VPS20-2200 - Triad Magnetics

POWE R TRAN S FO R M E R
CHASSIS MOUNT :
QUICK-CONNECT WORLD SERIES ™
VPS20-2200
Electrical Specifications (@25C)
1. Maximum Power: 43VA
2. Primary - Series: 230VAC@50/60Hz; Parallel: 115VAC@50/60Hz
3. Secondary - Series1: 20.0V CT@ 2.2A; Parallel2: 10.0V @ 4.4A
4. Voltage Regulation: 25% TYP @ full load to no load
5. Temperature Rise: 30C TYP (45C MAX allowed)
6. Insulation Resistance: 100MΩ
7. Recommended Fuse3:
Series: Littelfuse p/n 313 2.5HXP, 2.5A 250V, slow blow, ¼ x 1 ¼ or,
Cooper Bussmann p/n BKMDL-2 ½, 2.5A 250V, ¼ x 1 ¼
Parallel: Littelfuse p/n 313 5.0HXP, 5A 250V, slow blow, ¼ x 1 ¼ or,
Cooper Bussmann p/n BKMDL-5, 5A 250V, ¼ x 1 ¼
D
B
Construction:
Dual bobbin construction with an insulated shroud, both made of a high temperature
material that exceeds UL flammability requirements.
Safety:
These units are designed with 4000VAC isolation between the primary and
secondary, and also, between each winding and the core.
Agency File:
C
UL: File E53148, UL 5085-1 and 2 (formerly UL 506), General Purpose.
File E65390, UL 5085-1 and 3 (formerly UL1585), Class 2/3
CSA: File LR 221330. C22.2 NO. 66, General Purpose.
TUV Certificate No.: R72103639, EN60950, Information Technology
A
6
5
12
11
2
1
8
7
H
A. Dimensions:
Unit: In inches
H
W
D
A
B
C
T
MW
ML
2-11/16
3-1/8
2
2-5/16
1-1/8
5/16
3/16
2-13/16
-
T
B. Mounting Hole Size: 3/16”
C. WT Lbs. : 1.6
Connections4:
Input: Series – 6 and 1, Jumper 5 to 2
Parallel – 6 and 1, Jumper 6 to 2 and 5 to 1
Output: Series – 12 and 7, Jumper 11 to 8
Parallel – 12 and 7, Jumper 12 to 8 and 11 to 7
MW
RoHS Compliance: As of manufacturing date February 2005, all standard products
meet the requirements of 2011/65/EU, known as the RoHS initiative.
W
* Upon printing, this document is considered “uncontrolled”. Please contact Triad Magnetics’
website for the most current version.
1
Non-Inherently limited. Class 2 not wet, Class 3 wet.
2
Non-Inherently limited. Class 2.
3
Fuse must be used on secondary as conditions of acceptability for UL Class2/3 operation.
4
Primary and secondary windings are designed to be connected in series or parallel. Winding are not
intended to be used independently.
Web: www.TriadMagnetics.com
Phone 951-277-0757
Fax 951-277-2757
460 Harley Knox Blvd.
Perris, California 92571
6
12
5
2
11
8
1
7
SCHEMATIC
Publish Date: December 4, 2013