Description
Analog signals, such as 4-20 mA current loops, can
be protected with the PLUGTRAB PT 1X2… or PT
2X2… series. These modules provide protection for one
(PT 1X2…) or two (PT 2X2…) pairs of signal circuits.
The PLUGTRAB is installed in one of two base elements:
the PT…+F-BE base provides isolation between the shield
and ground while the PT…-BE base bonds the shield to
ground. The bond in the PT…-BE base provides a drain for
noise collected on the shield. Using the PT…+F-BE base
prevents unwanted ground loops by isolating the shield
and ground.
Pair 1
Signal
12
10
Field
Devices
11
9
11
9
5
7 3
1
6
4 8
2
OUT
12
10
5
3 7
1
Shield
IN
6
8 4
2
OUT
IN
PT 1X2+F-BE base
Control
Panel
PT 1X2-BE base
Figure 1. Typical Base Wiring for PT 1X2
Pair 1
Pair 2
Pair 1
Signal
12
10
Field
Devices
Pair 1
Pair 2
Pair 2
11
9
11
9
5
7 3
1
6
4 8
2
OUT
IN
PT 2X2+F-BE base
Figure 2. Typical Base Wiring for PT 2X2
12
10
5
3 7
1
Shield
6
8 4
2
OUT
IN
PT 2X2-BE base
Control
Panel
Analog Signal Protection
1.1 Proper Grounding
The PLUGTRAB prevents surge energy from reaching the
control equipment by diverting this energy to the ground
circuit. Figure 3 shows a grounding block attached to the
DIN rail. A ground wire should be connected from the
grounding block to the AC power ground. The wire should
be:
During a surge event, energy can come from several signal
cables. If multiple PLUGTRABs are used to protect different signal lines, they will all divert the surge energy to the
ground, via the DIN rail, requiring a large diameter wire.
−− the same diameter/gauge as the power ground wire.
−− not placed next to or near a signal wire.
Unprotected
IN
Protected
OUT
Protection of
Control Equipment
Controller
Input/Output
Analog IN
IN
OUT
Analog OUT
To Common
Ground
Figure 3. Proper grounding with the PT…X2-BE
90
52
66
45
Figure 4. Dimensions
2
Phoenix Contact
2554A
Analog Signal Protection
2
Products
Description of analog one circuit protection
Type
PLUGTRAB plug, 5 V DC
PT 1X2-5DC-ST
2856016
PLUGTRAB plug, 12 V DC
PT 1X2-12DC-ST
2856029
PLUGTRAB plug, 24 V DC
PT 1X2-24DC-ST
2856032
PLUGTRAB plug, 12 V AC
PT 1X2-12AC-ST
2856045
PLUGTRAB plug, 24 V AC
PT 1X2-24AC-ST
2856058
PLUGTRAB base element, accepts PT 1X2 plugs
PT 1X2-BE
2856113
PLUGTRAB base element, includes integrated gas discharge tube,
accepts PT 1X2 plugs
PT 1X2+F-BE
2856126
Description of analog two circuit protection
Type
PLUGTRAB plug, 5 V DC
PT 2X2-5DC-ST
2838241
PLUGTRAB plug, 12 V DC
PT 2X2-12DC-ST
2838254
PLUGTRAB plug, 24 V DC
PT 2X2-24DC-ST
2838228
PLUGTRAB plug, 12 V AC
PT 2X2-12AC-ST
2838270
PLUGTRAB plug, 24 V AC
PT 2X2-24AC-ST
2838283
PLUGTRAB base element, accepts PT 2X2 plugs
PT 2X2-BE
2839208
PLUGTRAB base element, includes integrated gas discharge tube,
accepts PT 2X2 plugs
PT 2X2+F-BE
2839224
3
Order No.
Order No.
Accessories
Description
Type
Tester, for checking the functions of TRABTECH protective devices,
includes adapter for PLUGTRAB devices
CHECKMASTER
2838924
Test Adapter, for PLUGTRAB
CM-PA-PT/A
2816933
2554A
Phoenix Contact • P.O. Box 4100 • Harrisburg, PA 17111-0100 • USA
Sales: 1-800-888-7388 • Technical Service: 1-800-888-7388
www.phoenixcontact.com
Order No.
3