EP80-12 - BB

VRLA Rechargeable Battery
Measures
EP80-12
Technology
Values
Innovation
APPLICATION
FEATURES
Absorbent Glass Mat technology for efficient gas recombination
Maintenance free(no water topping-up required)
No free acid(Non-spillable battery)
Can be used in any orientation(excluding used inverted)
The battery is designed for heavy duty cyclic application
Flame-arrestor is installed to ensure safety
Low self-discharge rate, lower than 3% capacity loss per month
UPS
EV
Telecom
Golf-Carts
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
12 V
80Ah @ 20 hour rate F.V.(1.75V/cell)
31.2Kg(68.8lbs.)
B3 (Fitting M6 bolt & nut) I2 is optional
5.0m (Fully Charged )
800 A (5 sec.)
24 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
Container Material
OUTER DIMENSIONS
TERMINAL TYPE
Terminal B3
172
2 (6.77
0.08)
[M6 BOLT & NUT]
[M6 BOLT]
Terminal Hardware Initial Torque: B3 ,I2(5.5Nm±5%)
o
o
Constant power discharge characteristics at 25 C/77 F
Discharge
Time
2.0(0.08)
0.08)
M6X1.0
7.0(0.28)
2 (12.95
24.5(0.96)
329
Terminal I2
7.3(0.29)
25.0(0.98)
11.0(0.43)
Length
329±2.0 (12.95±0.08)
Width
172±2.0 (6.77±0.08)
Container Height
215±2.0 (8.46±0.08)
Total Height
B3:238±2.0 (9.37±0.08)
I2:218.5±2.0 (8.60±0.08)
Standard: ABS( UL 94-HB) EP80-12
Optional: Flame Retardant ABS(UL 94-V0) EP80-12FR
215 2 (8.46 0.08)
238 2 (9.37 0.08)
DIMENSION(mm/inch)
IEC 60896-21/22
JIS C 8704-2
GB/T 19638.2
Unit: W
W
Unit:
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
1586
1015
553
233
161
89.8
47.0
1.75V
1661
1054
569
238
163
91.2
48.0
1.70V
1711
1078
579
240
165
91.7
48.2
1.65V
1751
1093
587
242
166
91.9
48.3
1.60V
1785
1104
593
243
166
91.9
48.3
o
Unit: A
F.V.
(V/cell)
o
Constant current discharge characteristics at 25 C/77 F
Discharge
Time
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
143
89.8
46.5
19.4
13.4
7.49
3.91
1.75V
151
93.3
47.8
19.8
13.6
7.60
4.00
1.70V
156
95.4
48.7
20.0
13.7
7.64
4.02
1.65V
159
96.7
49.4
20.2
13.8
7.66
4.03
1.60V
162
97.7
49.8
20.3
13.8
7.66
4.03
F.V.
(V/cell)
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
A/3
REV. Mar. 2013
Powered by