400V / 50 Hz
NOx < 500 mg/Nm3
SYSTEM RATINGS
Gas genset with optional heat recovery (90°/70°C heating water circuit)
Genset
Type
Engine
Type
MTU 6R400 GS*
MTU 6R400 GS
MTU 6R400 GS
MTU 6R400 GS
MTU 6R400 GS
MTU 12V400 GS*
MTU 12V400 GS
MTU 12V400 GS
MTU 12V400 GS
MTU 12V400 GS
E3066 D3*
E3066 L9
E3066 L9
E3066 L9
E3066 Z5
E3042 D3*
E3042 L9
E3042 L9
E3042 L9
E3042 Z6
Output
Elect.1)
kWel.
119
182
191
201
210
240
357
370
387
420
Therm.2)
kWth.
116
123
103
106
121
220
198
194
199
247
Exhaust3)
kWth. (°C)
82 (110)
143 (120)
149 (120)
154 (120)
132 (120)
151 (100)
256 (120)
264 (120)
274 (120)
257 (120)
Low Temp.
kWth. (°C)
----30 (50)
36 (40)
16 (40)
----51 (50)
63 (40)
31 (40)
Energy
input4)
kW
345
507
534
560
541
665
951
988
1029
1064
Efficiency
Electr.
nel. (%)
34.4
35.9
35.8
35.9
38.8
36.1
37.5
37.5
37.6
39.5
Total
ntot (%)
91.8
88.3
83.0
82.3
85.6
91.9
85.3
83.8
83.5
86.8
Low Temp.
kWth. (°C)
---------
Energy
input4)
kW
337
465
628
879
Efficiency
Electr.
nel. (%)
34.5
35.6
36.2
36.8
Total
ntot (%)
91.2
87.3
90.6
88.5
Methane
number5)
≥ 70
≥ 70
≥ 70
≥ 70
≥ 70
≥ 80
≥ 70
≥ 70
≥ 70
≥ 80
Cogeneration Module 100°/80°C heating water circuit
Genset
Type
Engine
Type
MTU 6R400 GS*
MTU 6R400 GS
MTU 12V400 GS*
MTU 12V400 GS
E3066 DH3*
E3066 LH9
E3042 DH3*
E3042 LH9
Output
Elect.1)
kWel.
116
165
227
323
Therm.2)
kWth.
110
111
198
206
Exhaust3)
kWth. (°C)
81 (120)
130 (120)
143 (120)
249 (120)
* = 1 with 3-Way-Catalyst, NOx < 250 mg/Nm3
1) Rated power at nominal voltage, power factor = 1,0 and nominal frequency
2) Heat output from engine cooling with tolerance of ± 8%
3) Heat output from exhaust (exhaust cooling to 100°C or 110°C or 120°C) with tolerance of ± 8%
4) Performance data in accordance with ISO 3046/I-2002 with tolerance of 5%
5) Referenced methane number
Project specific data on reques:
- different alternator voltage
- different flow-/return-temperatures, hot cooling, methane number, installation conditions etc.
- Container
Methane
number5)
≥ 70
≥ 70
≥ 80
≥ 70
DS
EMA 1
M12*1.5
H
DRAWINGS AND DIMENSIONS
SS
93.25114-0067
93.25114-0067
TP65-230/2/50Hz
L
W
B
Note: This drawing is provided for reference only and should not be used for installation planning.
Dimensions Genset (L x W x H)
---
3400 x 1700 x 2100 mm
3900 x 1900 x 2150 mm
4000 x 1700 x 2200 mm
4000 x 1700 x 2200 mm
-------
Cogeneration module (L x W x H)
3650 x 960 x 1875 mm
3700 x 1900 x 2100 mm
3900 x 1900 x 2150 mm
3700 x 1900 x 2300 mm
3900 x 1900 x 2300 mm
3950 x 960 x 1875 mm
3900 x 1900 x 2100 mm
4000 x 1900 x 2300 mm
ENGINE DATA
3066
Configuration
No. of cylinders
Bore/Stroke
Cyl. displacement
Rated speed
in-line
6
130/155 mm
2.06 lit.
1500 rpm
3042
Configuration
No. of cylinders
Bore/Stroke
Cyl. displacement
Rated speed
90°V
12
130/142 mm
1.88 lit.
1500 rpm
DESIGN AND EQUIPMENT (EXTRACT)
// Sliding gear starter 24V
// Gas supply with electronically controlled gas metering valve
// Electronic high-voltage capacitor ignition system with one ignition coil
per cylinder
// Electronic speed governor for speed and power output control with
automatic knocking control
Any specifications, descriptions, values, data or other information related to dimensions, power or other technical performance criteria of the goods as provided in
this general productinformation are to be understood as non-binding and may be subject to further changes such as but not limited to technical evolution at any time.
Version: 01.08.2014, materials and specifications subject to change without notice due to technical advances.
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Subject to change. | 3232571 | Edition 02/14 | ENC 2014-08 | Printed in Germany on chlorine-free bleached papaer.
Genset Type
MTU 6R400 GS (D3)
MTU 6R400 GS (L9)
MTU 6R400 GS (Z5)
MTU 12V400 GS (D3/L9)
MTU 12V400 GS (Z6)
MTU 6R400 GS (DH3)
MTU 6R400 GS (LH9)
MTU 12V400 GS (DH3/LH9/ZH6)