Instrumentation Analog Input Module Select instrumentation

Instrumentation Analog Input Module
Select instrumentation analog inputs when…
…you need to read thermocouples, or you need
differential inputs for high accuracy, or you need
floating 4-20 mA inputs.
n Advanced 16-bit A/D converter for extreme accuracy
n True differential inputs minimize noise and ground loops
n Software selectable ranges – mix inputs on module
n Linearizes and compensates thermocouple readings
n Upscale/downscale thermocouple burnout detection
n Fault tolerant 4-20 mA range with an auto-polarity feature
Performance Specifications
Number of channels
Lowest voltage range
Maximum voltage range
Auto-polarity current range
Thermocouple types (see note)
A/D resolution
Full scale accuracy (@ 20°C)
Input span adjustability
Input offset adjustability
Span temperature coefficient
Offset temperature coefficient
mV and voltage input impedance
4-20 mA input impedance
CMRR (at 50/60 Hz)
DMRR (at 50/60 Hz)
Common mode input voltage:
Between two input terminals
Between inputs and ground
No damage input voltage
Fastest scan rate (all 8 channels)
Maximum ST-Bus power
Isolation (input to ST-Bus)
Operating temperature range
Storage temperature range
Humidity (non-condensing)
8
+/- 0.062 Volts
+/- 10.0 Volts
4-20 mA
J,K,E,R,T,B,C,N,S
16 bits
+/- 0.02%
+/- 25%
+/- 25%
+/- 30 ppm per °C
+/- 30 ppm per °C
200K Ohms
100 Ohms
160 db
66 db
+/- 25 VDC
1200 Volts
+/- 50 VDC
500 mS
1200 mW
1200 VDC
-30 to 70°C
-40 to 85°C
5 to 95%
Note: Thermocouple inputs are cold junction compensated
and reported as °F, °C or 0.1°C.
Ordering Information
Description
8 Inputs w/Wiring Base
Module only
SIXNET , 331 Ushers Rd., Ballston Lake, NY 12019 USA
•
+1 (518) 877-5173
•
FAX +1 (518) 877-8346
Part Number
ST-AI-INS-08U
ST-AI-INS-08M
•
[email protected]
RTD Input Module
Select 100 Ohm RTD inputs when…
…you need accurate temperature measurements
using 100 Ohm platinum RTDs.
Select 10 Ohm copper RTD inputs when…
…you need to interface to existing 10 Ohm copper
RTD sensors.
■ Best performance/lowest cost precision
temperature solution
■ Resistance Temperature Detectors (RTD) are
more accurate than thermocouples
■ RTD linearization is performed in software for
extreme accuracy and repeatability
■ Excitation current is pulsed on only during the
measurement to reduce self-heating of the R TD
Performance Specifications
ST-AI-RTD-06U
6
100 Ohm platinum
Alpha = .00385
or .00392
Compatible lead configurations 2, 3, or 4 wire
Input range
-200 to 850°C
Basic A/D resolution
16 bits
Scaled resolution
0.1°C
Full scale accuracy (@20°C) 0.5°C
Span temperature coefficient +/- 25 ppm/°C
Offset temperature coefficient +/- 25 ppm/°C
Excitation current
250 µA
(pulsed to reduce self-heating)
Maximum lead wire resistance 100 Ohms per
side, balanced
Input protection
+/- 25 VDC
Fastest scan rate (all 6 channels) 700 mS
ST-AI-RTC-06U
6
10 Ohm copper
Number of channels
RTD type
2 or 3 wire
-200 to 260°C
16 bits
0.1°C
1.0°C
+/- 25 ppm/°C
+/- 25 ppm/°C
1.5 mA
40 Ohms per
side, balanced
+/- 25 VDC
700 mS
Ordering Information
Module w/Base
Module Only
100 Ohm RTD Inputs
Description
ST-AI-RTD-06U
ST-AI-RTD-06M
10 Ohm RTD Inputs
ST-AI-RTC-06U
ST-AI-RTC-06M
SIXNET , 331 Ushers Rd., Ballston Lake, NY 12019 USA
•
+1 (518) 877-5173
•
FAX +1 (518) 877-8346
•
[email protected]
8 Channel 4-20 mA Input Module
Select an 8 channel 4-20 mA input module when…
…the convenience of field wiring ready terminals
will simplify your design and reduce panel wiring.
n 12-bit A/D converter for precision measurements
n Field ready wiring saves time and panel space
n Field configurable wiring choice for loop-powered
transmitters or ground return instruments
n Field replaceable shunts reduce maintenance time
Performance Specifications
Number of channels
Input range
A/D resolution
Input resolution
Full scale accuracy (@ 20°C)
Input span adjustability
Input offset adjustability
Span temperature coefficient
Offset temperature coefficient
Input impedance
DMRR (differential rejection
at 50/60 Hz)
Input protection
Fastest scan rate (all 8 channels)
User DC loop power (optional)
Maximum ST-Bus power
Isolation (input to ST-Bus)
Operating temperature range
Storage temperature range
Humidity (non-condensing)
8
4-20 mA
12 bits
6 µA
0.10%
+/- 25%
+/- 25%
+/- 50 ppm per °C
+/- 50 ppm per °C
100 Ohms
66 db
Field-replaceable shunts
5 mS
24 VDC
600 mW
1200 VDC
-30 to 70°C
-40 to 85°C
5 to 95%
Ordering Information
Description
8 Current Inputs w/Wiring Base
Module only
Part Number
ST-AI-20M-08F
ST-AI-20M-08M
SIXNET , 331 Ushers Rd., Ballston Lake NY 12019 USA
•
+1 (518) 877-5173
•
FAX +1 (518) 877-8346
•
[email protected]
High Density 4-20 mA Input Module
Select high density 4-20 mA inputs when…
…reduced panel space and lowest cost are primary
requirements.
n 12-bit A/D converter for precision measurements
n High density modules have lowest cost per point
n Group isolation eliminates ground loops and
interactions with other modules
n Field replaceable shunts reduce maintenance time
Performance Specifications
Number of channels
Input range
A/D resolution
Input resolution
Full scale accuracy (@ 20°C)
Input span adjustability
Input offset adjustability
Span temperature coefficient
Offset temperature coefficient
Input impedance
DMRR (differential rejection
at 50/60 Hz)
Input protection
Fastest scan rate (all 16 channels)
Maximum ST-Bus power
Isolation (input to ST-Bus)
Operating temperature range
Storage temperature range
Humidity (non-condensing)
16
4-20 mA
12 bits
6 µA
0.10%
+/- 25%
+/- 25%
+/- 50 ppm per °C
+/- 50 ppm per °C
100 Ohms
66 db
Field-replaceable shunts
10 mS
600 mW
1200 VDC
-30 to 70°C
-40 to 85°C
5 to 95%
Ordering Information
Description
16 Current Inputs w/Wiring Base
Module only
Application Idea…
Pair this 16 channel 4-20 mA input module
with the current limiter module (on the next
page) for the highest system performance at
the lowest cost.
Part Number
ST-AI-20M-16H
ST-AI-20M-16M
SIXNET , 331 Ushers Rd. Ballston Lake, NY 12019 USA
•
+1 (518) 877-5173
•
FAX +1 (518) 877-8346
•
[email protected]
8 Channel Voltage Input Module
Select a voltage analog input module when…
…all the voltage input signals return to a common
ground point.
■ Software selectable voltage ranges maximize
input resolution
■ Group isolation eliminates ground loops and
interactions with other modules
■ 50/60 Hz rejection eliminates errors from
power line noise
Performance Specifications
Number of channels
Input ranges: bipolar
A/D resolution
Input resolution
Full scale accuracy (@ 20°C)
Input span adjustability
Input offset adjustability
Span temperature coefficient
Offset temperature coefficient
Input impedance
DMRR (differential rejection
at 50/60 Hz)
Input protection
Fastest scan rate (all 8 channels)
Maximum ST-Bus power
Isolation (from ST-Bus)
Operating temperature range
Storage temperature range
Humidity (non-condensing)
8
+/- 1.0, 2.0, 5.0, 10.0 Volts
12 bits
0.6 mV
0.10%
+/- 25%
+/- 25%
+/- 50 ppm per °C
+/- 50 ppm per °C
200K Ohms
66 db
+/- 50 VDC
5 mS
950 mW
1200 VDC
-30 to 70°C
-40 to 85°C
5 to 95%
Visit our web site for
the latest details!
www.sixnet.com
Ordering Information
Description
8 Voltage Inputs w/Wiring Base
Module only
Part Number
ST-AI-10V-08F
ST-AI-10V-08M
SIXNET , 331 Ushers Rd. Ballston Lake NY 12019 USA
•
+1 (518) 877-5173
•
FAX +1 (518) 877-8346
•
[email protected]