%
6) dimensions without exhaust gas heat exchanger
Project specific data on request:
- Other gas types
- Container
Dimensions
(L x W x H)
mm
- Individual data (e.g. flow-/return-temperatures, hot cooling, methane number, assembly space, etc.)
- Gas Processing
GAS SYSTEM
SERIES 4000 NATURAL GAS
10,5 kV / 50 Hz*
SYSTEM RATINGS
Natural gas genset with heat extraction from jacket water (heat recovery unit included in delivery) and
exhaust gas (exhaust gas heat exchanger loose supply)
MTU Onsite
Energy Type
GC 1165 N5
GC 1554 N5
GC 1948 N5
GC 1165 N5
GC 1554 N5
GC 1948 N5
L32 (High ambient temperatures)
12V 4000 L32
1165 1270
16V 4000 L32
1554 1668
20V 4000 L32
1948 2170
43 (53)
76 (53)
78 (53)
2747
3651
4577
42.4
42.6
42.6
88.6
88.2
90.0
≥ 80
≥ 80
≥ 80
6300x1850x2400
7100x1850x2400
7600x1850x2400
GC 1282 N5
GC 1707 N5
GC 2141 N5
L33 (Highest output)
12V 4000 L33
1282
16V 4000 L33
1707
20V 4000 L33
2141
88 (40)
113 (40)
142 (40)
2974
3991
4985
43.1
42.8
42.9
87.6
87.7
88.4
≥ 80
≥ 80
≥ 80
6300x1850x2400
7100x1850x2400
7600x1850x2400
1323
1795
2268
Energy
input4)
kW
Efficiency
Elect.
Total
nel. (%) ntot (%)
2731
3649
4560
42.7
42.6
42.7
87.6
88.1
88.7
≥ 70
≥ 70
≥ 70
6300x1850x2400
7100x1850x2400
7600x1850x2400
* NOx < 500 mg/mn3 (NOx < 250 mg/mn3 available)
1) Rated power at nominal voltage, power factor = 1 and nominal frequency
2) from jacket water, tolerance 8%
4) performance data in accordance with ISO 3046, tolerance 5%
5) referenced methane number
All data according to full load, indicated gas mixture cooler water inlet temperature and are subject to technical development.
Methane
Number5)
Dimensions6)
(L x W x H)
mm
Former
Output
KWK Type
Elect.1) Therm.3) Low Temp.
AE
kWel. kWth.
kWth. (°C)
L33 (Methane number 70)
12V 4000 L33
1165 1228
80 (40)
16V 4000 L33
1554 1662
99 (40)
20V 4000 L33
1948 2098
125 (40)
3) from jacket water and exhaust gas (120°C), tolerance 8%
6) dimensions without exhaust gas heat exchanger
Project specific data on request:
- Other gas types
- Container
- Individual data (e.g. flow-/return-temperatures, hot cooling, methane number, assembly space, etc.)
- Gas Processing
H
DRAWINGS AND DIMENSIONS
L
B
Note: This drawing is provided for reference only and should not be used for planning installation.
ENGINE DATA
90° V
12/16/20
170/210 mm
4.77 lit.
1500 rpm
DESIGN AND EQUIPMENT (EXTRACT)
// Sliding gear starter 24V, 2 x 9 kW
// Gas supply through venturi air-gas mixer with electronically controlled
gas metering valve
// Electronic high-voltage capacitor ignition system with one ignition coil
per cylinder
// Electronic speed governor for speed and power output control with
automatic knocking control
// Oil sump, removable without lifting the engine
Version: 11.04.2013, materials and specifications subject to change without notice due to
technical advances.
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Subject to change. | 3234741 | Edition 01/14 | ENC 2014-01 | Printed in Germany on chlorine-free bleached papaer.
4000
Configuration
No. of cylinders
Bore/Stroke
Cyl. displacement
Rated speed