AC1010 • 10 Amp Current Transformer

AC1010 • 10 Amp Current Transformer
Low Cost 50/60Hz Current Transformers
Applications
• Sensing Overload Current
• Ground fault detection
• Metering
• Analog to Digital Circuits
• Competitive pricing due to high volume
production
• Manufactured in an ISO-9001:2000,
TS-16949:2002 and ISO-14001:2004
certified Talema facility
• Fully RoHS compliant
Electrical Specifications @ 20°C ambient
E le c tric al S p e c ific atio n s
Pri mary C urrent
Turns Rati o
Volt per Amp Rati o at 10A for 100 ohm load
Volt per Amp Rati o at 1A for 100 ohm load
D C Resi stance at 20°C
D i electri c Wi thstandi ng Voltage (Hi -pot)
10A nom., 60 A max.
1000:1 nomi nal
0.100 V/A
0.097 V/A
41.8 ohms
4KVrms
Mechanical Specifications
C a se
Encapsulant
Flammi bi li ty
Termi nals
E n viro n me n tal S p e c ific atio n s
Polycarbonate
Epoxy
C onforms to UL94-VO
Pi ns Ø 0.80mm
Storage Temperature
Insulati on Resi stance
%RE vs RL at Rated primary current
(AC1010)
TALEMA
D ate C ode (W/Y)
1010, D ot at start pi n
Approxi mate Wei ght
Tolerance
10000
Load Resistance RL in ohms
Marki ng
16.3 grams
±0.2mm
Output Volts vs Input Current
For various ohmic loads
10
1000
100
10
Infinity
10K
5K
0
2K
100
200
1K
300
400
500
600
Percent ratio error in %
500
200
Typical Excitation Curve
(AC1005~AC1020)
50
100
1
100
0.1
0.01
1
10
100
Input Current in Amps
Dimensions
11.12
23.80
Sec RMS Exciting Voltage in Volts
Output Voltage in Volts
100
-55° to +130°C
100 megohms mi n.
10
1
0.1
0.01
0.1
1
10
100
1000
23.80
Sec RMS Exciting current in mA
TALEMA INDIA
W/Y
AC1010
5±1mm
Ø9.50
2
3
15.24
1
Ø 0.813
Notes:
1) Unless requested, the terminating resistor and the one-turn
primary are not supplied
2) Pin 3: Normally for mechanical support only but will be
used on center tapped designs
1.75
1
7.62
I - Turn
Primary
10A
10mA
RL
1.0V
1/8W
100 ohms
2
Germany: Int.+49 89 - 841 00-0 • Ireland: Int.+35 374 - 954 8666 • Czech Rep: Int.+420 37 - 744 9303 • India: Int.+91 427 - 244 1325
http://www.talema-nuvotem.com
(06-06) CT’s\AC1010