Information - Weidmuller

CB4200 Series Supplementary Circuit Breakers
Circuit Breakers
Thermal Magnetic Type
CB4200 Series
Single Pole
CB4200 Series
Double Pole
•
•
•
•
•
Rated from 0.05 to 16.0 amps
Available in single or double pole configurations
Features a tease free design to reduce contact damage
Offers push button trip/reset function
Trip free design means the breaker cannot be held
closed against a fault
• Mounts on 32mm* or 35mm DIN-rail
• UL 1077 recognized
• CSA C22.2 No. 235
Ordering Data
Type: Single Pole
Type: Double Pole
Current Part No. TS 35
Current Ratings
*For TS 32 Rail, Ratings
(amps)
see adapter below
(amps)
0.05
91240835000.05
0.08
91246535000.08
0.1
91041735000.1
0.2
91041835000.2
0.3
91298135000.3
0.4
91240935000.4
0.5
91010035000.5
0.6
91241135000.6
0.7
91295635000.7
0.8
91011035000.8
1.0
91012035001.0
1.2
91013035001.2
1.3
91241235001.3
1.4
91241335001.4
1.5
91014035001.5
1.8
91241435001.8
2.0
91015035002.0
2.5
91016035002.5
3.0
91017035003.0
3.5
91241635003.5
4.0
91043535004.0
4.5
91241735004.5
5.0
91018035005.0
5.5
9107833500 5.5
6.0
91038135006.0
6.5
91200435006.5
7.0
91041535007.0
8.0
91030035008.0
9.0
91046135009.0
10.0
910190350010.0
11.0
912418350011.0
12.0
910784350012.0
13.0
912419350013.0
14.0
910785350014.0
15.0
910200350015.0
16.0
912421350016.0
Part No. TS 35
*For TS 32 Rail,
see adapter below
9124223500
9124233500
9120353500
9124243500
9124263500
9124273500
9129583500
9124283500
9124293500
9129593500
9129613500
9129623500
9124313500
9124323500
9129633500
9124333500
9129643500
9129653500
9129663500
9124343500
9129713500
9124353500
9129673500
9124363500
9124373500
9124383500
9124393500
9104673500
9124423500
9129683500
9124433500
9124443500
9124453500
9124463500
9129693500
9124473500
Trip Curves
Thermal Magnetic Type
Typical time/current characteristics at 23°C
CB4200 Series
*Adapter foot – dimensions in mm (in.)
0.05 to 7.5 A
100
100
Trip time in seconds
1,000
Trip time in seconds
1,000
10
1
TS32 adapter
0.01
0.01
2
3
4
6
8 10
20 30
… times rated current
50 70 100
9102100000
1
0.1
0.8 1
–30°C
+23°C
+55°C
10
0.1
0.001
8 to 16 A
20
–30°C
+23°C
+55°C
M1+
10,000
(.787)
M1+
10,000
0.001
0.8 1
2
3
4
6
8 10
20 30
50 70 100
… times rated current
27
CB4200 Series Supplementary Circuit Breakers
CB4200 Series
Double Pole
CB4200 Series
Single Pole
Internal Wiring Diagram
Internal Wiring Diagram
Dimensions in mm
Technical Data
Rated voltage & current†
Creepage resistance
Dielectric strength
Insulation resistance
Interrupting capacity
(VDE 0660, Part 101, P-2)
UL
CSA
VDE
Interrupting capacity; 4201
(UL 1077/EN 60934 PC1)
Typical life at 2 x rated current
Shock
Torque
Vibration
Temperature range
Corrosion
Humidity
Weight
Wire size (UL)
Accessories
Jumpers
Daisy Chain 50*
Straight CQB**
insulated
Angled CQB**
insulated
Adapter foot (for TS 32 Rail)
Busbar
Busbar end cap for 6720000227
Power lug for 6720000227
Single pole 1 meter
Type
BDC 50
CQB 2
CQB 3
CQB 4
CQB 10
CQB 2
CQB 3
CQB 4
CQB 10
MCBAF/TS 32
Part No.
9970290000
9970560000
9970570000
9970580000
9970590000
9970600000
9970610000
9970620000
9970630000
9102100000
6720000227
6720000225
6720000226
28
Note: Resistive and inductive loads (0.05 - 16 A)
*BDC will accommodate 20 A per pin, 20 A total
**CQB will accommodate 18 A per pin, 18 A total; dedicated to 4201 Series
***Please specify horizontal or vertical print when ordering.
Standard quantity = 144 tags per card.
†
Marking Tags
Note:
Part numbers are shown
for
a single card of pre-printed
tags
numbered 1-50.
Dimensions in mm
Voltage Ratings
Current Ratings
AC 250 V, DC 65 V, 50/60 Hz
0.05…16 A
AC 250 V, DC 65 V, 50/60 Hz
0.05…16 A
AC 250 V, DC 65 V, 50/60 Hz
0.05…16 A
PTI 600 to IEC 112
4,000 VAC; IEC 664 & 664 A
> 100 MM (DC 500 V)
4201-10
Maximum capacity
0.05…0.8 A
Self-limiting
1…2 A
200 A
2.5…16 A
400 A
Rated current
Rated voltage
Maximum capacity
0.05…2.0 A
AC 250 V
200 A
2.0…16 A
AC 250 V
200 A
20 A
AC 125 V
400 A
5,000 operations
25 g (11 ms) to IEC 68-2-27, Test Ea
1.2 Nm
5 g (57 to 500 Hz / ±0.38 mm, 10 to 57 Hz) to IEC 68-2-6, Test Fc
-30°C…+55°C (-22°F…+131°F)
96 hours at 5% salt spray, to IEC 68-2-11, Test Ka
240 hours at 95% RH, to IEC 68-2-3, Test Ca
60 g per pole
#20…8 AWG
solid/0.5…6 mm2
Special print only
Consecutive horizontal
Consecutive vertical
WS 8/5 MC
DEK 5/5 DEK 5/5 1640750000***
0473460001
0473560001