CEAG requirements / OSRAM electronic control gears QT-FIT8

Product features of OSRAM ECGs in combination with central batteries systems
Manufacturer:
Type / Description:
OSRAM GmbH
81536 München
Criteria:
Operating voltage range DC:
ECG product family: QUICKTRONIC FIT QT-FIT8
CEAG-Data
186 V - 275 V at -10 °C
Description
Fulfilled
Battery voltage range in operation with emergency current
YES
Typical switching time of CEAG devices
YES
YES
Switching time:
from AC to DC
from DC to AC
Switching time of device:
180 ms - 450 ms
180 ms - 450 ms
In accordance with standard1):
DIN EN 60929
Electronic ballasts for fluorescent tube lamps, operating on
alternating current
1)
In accordance with standard :
DIN EN 61347-2-3 (incl. annex J)
Specific requirements for electronic ballasts for fluorescent
lamps operated on alternating current
In accordance with standard1):
DIN EN 61000-3-2
1)
In accordance with standard :
DIN EN 61547
1)
In accordance with standard :
DIN EN 55015
(Measurement on AC and DC)
1)
Designation after VDE 0108 is insignificant due to it not being an ECG standard
2)
Tests not yet completed for annex J
Features:
No-load current of ECG in DCoperation ( without or with a faulty
illuminant )
Max. inrush current per ECG
in AC-operation:
CEAG-Data:
EMC standard for electromagentic compatibility (harmonic
content)
EMC standard for electromagnetic interference, especially for
emergency lighting (immunity)
EMC standard for critical values and measuring methods for
radio shielding of electrical illumination appliances (interference)
Explanation:
2)
YES
YES
YES
YES
Manufacturer's statement:
Nominal value of operation:
2L-CG-S: <10 mA / <28 mA
2L-CG (4-120 W):
<10 mA
2L-CG (7-120 W):
<25 mA
2L-CG (11-120 W): <41 mA
Options for luminaire/EVG-monitoring units,
CEAG-type: 2L-CG, according to catalog
Maximum inrush current:
SKU 4 x 1A (CG) => 60 A/ms per
circuit
SKU 2 x 3A (CG) => 120 A/ms per
circuit
SKU 1 x 6A (CG) => 180 A/ms
SKU 2 x 3A CG-S => 250 A/ms per
circuit
SKU 1 x 6A CG-S => 250 A/ms
Refers to a max. allowable inrush current of ECG within an
electric circuit to consider the maximum contact load of the
electric circuits' change-overs.
see register "Overview"
< 10 mA
Nominal current in AC-operation:
manufacturer-specific
For ascertainment of max. quantity of ECG per electric circuit
see register "Overview"
Nominal current in DC-operation:
manufacturer-specific
dito
see register "Overview"
Luminous flux in DC-operation 186 V
in relation to 230 V
manufacturer-specific
ECG for emergency lighting on battery operation - for planning
> 75 %
The OSRAM ECGs mentioned above fullfill the requirements from the DIN-EN standards on this page. Explicit approval was carried out on those standards
mentioned in the identification.
OSRAM as a manufacturer of electronic control gear is not liable for the faultless function of other components for emergency lighting.
Luminaires for the operation as safety lighting must comply with norm DIN EN 60598-2-22.
Form CEAG
CEAG requirements
overview
Manufacturer:
Type / Description:
OSRAM GmbH
81536 München
ECG type
ECG product family: QUICKTRONIC FIT QT-FIT8
Max. inrush current per ECG in AC operation
Nominal current in ACoperation:
Nominal current in DCoperation:
QT-FIT8 1x18
Ip = 17 A; TH = 200 µs
0.10 A
0.10 A
QT-FIT8 1x36
Ip = 17 A; TH = 200 µs
0.17 A
0.17 A
QT_FIT8 1x58
Ip = 17 A; TH = 200 µs
0.25 A
0.25 A
QT-FIT8 2x18
Ip = 17 A; TH = 200 µs
0.17 A
0.17 A
QT-FIT8 2x36
Ip = 30 A; TH = 240 µs
0.33 A
0.33 A
QT-FIT8 2x58
Ip = 30 A; TH = 240 µs
0.48 A
0.48 A
QT-FIT8 3x/4x18
Ip = 30 A; TH = 240 µs
0.26 A (3x18)
0.34 A (4x18)
0.26 A (3x18)
0.34 A (4x18)
Overview