Emergency Lighting - Emerson Network Power

Emergency Lighting - ELSX Modular Static Inverter Unit
3 Phase 25kVA - 125kVA
Benefits
n Performance
n Pure sine wave output
n Higher lighting levels when compared
to self contained emergency lighting
n Most standard AC luminaires can be
used, no need for modification.
It should be ensured that all fittings
selected for emergency lighting
comply with EN60598-2-22, therefore
must not be 2 pin, have glow starters
or be lamps with built in starters
n More energy efficient than self contained
lighting offering cost savings year on year
n Best in class electrical performance for
3 phase Emergency Lighting requirements
n Installation
n Removable top entry gland plate
n Integral 100mm plinth (excluding
distribution) to allow good manouverability
n Allows load to be distributed across
3 phases - smaller cabling required
n Front access enclosures keeps footprint
to a minimum
n Operational
n Central point for maintenance and
testing therefore less disruptive to
daily working routines
n Hot swappable modules reducing
Mean Time To Repair (MTTR)
n Comprehensive and easy to use
diagnostic display
Key Features
n
n
n
n
n
n
n
Pure sine wave output
Modular hot swappable
Fully compliant with BS EN 50171:2001
High efficiency = High energy savings
Battery deep discharge protection
Full LCD and LED display
Enclosure protection to IP21 as standard
(options up to IP54 are available)
Applications
n
n
n
n
n
n
n
n
n
Commercial
Retail
Hotels
Sports and Leisure Facilities
Cinemas
Museums
Airports
Hospitals
Manufacturing
The ELSX range of Static Inverter Units offer a reliable, proven and space
saving solution for Emergency Lighting requirements.
The ELSX is a modular system utilising hot swappable technology ensuring that repair
time on your life safety system is kept to a minimun. The ELSX is compact, easy to
maintain and fully compliant to BS EN50171:2001. The ELSX is robust and designed to
meet the most demanding on site requirements.
System Operation
Active Standby
Mains Healthy
Mains Failed
Emergency Lighting - ELSX Modular Static Inverter Unit
3 Phase 25kVA - 125kVA
Technical Data
System Input
Enclosure
n Zintec Steel - RAL 7035
n Key lockable doors
n Front access enclosure for ease of maintenance
n Top cable entry with removable gland plate
n IP21 for standard enclosures
Voltage: 400VAC 3ph
Voltage range: +/- 10%
Frequency: +/- 15%
Battery Charger
n Microprocessor controlled, power factor corrected
n Temperature compensated
n Constant voltage, current limited rectifier
n Protection against reverse battery polarity
n Protection against battery over voltage, input mains
low and mains surges
n Low volts disconnect
Inverter
n Modular with hot swappable capability
n High frequency microprocessor controlled
PWM IGBT inverter
n Pure sine wave output
n Galvanic isolation with ground neutral (when supplied
with optional output transformer)
Load Circuit
n Single or multiple outputs can be offered as maintained,
non maintained or a combination of both
n Solid state switching device
Remote Monitoring
n Volt free contacts for: Common Alarm, Static
Inverter Fault, Battery Discharging, Low Battery
Volts, Load on Inverter, Load on Bypass - contacts
rated at 1A, 24V AC/DC
Datalogger
n 1024 historical records can be retrieved for reference
and diagnosis
Display
n A 320 x 240 user friendly graphic display allowing the
user to browse the parameters for input, output, load,
batteries and current Static Inverter status
System Output
Voltage: 400VAC 3ph
Voltage regulation: +/- 1%, static balanced load
Output frequency: 50Hz
Frequency regulation: +/- 2% synchronised
+/- 0.2% free-running
Wave form: Sine wave
DC / AC Efficiency: >95%
Load power factor: 0.5 lag - 0.5 lead
Overload: 120% continuous
Operating temperature: 0 to 40°C (inverter only)
LCD Digital Meter (Readings)
n
n
n
n
n
n
Mains input - voltage and frequency
Inverter - AC voltage / current / kVA / % load / frequency
DC volts
DC discharge current
Charge current
Maintained output - AC voltage / frequency
Alarms
n
n
n
n
n
n
n
n
n
n
n
n
n
Mains fail
Charge fail
Inverter fail
Boost charge (NiCd batteries only)
Battery disconnected
DC over voltage
Battery test - 10 minute / rated standby test
Battery fail
Cooling fan fail
Inverter overload
Inverter over temperature
Short circuit
Battery low volts
Fully Compliant with the Following Standards
n
n
n
n
Emerson Network Power
George Curl Way, Southampton SO18 2RY, UK
Tel: +44 (0)23 8061 0311
Fax: +44 (0)23 8061 0852
[email protected]
EmersonNetworkPower.eu
Emergency Lighting EN 50171:2001
Safety EN 62040-1
EMC Emissions EN 61000-6-3
EMC Immunity EN 61000-6-2
Emerson. Consider it Solved., Emerson Network Power and the
Emerson Network Power logo are trademarks and service marks of
Emerson Electric Co. or one of its affiliated companies.