SPF-1000 Discontinued Datasheet

500, 750, 1000 WATTS
POWER FACTOR CORRECTED
SINGLE OUTPUT, FORCED CURRENT SHARING
SPF-500
SPF-750
SPF-1000
Featuring:
• Forced current sharing for N +1
redundancy
• Universal AC input
• 0.99 typical power factor
• Low ripple and noise
• DC power good and AC power
fail signals
• True remote inhibit
• Monotonic turn-on and turn-off
When you need a single-output power
supply, but want all the proven industry
leading features of our NMX series, the
SPF power supplies can’t be beat. They
incorporate Condor’s high performance,
power factor correction, low cost and
reliable technology. The SPF series
gives you all this and more in low-profile,
compact packages that cost no more than
common single-output switchers without
power factor correction.
STANDARD SPF SERIES
500 WATTS
90-264 VAC INPUT–11” x 5” x 2.5”
MODEL
SPF-500-12
SPF-500-15
SPF-500-24
SPF-500-28
SPF-500-48
OUTPUT RATING PWR OUT
+12V @ 42A
500
+15V @ 34A
500
+24V @ 21A
500
+28V @ 18A
500
+48V @ 10.4A
500
750 WATTS
90-264 VAC INPUT–12.92” x 5” x 2.5”
MODEL
SPF-750-12
SPF-750-15
SPF-750-24
SPF-750-28
SPF-750-48
OUTPUT RATING PWR OUT
+12V
+15V
+24V
+28V
+48V
@
@
@
@
@
62A
50A
31A
27A
16A
1000 WATTS
90-264 VAC INPUT–12” x 8” x 3.38”
MODEL
OUTPUT RATING PWR OUT
SPF-1000-24
+24V @ 42A
1000
SPF-1000-28
+28V @ 36A
1000
SPF-1000-48
+48V @ 21A
1000
Condor D.C. Power Supplies, Inc., A subsidiary of SL Industries, Inc. 805-486-4565 • (800) 235-5929 Fax: (805) 487-8911 http://www.condorpower.com
750
750
750
750
750
500 WATTS
11”x 5”x 2.5”
SPF-500
750 WATTS
12.92”x 5”x 2.5”
SPF-750
1000 WATTS
12”x 8”x 3.38”
SPF-1000
SPF-500
SPF-750
SPF-1000
3.8 lbs - 1.7 kgs
4.7 lbs - 2.1 kgs
10.4 lbs - 4.7 kgs
Dimensions:
Inches
Millimeters
SPECIFICATIONS: ALL MODELS
INPUT
AC Input: 90-264 Vac continuous range, 47 to 63 Hz. 750 W units fused for 15 A. 1000 W
units fused for 20 A.
Power Factor: 0.99 typical at full load. Meets EN61000-3-2.
Inrush: Cold start AC current is less than 50 A at 115 Vac and 100 A at 230 Vac for 500 W
and 750 W models; 90 A at 115 Vac and 180 A at 230 Vac for 1000 W models. Limited by
thermistor.
Brownout Protection: Continuous range units hold regulation to 85 Vac.
Holdup Time: 20 ms minimum after removal of power at full load. (See page 89.)
Efficiency: 75% typical.
AC Power Fail: Provides TTL “0” 5 ms before output voltage goes out of regulation band
upon loss of power.
OUTPUT
Adjustability: User adjustable ±5% minimum.
Line & Load Reg: ±1% over AC input range and 0 to 100% load change.
Ripple & Noise: Less than 1% p-p or 100 mV, whichever is greater.
Remote Sense: Compensates for 250 mV total line drop. Open sense lead protection. (See
Redundancy, below.)
Temperature Coefficient: 0.02% per degree C.
Stability: 0.1% over 8 hours after 30 minutes warm-up.
Transient Response: Output voltage returns to within 1% in less than 500 µs for a 50% load
change. Peak transient does not exceed 5%.
Overload Protection: All outputs are protected against overload and short circuit. Automatic
recovery upon removal of fault.
Overvoltage Protection: Protects load against power supply induced overvoltage. Trip point is
factory set so that output voltage cannot exceed 136% of nominal.
Remote Inhibit: Contact closure to the negative sense line or a TTL level “0” turns off DC
output.
DC Power Good (5V Outputs): Provides a TTL “1” open collector when output is above 4.6 V
nominal.
Redundancy: External OR-ing diodes and forced current sharing provide “N+1” capability.
Remote sense (+S) compensates for additional 0.6 V diode voltage drop. When the current
sharing terminal is connected between units, current sharing remains within 10% of the
unit’s full output current rating.
Reverse Voltage: Protected against reverse voltage up to supply current rating.
ENVIRONMENTAL
Thermal Protection: Shuts down power supply if overheated. Automatic recovery.
Temperature Range: 0° to 50°C at full ratings.
Safety Agencies: Most models are approved to UL1950; CSA 22.2 #234; IEC 950 and TÜV
EN60950, Class 1 SELV., CE 72/23/EEC/93/68EEC (low voltage directive).
Conducted RFI: Meets FCC Part 15, Subpart J, Class A; EN55022 Class B; CISPR 22 Class B.
Output Isolation: Isolated from ground 50 Vdc.
Cooling: Self cooled by internal ball-bearing fans.
OPTIONS:
Consult factory for available options.
AC INPUT (90-264 VAC Continuous Range)
FUNCTION
TB1- (L )
TB1- (N)
TB1- ( )
115 VAC*
230 VAC
Line
Line 1
Neutral
Line 2
Safety Ground Safety Ground
CONNECTOR
Barrier strip #6-32 screws
3/8” centers
DC OUTPUT
FUNCTION
Output
Voltage
MODEL
All SPF-500 models
LOCATION
Terminal +V
Terminal -V
All SPF-750 models
Terminal +V
Terminal -V
SPF-1000-24, 28, and 48 Terminal +V
Terminal -V
SPF-1000-12, and 15
Terminal +V
Terminal -V
CONNECTOR
Bus Bars #8-32
screws 2PL
Bus bars #1/4-20
screws 2PL
Bus bars #10-32
screws 2PL
Bus bars #5/16-18
screws 2PL
STATUS AND CONTROL
FUNCTION
Remote Sense
Power Good
Inhibit
Current Share
AC Power Fail
Aux. Fan Voltage
Signal Ground
SPF-500
J1-2 (+S)
J1-1 (-S)
J1-7
J1-5
J1-6
J1-8
J2-1 (+12V)
J2-2 (Rtn)
J1-10
SPF-750
J1-5 (+S)
J1-4 (–S)
J1-3
J1-2
J1-6
J1-1
N/A
N/A
N/A
SPF-1000
J3-7 (+S)
J3-8 (–S)
J3-5
J3-4
J3-6
J3-3
J3-1 (+12V)
J3-2 (RTN)
N/A
CONNECTOR
AMP MTA type
#640456-6 (J1 - 500 W)
or
#640656-3 (J2 - 500W)
or
#640656-6 (J1 - 750W)
or
#640456-8 (J3 - 1000W)
pin headers (locking)
Condor D.C. Power Supplies, Inc., A subsidiary of SL Industries, Inc. 805-486-4565 • (800) 235-5929 Fax: (805) 487-8911 http://www.condorpower.com