Liebert® SiteScan® IGM Reference Document

Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Liebert® SiteScan® IGM Reference Document Including Modbus and BACnet object Listings
Reference document is based on the assumption that the
connecting module is of exec. 6 or exec. B firmware type unless
otherwise noted.
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Revision Level Updates:
Revision
Date
B.5
B.6
B.7
B.8
B.9
B.10
B.11
B.12
11/8/00
2/19/01
4/4/02
5/3/02
10/1/02
1/22/03
7/23/03
4/19/04
B.13
B.14
B.16
5/24/04
8/19/200
4
11/22/20
04
5/18/05
B.17
7/1/05
B.18
7/21/05
B.19
B.20
11/30/05
12/14/05
B.21
8/9/06
B.22
8/10/06
B.23
3/16/07
B.24
B.25
B.26
B.27
4/16/07
4/30/07
5/2/07
11/15/07
B.28
B.29
B.30
6/24/08
7/11/08
5/13/09
B.31
10/13/09
B.15
Description
Added: revision level update chart, HiPulse support, and NPower support
Revised NPower definition
Added support for HiMod LNA
Revised Modbus explanation (Hi Byte / Lo Byte)
Corrected NPower table (typing error)
Added support for DataMate
Added support for STS-2
Corrected ModBus register addressing for STS-2 alarms. PM2 – removed duplicate
Output Voltage THD Alarm. Added XDP Unit. Added LDS5000 Unit. Added Universal
Monitor. Added BACNet/IP for: WDU, MM4, SC4, PM2 & LAM. Added Run Hours for
MM2
Removed non-existent alarms for MM2. Added BacNet/IP Point addresses for MM2.
Track issue 3576 – Make BacNet points consistent with Modbus Points.
Added ESP-2 based UPS Units that use OC485 card. Includes Nx, HiNet, PSI, and
GXT
Added “High Water Humidifier Pan” alarm to L00. Corrected alarm points for BACNet
and Modbus addressing on STS-2.
Added Remote shutdown alarm to LAM. Added Note about Alarms “BACNet auto
discovery” to CCM, L00, LAM, MMS, PM2, PMP, SCC. Added note to STS2 that it is
for units with or without PDU. Changed breaker status register for STS2 from bits1-8
to 0-7.
Added XDC Unit. Added control point note for units with on/off control as follows: Bit
0 on=unit off Bit 1 on=unit on. Removed cables 3 & 4 on LDS5000 and marked these
registers as spares.
Corrected revision level and date in header on this document.
SMS – Added Scale factor for kVA & kW. Revised note on page 1 to state module
type rather than “SS2000 Hardware”.
Series 610 UPS – added note that Series 610 is the same as series 600. SC4-SM4
changed “Bypass Breaker Closed” alarm from “Bypass Breaker Open”. Added note to
LAM that iCOM w/native IGM also applies.
Nfinity UPS (pnf), Nx (pnx), STS-2 (st2) – deleted status and setpoint points that are
not displayed in SiteScan. XDC, XDP added scale factor notes for Ref, Fluid and CW
temps.
PMP – Local Alarm #1 was Load Alarm, Added Local Alarm #2, Corrected Modbus
addressing from 40290:04 to 40290:07
AC8 – Added Unit tables to reference library
MM2 – Corrected entire table due to MS Word problems.
Corrected major MS Word formatting problems throughout document.
Added iCOM DS unit for 2mb modules (small version), SM3 corrected reversed
Modbus addressing for kW & kVA. Noted that pages for Series 600 UPS also apply
to series 610.
Added iCOM-XDP unit
Corrected alarm info for Npower (IMP) unit.
Corrected revision number in page header B.30 from B.9. Changed XDP unit
description on page 53 from XD. Corrected miscellaneous document formatting
errors. Added WDU definition back in document from accifental deletion.
Added local Alarms 2,3 &4 for MM2, L00 & LSM. Local alrm 3=High Water for MM2
Page 2 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Table of Contents
Click on the desired page number for instant navigation. Use the “back” arrow on your toolbar to return to the table
of contents.
REVISION LEVEL UPDATES:........................................................................................................................................ 2 TABLE OF CONTENTS ................................................................................................................................................. 3 OPEN COMMUNICATIONS .............................................. 7 DEFAULT MAPPING FOR MODBUS & BACNET OBJECTS ............................................................................................ 7 MODBUS COMMUNICATIONS ...................................................................................................................................... 8 Connectivity to SiteLink modules using Modbus ................................................................................................... 8 Implementation Basics ........................................................................................................................................... 9 Transmission Format ............................................................................................................................................. 9 Modbus Packet Format........................................................................................................................................ 10 RTU Framing ....................................................................................................................................................... 11 BACNET COMMUNICATIONS .................................................................................................................................... 12 BACnet Protocol Implementation Conformance Statement Rev. 2.1 .............................................................. 12 LIEBERT ENVIRONMENTAL UNITS ............................. 15 AIR UNIT - LEVEL 0 – L00 ........................................................................................................................................ 16 AIR UNIT – LEVEL 10 – L10 ..................................................................................................................................... 18 AIR UNIT – STANDARD MICROPROCESSOR – LSM ................................................................................................... 20 AIR UNIT – ADVANCED MICROPROCESSOR – LAM.................................................................................................. 22 AIR UNIT – SMALL SYSTEMS – L0B ......................................................................................................................... 25 AIR UNIT – MINI-MATE 2 – MM2, DATAMATE ....................................................................................................... 27 AIR UNIT – 8 TON MINIMATE – L8T ........................................................................................................................ 29 ATLAS AIR UNIT – C10 ............................................................................................................................................ 32 CHILLER UNIT – CSU3000 – CSU............................................................................................................................ 35 CHILLER UNIT – CSU 3000 W/ECONO – CSE ........................................................................................................... 37 AIR UNIT - HIROSS MICROFACE ............................................................................................................................... 39 AIR UNIT – X-TREME DENSITY COOLANT DISTRIBUTION UNIT– CDU .................................................................... 42 AIR UNIT – X-TREME DENSITY COOLANT PUMPING UNIT– XDP ............................................................................ 44 AIR UNIT – X-TREME DENSITY CHILLER UNIT– XDC ............................................................................................. 46 AIR UNIT – ICOM DS & RETROFIT (2MB VERSION SITELINK) ................................................................................. 49 AIR UNIT – XDP REFRIGERANT PUMPING UNIT – XDP W/ ICOM CONTROL .......................................................... 52 LIEBERT POWER UNITS ............................................... 54 POWER UNIT – VOLTAGE- CURRENT MONITORING PANEL – VCM .......................................................................... 55 POWER UNIT – POWER MONITORING PANEL – PMP ................................................................................................ 57 POWER UNIT – VOLTAGE-CURRENT-FREQ. MONITOR PANEL – VCF ....................................................................... 60 POWER UNIT – POWER MONITORING PANEL (EXT. PROTOCOL– PM2) .................................................................... 62 POWER UNIT – STATIC TRANSFER SWITCH PDU – EDS........................................................................................... 65 POWER UNIT – STATIC TRANSFER SWITCH PDU DUAL OUTPUT – STS ................................................................... 68 POWER UNIT – STATIC TRANSFER SWITCH PDU DUAL OUTPUT – STS-2 ................................................................ 71 LIEBERT UPS UNITS ..................................................... 74 UPS UNIT – MULTI MODULE UPS – S600/610 EXTENDED PROT. – MM4 ............................................................... 76 UPS UNIT – MULTI MODULE SERIES – MMS ........................................................................................................... 79 UPS UNIT – SYSTEM CONTROL CABINET – S/610 EXT. PROT. – SC4 ....................................................................... 81 UPS UNIT – SYSTEM CONTROL CABINET – SCC ...................................................................................................... 84 UPS UNIT – SINGLE MODULE SERIES – SMS ........................................................................................................... 86 Page 3 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS UNIT – SINGLE MODULE UPS – S/610 EXT. PROT. – SM4 ............................................................................... 88 UPS UNIT – MULTI-MODULE SICE 7200 & HIPULSE UPS – SMM ......................................................................... 92 UPS UNIT – SYSTEMS CABINET SICE 7200 UPS – SSC........................................................................................... 97 UPS UNIT – SINGLE MODULE SICE 7200 & HIPULSE UPS – SSM ........................................................................ 100 UPS UNIT – UPSTATION S – DCU ......................................................................................................................... 105 UPS UNIT – UPSTATION S3 – US3 ........................................................................................................................ 108 UPS UNIT – SINGLE MODULE SERIES AP301/302 – SM3 ...................................................................................... 111 UPS UNIT – SINGLE MODULE UPS – NPOWER—IMP ........................................................................................... 114 UPS UNIT – SINGLE MODULE UPS – NX—PNX ................................................................................................... 117 UPS UNIT – HINET – PHN ..................................................................................................................................... 120 UPS UNIT – NFINITY – PNF................................................................................................................................... 122 UPS UNIT – GXT – PGX ....................................................................................................................................... 125 UPS UNIT – PSI – PPS ........................................................................................................................................... 129 LIEBERT MONITORING MODULES ............................ 132 CONTACT CLOSURE MODULE – CCM .................................................................................................................... 133 WATER/LIQUID DETECTION UNIT – WDU ............................................................................................................. 136 REMOTE AUTOCHANGEOVER – RAC...................................................................................................................... 137 TEMPERATURE/HUMIDITY MODULE – THM .......................................................................................................... 138 WATER/LIQUID DETECTION UNIT LDS5000 – WD5 .............................................................................................. 141 UNIVERSAL MONITOR – UVM ............................................................................................................................... 142 AUTOCHANGEOVER CONTROLLER – AC8 .............................................................................................................. 145 Page 4 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
How to use the Reference Library Charts
This document contains a dedicated sheet for each Liebert Unit and associated controller. The title of each chart
contains the name of the Liebert Controller used such as L00 for a Level-0 Air unit or PMP for a Power Monitoring
Panel for Power Center.
The first section, Compatible Hardware, indicates the equipment associated with this particular controller as follows:
Liebert Units
Indicates the Environmental, Power, UPS or Monitoring Module by model name that
uses this controller.
SiteScan Interface
Indicates which SiteScan Hardware Modules can be used with the controller. Take
Modules
Special note of this box when adding new units to an existing SiteScan system, as
some new controllers are only compatible with the new hardware (SiteLink).
BMS interface Modules
Indicates which SiteScan Hardware Modules can be used with the controller for
interfacing with a third part using BACnet or Modbus protocol.
The next section, Available Points, contains six categories providing the following information:
Status Information for the listed points that will be presented in SiteScan
Status Points (View)
Alarms that are available to SiteScan
Alarm Points
Current settings of controllable Setpoints available to SiteScan
Setpoints (View)
Setpoints that can be changed with SiteScan
Control Points (Set)
Points that can be graphically trended within the SiteScan software
Trendable Points (Set)
Reports that can be triggered within the SiteScan software
Reports
Page 5 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
3-Letter
ID
L00
Liebert Unit ID Chart
Environmental Products
3-Letter
ID
Level 00, Level 1
SMS
L10
Level 2, Level 3, and Level 10
SM3
LAM
Level 15 and Level AM/AG,
HiMod (LNA), iCOM control w/ native
IGM
Level SM and Level 0 w/ On/Off
Control
Small Systems Controller
SM4
LSM
L0B
MM2
UPStation S3 UPS
MMS
SSC
Multi Module Series 500-600 UPS
(Prior to 1/98)
Multi Module Series 600/610 UPS Extended Protocol (1/98 or later)
System Control Cabinet Series 500600 (Prior to 1/98)
System Control Cabinet Series
600/610- Extended Protocol (1/98 or
later)
Single Module Series UPS - SICE
7200 & HiPulse
Multi Module Series UPS - SICE 7200
& HiPulse
System Control Cabinet - SICE 7200
IMP
PNX
NPower (S300 Replacement)
NX UPS – ESP2 Protocol
PHN
HiNet UPS – ESP2 Protocol
PNF
PGX
Nfinity UPS – ESP2 Protocol
GXT UPS – ESP2 Protocol
PPS
PSI UPS – ESP2 Protocol
MM4
CSE
CSU
Chiller
SSM
XDP
SMM
THM
WDU
Xtreme Density Unit Environmental
Control
Xtreme Density Coolant Distribution
Unit
DS Unit with iCOM control or Deluxe
System 3 with iCOM control retrofit.
Static Switch PDU
Static Switch PDU (Single Output
Breaker, Prior to 1/99)
Static Switch PDU (Dual Output
Breaker Option, 1/99 or later)
Miscellaneous
All IGM Contact Modules CM200 /
RCM8 / VSM
Remote Autochangeover Module RAC2-8
Temperature / Humidity Module
Liquid Detection LDS750 or LDS1000
WD5
Liquid Detection LDS5000
VCF
UVM
Universal Monitor
VCM
AC8
Autochangeover Controller
PM2
CDU
iCOM
EDS
STS
CCM
RAC
Page 6 of 146
Single Module Series UPS - S300,
S500, S600 (Prior to 1/98)
Single Module Series 30x (latest
version)
Single Module Series 600/610 Extended Protocol (1/98 or later)
US3
Small Systems Controller - Mini Mate
II, DataMate
Atlas Air Environmental Control
(LECS15)
Chiller w/ Econocoil
C10
UPS Products
SCC
SC4
PMP
Power Products PDU
Precision Power & Datawave w/ PMP
(latest LCD display)
All Voltage-Current-Frequency Panels
(Old Red LED Display)
All Voltage-Current Monitoring Panels
(Old Red LED Display)
Precision Power & Datawave w/ PMP
(latest LCD display and extended
protocol EPROM version 3.290.0,
manufactured and shipped after 4/99)
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Open Communications
Default Mapping for Modbus & BACnet Objects
This model represents the standard configuration for a Liebert Sitelink-12 module. Consecutive register /
object mapping is utilized, regardless of the SiteLink-12 population. All ports that do not have a Liebert
IGM attached will be assigned “null values” (or zero’s) for their corresponding registers. The default
“slave ID” or “Device ID” follows the CMNet address of the unit. The address can be visually checked by
looking at the address dip-switch or rotary switch settings. However, the address can be changed in
software to suit specific needs.
How to use this table:
The unit or model specific reference sheets assume that the desired unit is attached to port 1 of the
SiteLink module. If the desired unit is attached to a different port, the table below indicates the starting
register or object number for the unit.
For example: The register for “temperature” for a L00 type unit attached to port 1 is identified as
40001. If an additional L00 type unit were attached to port 2, the “temperature” value would be located in
register 40025. The same type unit attached to port 3 = 40049…etc.
Modbus Notes:
•
Modbus Registers start at 40001.
•
All registers are unsigned integers.
BACnet Notes:
•
BACnet Objects start at 1.
•
All “Status” and “Alarm” objects are “AI’s” (analog inputs).
•
The “Control” objects are “AO’s” (analog outputs)
Page 7 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Register Offset
1-24
25-48
49-72
73-96
97-120
121-144
145-168
169-192
193-216
217-240
241-264
265-288
Object Type
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Port Assignment
1
2
3
4
5
6
7
8
9
10
11
12
289-293
294-298
299-303
304-308
309-313
314-318
319-323
324-328
329-333
334-338
339-343
344-348
Alarms
Alarms
Alarms
Alarms
Alarms
Alarms
Alarms
Alarms
Alarms
Alarms
Alarms
Alarms
1
2
3
4
5
6
7
8
9
10
11
12
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
1
2
3
4
5
6
7
8
9
10
11
12
349-351
352-354
355-357
358-360
361-363
364-366
367-369
370-372
373-375
376-378
379-381
382-384
** See reference libraries for unit specific objects.
Modbus Communications
Connectivity to SiteLink modules using Modbus
This design specification describes the Modbus communications protocol as supported by the SiteLink module. It
includes information on how to pass information to and from the SiteLink module via Modbus. It is also intended to
help facilitate answering questions regarding supported types, frame format, function code support etc.
Page 8 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Implementation Basics
Protocol controls the language structure or message format between devices in other words, the rules for
communication. The rules for communication include how master and slave devices initiate communications, as
well as unit identification, message handling and error checking. Modbus protocol simply refers to the control of
the query and response cycles between master and slave devices.
The SiteLink module is configured to act as a slave device on a common network. The common network can be
point-to-point over EIA-232, where one master communicates to one slave device or in a multi-drop configuration
over EIA-485, where multiple slaves reside on a common wire or loop.
Transmission Format
The SiteLink module supports both Modbus RTU (Remote Terminal Unit) and ASCII (American Standard Code for
Information Interchange) transmission modes. The SiteLink module has a choice of transmission medium, baud
rate, character parity and number of stop bits. See chart below.
Physical
Port
EIA-232 –
DB9 DCE
EIA-232 –
DB9 DCE
Transmission
Mode
RTU
Baud Rate
Data Bits
Parity Bits
Stop Bits
Default
9600
8
None
1
Yes
ASCII
Configurable
Configurable
Configurable
No
EIA-485 – 2
or 4 wire
RTU or ASCII
1200 –
38.4kbd
(19.2kbd omit)
1200 –
38.4kbd
(19.2kbd omit)
Configurable
Configurable
Configurable
No
Page 9 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Modbus Packet Format
Each Modbus packet consists of the following fields:
•
•
•
•
Device Address
Function Code
Data Field(s)
Error Check Field
Device Address:
The address field immediately follows the beginning of the frame and consists of 8-bits (RTU) or 2 characters
(ASCII). These bits indicate the user assigned address of the slave device that is to receive the message sent by the
attached master device.
Each slave must be assigned a unique address and only the addressed slave will respond to a query that contains its
address.
Function Code:
The function code field tells the addressed slaves what function to perform. Function codes are specifically
designed invoke a specific action by the slave device. The function code range is from 1 to 127. However, the
SiteLink module primarily uses Function Code 3 (Read Holding Registers), Function Code 6 (Preset Single
Register) and Function Code 16 (Preset Multiple Registers).
Data Field(s):
The data field varies in length depending on whether the message is a request or a response to a packet.
This field typically contains information required by the slave device to perform the command specified or
to pass back data to the master device.
Error Check Field:
The Error Check Field consists of a 16-bit (2 byte) Cyclical Redundancy Check (CRC16). It allows the
receiving device to detect a packet that has been corrupted with transmission errors.
Page 10 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
RTU Framing
The example below shows a typical Q/R from a SiteLink module. In common terms, the master device initiates a
query asking slave device 2 for holding registers starting at holding register 40051 (decimal 50) and including
next 2 Registers (3 total).
Query Sample
Slave
Address
Function
Code
02
03
Starting
Register
“Hi Byte”
Starting
Register
“Lo Byte”
Number of
Registers
“Hi Byte”
Number of
Registers
“Lo Byte”
CRC16
CRC16
“Hi Byte”
“Lo Byte”
00
32
00
03
E5
FA
Count:
Bytes of
Data
Register
40051 Data
Hi
Lo
Register
40052 Data
Hi
Lo
Register
40053 Data
Hi
Lo
CRC16
CRC16
“Hi Byte
“Lo Byte”
1B
0D
Response Sample
Slave
Address
Function
Code
02
03
6
01
58
00
FA
00
54
Slave address 2 responds to Function Code 3 with 6 bytes of hexadecimal data and ends with CRC16 checksum.
Register values: 40051 = 158(hex) = 344(decimal)
40052 = FA (hex) = 250 (decimal)
40053 = 54 (hex) = 84 (decimal)
ASCII Framing:
Framing in ASCII transmission mode is accomplished by the use of the unique colon (:) to indicate the beginning of the
frame and a carriage return (CR) line feed (LF) to delineate the end of the frame. The line feed also serves as a
synchronizing character which indicates that the transmitting station is ready to receive an immediate reply.
ASCII Example
Frame
Start
Slave
Address
Function
Code
Data
Error
Check
End of
Frame
CR
Ready for
Data
LF
:
2 Char
2 Char
N x 4 Char
B3
0D
0A
16-bits
16-bits
N x 16-bits
Char = Character: 1 Character = 7 data bits, 1 start bit, 1 or 2 stop bits and 1 parity bit (optional)
Page 11 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
BACnet Communications
BACnet Protocol Implementation Conformance Statement
Vendor Name:
Liebert Corporation
Product Name:
SiteLink Module
Rev. 2.1
Product Model Number: SiteLink-DC12i, SiteLink-DC4i, SiteLink-12, and SiteLink-4
Product Description:
The SiteLink module provides a BACnet Point-to-Point communication exchange between proprietary Liebert
Environmental, Power, UPS units to other BACnet compliant devices. The connection to the SiteLink module is via
EIA-232, 9600 baud, no parity, 8 data bits, 1 stop bit (9600,N,8,1 default.) The SiteLink modules are available in 12
port and 4 port configurations (i.e. 1 port per/ Liebert Unit, 12 Liebert units per/ SiteLink module maximum.)
Class 1
Class 2
Class 3
BACnet Conformance Class Supported:
Class 4
Class 5
x
Class 6
BACnet Functional Groups Supported:
Clock
HHWS
PCWS
Event Initialization
Event Response
COV Event Initiation
COV Event Response
Files
Reinitialize
Virtual Operator Interface
Virtual Terminal
Device Communications
Time Master
Page 12 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
BACnet Standard Application Services Supported:
Application Service
Initiate
Execute Requests
Requests
AcknowledgeAlarm
ConfirmedCOVNotification
ConfirmedEventNotification
GetAlarmSummary
GetEnrollmentSummary
SubscribeCOV
UnconfirmedCOVNotification
UnconfirmedEventNotification
AtomicReadFile
AtomicWriteFile
AddListElement
RemoveListElement
CreateObject
DeleteObject
ReadProperty
ReadPropertyConditional
ReadPropertyMultiple
WriteProperty
WritePropertyMultiple
DeviceCommunicationControl
ConfirmedPrivateTransfer
UnconfirmedPrivateTransfer
ReinitializeDevice
ConfirmedTextMessage
TimeSynchronization
Who-Has
I-Have
Who-Is
I-Am
VT-Open
VT-Closed
VT-Data
Authenticate
Request Key
Page 13 of 146
X
X
X
X
X
X
X
X
X
X
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
BACnet Standard Application Services Supported (continued):
Supported
Dynamically
Dynamically
Optional
Creatable
Deleteable
Properties
X
Analog Input
X
Analog Output
Analog Value
Binary Input
Binary Output
Binary Value
Calendar
Command
Device
Event Enrollment
File
Group
Loop
Multi-State Input
Multi-State Output
Notification Class
Program
Schedule
Object Type
Data Link Layer:
Point-to-Point, EIA-232, baud rates: 9600 & 38,400
Character Set Supported:
ANSI X3.4
Special Functionality:
Segmented Requests Supported
Segmented Responses Supported
Router
Page 14 of 146
No
No
No
Writable
Properties
None
Present Value
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Liebert Environmental Units
Page 15 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit - Level 0 – L00
Hardware Compatibility
Liebert Units: Challenger 3, Logicool, Modular Plus, LS400, Mini-Tower, System 4
SiteScan Interface Modules: DC-1; DC4; DC12; SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Temperature
Humidity
Cooling
Heating
Humidification
Dehumidification
Econ-o-Cycle
Stages
% Capacity
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
1
2
3
4
5
6
7
8
9
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
Discrete BACnet alarm objects available –
use auto-discover for this unit
Alarm Points
Communications
High Head Pressure 1
High Head Pressure 2
Loss of Airflow
Liquid Detected
Change Filters
High Temperature
Low Temperature
High Humidity
Low Humidity
Local Alarm 1
High Water Humidifier Pan
Local Alarm 2
Local Alarm 3
Local Alarm 4
Notes:
40289:0
40289:1
40289:2
40289:3
40289:4
40289:5
40289:6
40289:7
40289:8
40289:9
40289:10
40289:11
40289:12
40289:13
40289:14
289:0
289:1
289:2
289:3
289:4
289:5
289:6
289:7
289:8
289:9
289:10
289:11
289:12
289:13
289:14
Page 16 of 146
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA01_x:11
BA01_x:12
BA01_x:13
BA01_x:14
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Setpoints (View)
Temperature Setpoint
Temperature Tolerance
Humidity Setpoint
Humidity Tolerance
40010
40011
40012
40013
10
11
12
13
BS10_x
BS11_x
BS12_x
BS13_x
Control Points (Set)
Temperature Setpoint
Temperature Tolerance
Humidity Setpoint
Humidity Tolerance
40350
40350
40351
40351
350
350
351
351
BC02_x
BC02_x
BC03_x
BC03_x
Trendable points (Set)
Temperature
Humidity
Reports
Trend
Status
Page 17 of 146
Notes:
Multiply desired value by 1000
Multiply desired value by 1000
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit – Level 10 – L10
Hardware Compatibility
Liebert Units: Modular Plus, Deluxe System/3, Industrial Cooling Series
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Temperature
Humidity
Cooling
Heating
Humidification
Dehumidification
Econ-o-Cycle
Stages
% Capacity
Alarm Points
Communications
High Head Pressure 1
High Head Pressure 2
Loss of Airflow
Standby Glycol Unit On
Liquid Detected
Change Filters
High Temperature
Low Temperature
High Humidity
Low Humidity
Humidifier Problem
No Water in Humidifier Pan
Compressor 1 Overload
Compressor 2 Overload
Main Fan Overload
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
1
2
3
4
5
6
7
8
9
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
40289:0
40289:1
40289:2
40289:3
40289:4
40289:5
40289:6
40289:7
40289:8
40289:9
40289:10
40290:0
40290:1
40290:2
40290:3
40290:4
289:0
289:1
289:2
289:3
289:4
289:5
289:6
289:7
289:8
289:9
289:10
290:0
290:1
290:2
290:3
290:4
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
Page 18 of 146
Notes:
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Manual Override
Smoke Detected
Loss of Water
Standby Unit On
Low Suction
Short Cycle
Loss of Power
Inverter Bypass
Standby Fan On
Loss of Emergency Power
Local Alarm 1
Local Alarm 2
Setpoints (View)
Temperature Setpoint
Temperature Tolerance
Humidity Setpoint
Humidity Tolerance
High Temperature Setpoint
Low Temperature Setpoint
High Humidity Setpoint
Low Humidity Setpoint
Auto-Restart Delay
Control Points (Set)
Temperature Setpoint
Temperature Tolerance
Humidity Setpoint
Humidity Tolerance
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40290:5
40290:6
40290:7
40290:8
40290:9
40290:10
40291:0
40291:1
40291:2
40291:3
40291:4
40291:5
290:5
290:6
290:7
290:8
290:9
290:10
291:0
291:1
291:2
291:3
291:4
291:5
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA04_x:05
40010
40011
40012
40013
40014
40015
40016
40017
10
11
12
13
14
15
16
17
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
40350
40350
40351
40351
350
350
351
351
BC02_x
BC02_x
BC03_x
BC03_x
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Page 19 of 146
Notes:
Multiply desired value by 1000
Multiply desired value by 1000
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit – Standard Microprocessor – LSM
Hardware Compatibility
Liebert Units: Challenger 3000. Deluxe System / 3, ICS , System 4 (Replaces L0A control)
SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Status Points (View)
Temperature
Humidity
Cooling
Heating
Humidification
De-humidification
Econ-O-Cycle
Stages
% Capacity
Unit Status (On / Off)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40014
1
2
3
4
5
6
7
8
9
14
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS14_x
Alarm Points
Communications
Local Off
Remote Off
High Head Pressure 1
High Head Pressure 2
Loss of Airflow
Liquid Detected
Change Filters
High Temperature
Low Temperature
High Humidity
Low Humidity
Local Alarm 1
Local Alarm 2
Local Alarm 3
Local Alarm 4
40289:0
40289:1
40289:2
40289:3
40289:4
40289:5
40289:6
40289:7
40289:8
40289:9
40289:10
40290:0
40290:1
40290:2
40290:3
40290:4
289:0
289:1
289:2
289:3
289:4
289:5
289:6
289:7
289:8
289:9
289:10
290:0
290:1
290:2
290:3
290:4
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
Page 20 of 146
Notes:
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Setpoints (View)
Temperature Setpoint
Temperature Tolerance
Humidity Setpoint
Humidity Tolerance
40010
40011
40012
40013
10
11
12
13
BS10_x
BS11_x
BS12_x
BS13_x
Control Points (Set)
Unit On / Off
Temperature Setpoint
Temperature Tolerance
Humidity Setpoint
Humidity Tolerance
40349
40350
40350
40351
40351
349
350
350
351
351
BC01_x
BC02_x
BC02_x
BC03_x
BC03_x
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Page 21 of 146
Notes:
Bit 0 on=unit off Bit 1 on=unit on
Multiply desired value by 1000
Multiply desired value by 1000
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit – Advanced Microprocessor – LAM
Hardware Compatibility
Liebert Units: Challenger 3000. Deluxe System / 3, ICS, System 4 (Replaces L15 & L1A)
HiMod (LNA version) – iCOM control (Native IGM port)
SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Temperature
Humidity
Cooling
Heating
Humidification
De-humidification
Econ-O-Cycle
Stages
% Capacity
Unit Status (On / Off)
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40018
1
2
3
4
5
6
7
8
9
18
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS18_x
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
Discrete BACnet alarm objects available –
use auto-discover for this unit
Alarm Points
Communications
Local Off
Remote Off
High Head Pressure 1
High Head Pressure 2
Loss of Airflow
Standby Glycol Unit On
Liquid Detected
Change Filters
High Temperature
Low Temperature
High Humidity
Low Humidity
Humidifier Problem
No Water in Humidifier Pan
Notes:
40289:0
40289:1
40289:2
40289:3
40289:4
40289:5
40289:6
40289:7
40289:8
40289:9
40289:10
40290:0
40290:1
40290:2
40290:3
289:0
289:1
289:2
289:3
289:4
289:5
289:6
289:7
289:8
289:9
289:10
290:0
290:1
290:2
290:3
Page 22 of 146
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Compressor 1 Overload
Compressor 2 Overload
Main Fan Overload
Manual Override
Smoke Detected
Loss of Water
Standby Unit On
Low Suction
Short Cycle
Loss of Power
Inverter on Bypass
Standby Fan On
Loss of Emergency Power
Local Alarm 1
Local Alarm 2
Off by Remote Shutdown
Runtimes (View)
Compressor 1 Run Hours
Compressor 2 Run Hours
Glycol Run Hours
Fan Motor Run Hours
Humidifier Run Hours
Reheat 1 Run Hours
Reheat 2 Run Hours
Reheat 3 Run Hours
Chilled Water Valve Run
Hours
Setpoints (View)
Temperature Setpoint
Temperature Tolerance
Humidity Setpoint
Humidity Tolerance
High Temp Alarm Setpoint
Low Temp Alarm Setpoint
High Humd Alarm Setpoint
Low Humidity Alarm Setpoint
Modbus
Register
40290:4
40290:5
40290:6
40290:7
40290:8
40290:9
40290:10
40291:0
40291:1
40291:2
40291:3
40291:4
40291:5
40291:6
40291:7
40291:8
BACnet
Instance
(Exec. 6
Modules)
290:4
290:5
290:6
290:7
290:8
290:9
290:10
291:0
291:1
291:2
291:3
291:4
291:5
291:6
291:7
291:9
BACnet
Instance
(Exec. B
Modules)
BA02:04_x
BA02:05_x
BA02:06_x
BA02:07_x
BA02:08_x
BA02:09_x
BA02:10_x
BA03:00_x
BA03:01_x
BA03:02_x
BA03:03_x
BA03:04_x
BA03:05_x
BA03:06_x
BA03:07_x
BA03:08_x
40019
40020
19
20
BS19_x
BS20_x
40021
40022
21
22
BS21_x
BS22_x
40010
40011
40012
40013
40014
40015
40016
40017
10
11
12
13
14
15
16
17
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
Notes:
Runtimes not available on iCOM control
Page 23 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Control Points (Set)
Unit On / Off
Temperature Setpoint
Temperature Tolerance
Humidity Setpoint
Humidity Tolerance
Reheat Lockout
Humidifier Lockout
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40349
40350
40350
40351
40351
40349
40349
349
350
350
351
351
349
349
BC01_x
BC02_x
BC02_x
BC03_x
BC03_x
BC01_x
BC01_x
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Page 24 of 146
Notes:
Bit 0 on=unit off Bit 1 on=unit on
Multiply desired value by 1000
Multiply desired value by 1000
Bit 2 on=RH off Bit 3 on=RH on
Bit 4 on=HL off Bit 5 on=HL on
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit – Small Systems – L0B
Hardware Compatibility
Liebert Units: DataMate, Mini-Mate, Mini-Mate Plus
SiteScan Interface Modules: DC-1; DC4; DC12; SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Temperature
Humidity
Cooling
Heating
Humidification
Dehumidification
Econ-o-Cycle
Stages
% Capacity
Unit On/Off
Alarm Points
Communications
Local Off
Remote Off
High Temperature
Low Temperature
High Humidity
Low Humidity
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40011
1
2
3
4
5
6
7
8
9
11
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS11_x
40289:0
40289:1
40289:2
40289:3
40289:4
40289:5
40289:6
289:0
289:1
289:2
289:3
289:4
289:5
289:6
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
40349
349
BC01_x
Notes:
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
Setpoints (View)
None
Control Points (Set)
Remote On/Off
Page 25 of 146
Bit 0 on=unit off Bit 1 on=unit on
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Page 26 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit – Mini-Mate 2 – MM2, DataMate
Hardware Compatibility
Liebert Units: Mini-Mate 2, DataMate
SiteScan Interface Modules: SiteLink
BMS interface Modules: SiteLink (All)
Available
Points
SiteScan Availability
Status Points (View)
Temperature
Humidity
Cooling
Heating
Humidification
Dehumidification
Econ-o-Cycle
Stages
% Capacity
Unit On/Off
Alarm Points
Communications
Local Off
Remote Off
High Head Pressure 1
Loss of Airflow
Standby Glycol Unit On
Change Filters
High Temperature
Low Temperature
High Humidity
Low Humidity
Humidifier Problem
Smoke Detected
Loss of Water Flow
Standby Unit On
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40018
1
2
3
4
5
6
7
8
9
18
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS18_x
40289:0
40289:1
40289:2
40289:3
40289:5
40289:6
40289:7
40289:8
40289:9
40290:0
40290:1
40290:2
40290:8
40290:9
40290:10
289:0
289:1
289:2
289:3
289:5
2896
289:7
289:8
289:9
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:08
BA02_x:09
BA02_x:10
290:0
290:1
290:2
290:8
290:9
290:10
Page 27 of 146
Notes:
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Short Cycle
Loss of Power
Local Alarm 1
Local Alarm 2
High Water
Local Alarm 4
Run Hours (View)
Compressor 1
Fan Motor
Humidifier
Reheat 1
Reheat 2
Reheat 3
Chilled Water Valve
Setpoints (View)
Temperature
Temp Tolerance
Humidity
Humidity Tolerance
High Temperature Alarm
Low Temperature Alarm
High Humidity Alarm
Low Humidity Alarm
Control Points (Set)
Remote On/Off
Temperature Setpoint
Temperature Tolerance
Humidity Setpoint
Humidity Tolerance
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40291:1
40291:2
40291:6
40291:7
40291:8
40291:9
291:1
291:2
291:6
291:7
291:8
291:9
BA03:01
BA03:02
BA03:06
BA03:07
BA03:08
BA03:09
40019
40020
40021
19
20
21
BS19_x
BS20_x
BS21_x
40010
40011
40012
40013
40014
40015
40016
40017
10
11
12
13
14
15
16
17
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
40349
40350
40350
349
350
350
BC01_x
BC02_x
BC02_x
40351
40351
351
351
BC03_x
BC03_x
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Page 28 of 146
Notes:
Bit 0 on=unit off Bit 1 on=unit on
Multiply desired value by 1000 (ModBus &
BACNet 2.6 only) 0=No Change
Multiply desired value by 1000 (ModBus &
BACNet 2.6 only) 0=No Change
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit – 8 Ton MiniMate – L8T
Hardware Compatibility
Liebert Units: MiniMate - 8 Ton only
SiteScan Interface Modules: DC-1; DC4-422; SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Temperature
Humidity
Cooling
Heating
Humidification
De-humidification
Econ-O-Cycle
Stages
% Capacity
Unit Status (On / Off)
Alarm Points
Communications
Local Off
Remote Off
High Head Pressure 1
High Head Pressure 2
Loss of Airflow
Standby Glycol Unit On
Not Used
Change Filters
High Temperature
Low Temperature
High Humidity
Low Humidity
Humidifier Problem
Not Used
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40018
1
2
3
4
5
6
7
8
9
18
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS18_x
40289:0
40289:1
40289:2
40289:3
40289:4
40289:5
40289:6
40289:7
40289:8
40289:9
40289:10
40290:0
40290:1
40290:2
40290:3
289:0
289:1
289:2
289:3
289:4
289:5
289:6
289:7
289:8
289:9
289:10
290:0
290:1
290:2
290:3
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x00
BA02_x01
BA02_x02
BA02_x03
Page 29 of 146
Notes:
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
1=on / 0=off
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Not Used
Not Used
Not Used
Not Used
Smoke Detected
Loss of Water
Standby Unit On
Not Used
Short Cycle
Loss of Power
Not Used
Not Used
Not Used
Local Alarm 1
Local Alarm 2
Run Times (View)
Compressor 1 Run Hours
Compressor 2 Run Hours
Glycol Run Hours
Fan Motor Run Hours
Humidifier Run Hours
Reheat 1 Run Hours
Reheat 2 Run Hours
Reheat 3 Run Hours
Chilled H2O Valve Run Hours
Setpoints (View)
Temperature Setpoint
Temperature Tolerance
Humidity Setpoint
Humidity Tolerance
High Temperature Alarm
Setpoint
Low Temp Alarm Setpoint
High Humidity Alarm Setpoint
Low Humidity Alarm Setpoint
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40290:4
40290:5
40290:6
40290:7
40290:8
40290:9
40290:10
40291:0
40291:1
40291:2
40291:3
40291:4
40291:5
40291:6
40291:7
290:4
290:5
290:6
290:7
290:8
290:9
290:10
291:0
291:1
291:2
291:3
291:4
291:5
291:6
291:7
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
BA03_x:07
40019
40020
19
20
BS19_x
BS20_x
40021
40022
21
22
BS21_x
BS22_x
40010
40011
40012
40013
40014
10
11
12
13
14
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
40015
40016
40017
15
16
17
BS15_x
BS16_x
BS17_x
Page 30 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Control Points (Set)
Unit On / Off
Temperature Setpoint
Temperature Tolerance
Humidity Setpoint
Humidity Tolerance
Reheat Lockout
Humidifier Lockout
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40349
40350
40350
40351
40351
40349
40349
349
350
350
351
351
349
349
BC01_x
BC02_x
BC02_x
BC03_x
BC03_x
BC01_x
BC01_x
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Page 31 of 146
Notes:
Bit 0 on=unit off Bit 1 on=unit on
Multiply desired value by 1000
Multiply desired value by 1000
Bit 2 on=RH off Bit 3 on=RH on
Bit 4 on=HL off Bit 5 on=HL on
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Atlas Air Unit – C10
Hardware Compatibility
Liebert Units: Atlas Air; LECS 15
SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Unit Number
Average Return Air Temp.
Average Return Air Humidity
Average Supply Air Temp.
Average Supply Air Humidity
Activation Mode
Fan Status
Cool 1 Status
Cool 2 Status
Heat 1 Status
Heat 2 Status
Humidifier Status
De-humidifier Status
Cooling Capacity
Heating Capacity
Active Operation (Days)
Active Operation (Hours)
Cool Mode (Days)
Cool Mode (Hours)
Heat Mode (Days)
Heat Mode (Hours)
Humidifier Mode (Days)
Humidifier Mode (Hours)
De-humidifier Mode (Days)
De-humidifier Mode (Hours)
Cool 1 Operating Mode
(Days)
Cool 1 Operating Mode
(Hours)
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
Page 32 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Cool 2 Operating Mode (Days)
Cool 2 Operating Mode (Hours)
Fan Operation (Days)
Fan Operation (Hours)
Heat 1Operating Mode (Days)
Heat 1Operating Mode (Hours)
Heat 2 Operating Mode (Days)
Heat 2 Operating Mode (Hours)
Humidify Operating Mode (Days)
Humidity Operating Mode (Hours)
Cool Service (Days)
Cool Service (Hours)
Filter Service (Days)
Filter Service (Hours)
Humidifier Service (Days)
Humidifier Service (Hours)
Temperature Control Status
Battery Voltage Level
Remote Shutdown Status
General Alarm Status
Audible Alarm Status
Temperature Control Select
Alarm Points
Communications
Faulty Sensor
High Temperature
Low Temperature
High Humidity
Low Humidity
Loss of Airflow
Water Under Floor
Cool 1 Low Pressure Alarm
Cool 2 Low Pressure Alarm
Cool 1 High Pressure Alarm
Cool 2 High Pressure Alarm
Cool Service
Humidifier Service
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40019
40020
40021
40022
40023
40024
19
20
21
22
23
24
BS19_x
BS20_x
BS21_x
BS22_x
BS23_x
BS24_x
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
Page 33 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Filter Service
Humidity Low Level
Battery Level Low
Loss of Power
Spare 1
Spare 2
Setpoints (View)
Unit Status (On / Off)
Return Air Temperature
Return Air Humidity
Supply Air Temperature
High Temperature Alarm
Low Temperature Alarm
High Humidity Alarm
Low Humidity Alarm
Start up Delay
Control Points (Set)
Unit Status (On / Off)
Return Air Temperature
Return Air Humidity
Supply Air Temperature
High Temperature Alarm
Low Temperature Alarm
High Humidity Alarm
Low Humidity Alarm
Start up Delay
Trendable Points (Set)
Average Return Air Temp.
Average Return Air Humidity
Average Supply Air Temp.
Average Supply Air Humidity
Reports
Trend
Status
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40290:3
40290:4
40290:5
40290:6
40290:7
40290:8
290:3
290:4
290:5
290:6
290:7
290:8
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
40016
40017
40018
16
17
18
BS16_x
BS17_x
BS18_x
40349
40350
40351
349
350
351
BC01_x
BC02_x
BC03_x
Page 34 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Chiller Unit – CSU3000 – CSU
Hardware Compatibility
Liebert Units: Chiller CSU-3000
SiteScan Interface Modules: DC-1; DC4-422; DC12-422; SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Number of Modules
Module 1 Start
Module 1 Pump
Module 1 Cool
Module 2 Start
Module 2 Pump
Module 2 Cool
Module 3 Start
Module 3 Pump
Module 3 Cool
Alarm Points
Communications
Mod 1 High Head Pressure
Mod 2 High Head Pressure
Mod 3 High Head Pressure
Module 1 No Water Flow
Module 2 No Water Flow
Module 3 No Water Flow
Module 1 High Water Temp.
Module 2 High Water Temp.
Module 3 High Water Temp.
Module 1 Low Water Temp.
Module 2 Low Water Temp.
Module 3 Low Water Temp.
Module 1 No Power
Module 2 No Power
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
1
2
3
4
5
6
7
8
9
10
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
40289:0
40289:1
40289:2
40289:3
40289:4
40289:5
40289:6
40289:7
40289:8
40289:9
40289:10
40290:0
40290:1
40290:2
40290:3
289:0
289:1
289:2
289:3
289:4
289:5
289:6
289:7
289:8
289:9
289:10
290:0
290:1
290:2
290:3
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
Page 35 of 146
Notes:
1=START / 0=STOP
1=ON / 0=OFF
1=ON / 0=OFF
1=ON / 0=OFF
1=ON / 0=OFF
1=START / 0=STOP
1=ON / 0=OFF
1=ON / 0=OFF
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Module 3 No Power
Module 1 Liquid Detected
Module 2 Liquid Detected
Module 3 Liquid Detected
Local Alarm 1
Local Alarm 2
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40290:4
40290:5
40290:6
40290:7
40290:8
40290:9
290:4
290:5
290:6
290:7
290:8
290:9
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
None
Reports
Status
Page 36 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Chiller Unit – CSU 3000 w/Econo – CSE
Hardware Compatibility
Liebert Units: Chiller CSU-3000
SiteScan Interface Modules: DC-1; DC4-422; SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
System Econ-o-Cycle
Number of Modules
Module 1 Start
Module 1 Pump
Module 1 Cool
Module 2 Start
Module 2 Pump
Module 2 Cool
Module 3 Start
Module 3 Pump
Module 3 Cool
Module 1 Econ-o-Cycle
Module 2 Econ-o-Cycle
Module 3 Econ-o-Cycle
Alarm Points
Communications
Mod 1 High Head Pressure
Mod 2 High Head Pressure
Mod 3 High Head Pressure
Module 1 No Water Flow
Module 2 No Water Flow
Module 3 No Water Flow
Module 1 High Water Temp.
Module 2 High Water Temp.
Module 3 High Water Temp.
Module 1 Low Water Temp.
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
1
2
3
4
5
6
7
8
9
10
11
12
13
14
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
Page 37 of 146
Notes:
1=ON / 0=OFF
1=START / 0=STOP
1=ON / 0=OFF
1=ON / 0=OFF
1=START / 0=STOP
1=ON / 0=OFF
1=ON / 0=OFF
1=START / 0=STOP
1=ON / 0=OFF
1=ON / 0=OFF
1=ON / 0=OFF
1=ON / 0=OFF
1=ON / 0=OFF
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Module 2 Low Water Temp.
Module 3 Low Water Temp.
Module 1 No Power
Module 2 No Power
Module 3 No Power
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40290:0
40290:1
40290:2
40290:3
40290:4
290:0
290:1
290:2
290:3
290:4
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
Setpoints (Set)
None
Control Points (Set)
None
Trendable Points (Set)
None
Reports
Status
Page 38 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit - Hiross Microface
Hardware Compatibility
Liebert Units: Liebert Hiross Microface
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: Liebert Hiross Hirolink
Available Points
SiteScan Availability
Modbus Register
Status Points (View)
Unit On Off
Heater Working Hours
Humidifier Working Hours
Compressor 1 Working Hours
Conditioner Working Hours
Low Humidity Warning
High Humidity Warning
Low Temperature Warning
High Temperature Warning
Humidity Proportional Band
Temperature Proportional Band
Room Humidity Setpoint
Room Temperature Setpoint 1
Compressor 2 Working Hours
Free-cooling Working Hours
Cooling Ramp
Status Dehumidification
Status Electrical Heater 2
Status Electrical Heater 1
Status Compressor 1
Humidifier Current
Room Humidity
Room Temperature
Status Compressor 2
Free-cooling Status
Page 39 of 146
BACnet Instance
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Smoke Alarm
No Power (User Input)
Power On (User Input)
User Input 2 Triggered
User Input 2 Triggered
No Connection To Unit 1
Compressor 1 Motor Protection
Compressor 2 Motor Protection
Fire Alarm
Out Of Memory
Condenser 1 Fan Failure
Condenser 2 Fan Failure
Network Ping
Subgroup-Id Not Unique
Subgroup-Unit 1 Not Connected
Subgroup-Unit 2 Not Connected
Share Rm. Sensor Failure Warn
Share Rm. Sensor Failure Alarm
Share Outdoor Temp Sensor
Share Glycol Temp Sensor
Unit Synch (Short Reset)
Humidifier High Temperature
Humidifier Overflow
Modbus Register
Setpoints (View)
Room Temperature Setpoint 1
Temperature Proportional Band
Room Humidity Setpoint
Humidity Proportional Band
High Temperature Alarm Setpoint
Low Temp Alarm Setpoint
High Humidity Alarm Setpoint
Low Humidity Alarm Setpoint
Page 40 of 146
BACnet Instance
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Control Points (Set)
Unit On/Off
Humidity Proportional Band
Temperature Proportional Band
Room Humidity Setpoint
Room Temperature Setpoint
Modbus Register
Trendable Points (Set)
Temperature
Humidity
Reports
Trend
Status
Page 41 of 146
BACnet Instance
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit – X-Treme Density Coolant Distribution Unit– CDU
Hardware Compatibility
Liebert Units: X-Treme Density Coolant Distribution Unit
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Valve % Open
Pump 1 Status
Pump 2 Status
Fluid Level
Fluid Temperature
Stop Valve
Purge Valve
FMS Disable
Rate Of Change
Local Temp
Local Humidity
Local Dewpoint
Remote Temp
Remote Humidity
Remote Dewpoint
Unit Status
Alarm Points
Communications
Local Off
Remote Off
Loss Of Flow P1
Loss Of Flow P2
Pump Short Cycle
Spare 5
Leak Detected
Valve Failure
Customer Alarm 1
Fan Fail
High Fluid Temp
Low Fluid Temp
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
289:0
289:1
289:2
289:3
289:4
289:5
289:6
289:7
289:8
289:9
289:10
290:0
290:1
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
Page 42 of 146
Notes:
1=On / 0=Off
1=On / 0=Off
1=On / 0=Off
43=C / 46=F
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Fluid Sensor Problem
High Remote Temp
Low Remote Temp
Remote Sensor Problem
High Local Temp
Low Local Temp
Local Sensor Problem
Low Pressure
High Fluid Level
Low Fluid Level
Low Low Level
Fluid Level ROC
System Purge P1
Emergency Purge
FMS Power Loss
Loss Of Power
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
40291:06
290:2
290:3
290:4
290:5
290:6
290:7
290:8
290:9
290:10
291:0
291:1
291:2
291:3
291:4
291:5
291:6
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
Setpoints (View)
Temperature Setpoint
High Fluid Temp Setpoint
Temp Scale
High Air Temp
Low Air Temp
Dewpoint Margin
Restart Delay
40017
40018
17
18
BS17_x
BS18_x
40019
40020
40021
40022
19
20
21
22
BS19_x
BS20_x
BS21_x
BS22_x
Control Points (Set)
Unit On / Off
Temperature Setpoint
Dewpoint Margin
40349
40350
40351
49
50
51
BC01_x
BC02_x
BC03_x
Trendable Points (Set)
Temperature
Humidity
Dewpoint
Reports
Trend
Status
Page 43 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit – X-Treme Density Coolant Pumping Unit– XDP
Hardware Compatibility
Liebert Units: X-Treme Density Coolant Pumping Unit
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Status Points (View)
Valve % Open
Pump 1 Status
Pump 2 Status
Fluid Temperature
Chilled Water Temperature
Unit Status
Scale F or C
Local Temperature
Local Humidity
Local Dewpoint
Remote Temperature
Remote Humidity
Remote Dewpoint
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
1
2
3
4
5
6
7
8
9
10
11
12
13
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
Alarm Points
Communications
Local Off
Remote Off
Loss Of Flow P1
Loss Of Flow P2
Pump Short Cycle
Condensation
Refrigerant Leak
Valve Failure
Customer Alarm 1
Fan Failure Alarm
High Chilled Water Temp
Low Chilled Water Temp
Failed Chilled Water Sensor
High Remote Temp
Low Remote Temp
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
289:0
289:1
289:2
289:3
289:4
289:5
289:6
289:7
289:8
289:9
289:10
290:0
290:1
290:2
290:3
290:4
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
Page 44 of 146
Notes:
1=On / 0=Off
1=On / 0=Off
Divide by 10 for correct value
Divide by 10 for correct value
1=On / 0=Off
43=C / 46=F
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Remote Sensor Problem
High Local Temp
Low Local Temp
Local Sensor Problem
Low Pressure
High Refrigerant Temp
Low Refrigerant Temp
Failed Refrigerant Sensor
Loss Of Power
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
40291:02
290:5
290:6
290:7
290:8
290:9
290:10
291:0
291:1
291:2
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
Setpoints (View)
Temperature Setpoint
Temperature Scale
High Chilled Water Temp
High Air Temp
Low Air Temp
Dewpoint Margin
Restart Delay
40014
14
BS14_x
40015
40016
40017
40018
40019
15
16
17
18
19
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
Control Points (Set)
Unit On / Off
Temperature Setpoint
Dewpoint Margin
40349
40350
40351
49
50
51
BC01_x
BC02_x
BC03_x
Trendable Points (Set)
Temperature
Humidity
Dewpoint
Reports
Trend
Status
Page 45 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit – X-Treme Density Chiller Unit– XDC
Hardware Compatibility
Liebert Units: X-Treme Density Chiller Unit
SiteScan Interface Modules: SiteLink-12, SiteLink-4
BMS interface Modules: SiteLink-12, SiteLink-4
Available Points
SiteScan Availability
Status Points (View)
Pump 1 Status
Pump 2 Status
Cooling %
Compressor 1A status
Compressor 1B status
HG Valve1 %
Compressor 2A status
Compressor 2B status
HG Valve2 %
Refer Temp 1
Refer Temp 2
CW Temp
Unit Status
Scale F or C
Local Temp
Local Humidity
Local Dew Point
Remote Temp
Remote Humidity
Remote Dew Point
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
1=On / 0=Off
1=On / 0=Off
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
Alarm Points
Communications
Local Off
Remote Off
Loss Of Flow Pump 1
Loss Of Flow Pump 2
Pump Short Cycle
Customer Alarm 1
Condensation
Fan Failure Alarm
Page 46 of 146
1=On / 0=Off
1=On / 0=Off
1=On / 0=Off
1=On / 0=Off
Divide by 10 for correct value
Divide by 10 for correct value
Divide by 10 for correct value
1=On / 0=Off
43=C / 46=F
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
40291:06
40291:07
40291:08
40291:09
40291:10
40292:00
40292:01
40292:02
40292:03
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
BA03_x:07
BA03_x:08
BA03_x:09
BA03_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
40021
40022
40023
N/A
N/A
N/A
BS21_x
BS22_x
BS23_x
Alarm Points (cont.)
High Local Temperature
Low Local Temperature
Local Sensor Problem
High Remote Temperature
Low Remote Temperature
Remote Sensor Problem
High Dewpoint
High Head Compressor 1a
High Head Compressor 1b
High Head Compressor 2a
High Head Compressor 2b
Low Suction P Tandem 1
Low Suction P Tandem 2
Short Cycle Compressor 1a
Short Cycle Compressor 1b
Short Cycle Compressor 2a
Short Cycle Compressor 2b
High Refrigerant Temp 1
Low Refrigerant Temp 1
Failed Refrigerant Sensor 1
High Refrigerant Temp 2
Low Refrigerant Temp 2
Failed Refrigerant Sensor 2
High Chilled Water Temp
Low Chilled Water Temp
Failed Chilled Water Sensor
Valve Failure
Loss Of Power
Setpoints (View)
Temp Setpoint
High Temp Setpoint
Low Temp Setpoint
Page 47 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Control Points (Set)
Unit On / Off
Temperature Setpoint
Dewpoint Margin
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40349
40350
-
N/A
N/A
N/A
BC01_x
BC02_x
-
Trendable Points
Temperature
Humidity
Dewpoint
Reports
Trend
Page 48 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit – iCOM DS & Retrofit (2mb version SiteLink)
Hardware Compatibility
Liebert Units: iCOM DS controls and retrofit
SiteScan Interface Modules: SiteLink-12, SiteLink-4, SiteLink-E
BMS interface Modules: SiteLink-12, SiteLink-4, SiteLink-E
Available Points
SiteScan Availability
Status Points (View)
Unit On/Off Status
Unit Standy Status
Control Mode (Auto, Manual)
Control Reason
Fan Status
Cooling Status
Freecooling Status
Hot Water State
Electric Heater State
Humidifier State
De-humidifier State
Audible Alarm State
Cooling Ramp
Heating Ramp
Return Temp
Return Humidity
Run Hours (View)
Conditioner Run Hrs.
Comp 1 Run Hrs.
Comp 2 Run Hrs.
Humidifier Run Hrs.
Reheat 1 Run Hrs.
Reheat 2 Run Hrs.
Reheat 3 Run Hrs.
Setpoints (View)
Front Display Temp Scale
Humidifier Lockout Status
Reheat Lockout Status
Temperature Setpoint
Temp Proportional Band
Temp Deadband
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
BS01
BS02
40003
BS03
40004
40005
40006
BS04
BS05
BS06
40007
40008
40009
40010
BS07
BS08
BS09
BS10
40011
40012
40013
40014
BS11
BS12
BS13
BS14
40015
40016
40017
40018
BS15
BS16
BS17
BS18
Page 49 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Setpoints (View)
Humidity Setpoint
Humd Proportional Band
Humd Deadband
Autorestart Delay
IR Humidifier Flush Rate
High Temperature Alarm
Low Temperature Alarm
High Humidity Alarm
Low Humidity Alarm
Setpoints (Set)
Temperature Setpoint
Temp Proportional Band
Temp Deadband
Humidity Setpoint
Humd Proportional Band
Humd Deadband
Autorestart Delay
IR Humidifier Flush Rate
High Temperature Alarm
Low Temperature Alarm
High Humidity Alarm
Low Humidity Alarm
Commands (Set)
Unit On/Off
Humidifier Lockout
Reheat Lockout
Alarms
Loss Of Comm
Main Fan Overload
Loss of Airflow
Loss of Water Flow
Compressor 1 High Pressure
Compressor 1 Overload
Compressor 2 High Pressure
Compressor 2 Overload
Smoke Detected
Water Detected
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
40019
40020
BS19
BS20
40021
40022
40023
40024
BS21
BS22
BS23
BS24
40350
40350
BC02_1
BC02_2
Scale by 1000 (e.g. 2=2000 Modbus Only)
40351
40351
BC03_1
BC03_2
Scale by 1000 (e.g. 5=5000 Modbus Only)
40349:0,1
40349:2,3
40349:4,5
BC01_1
BC01_2
BC01_3
Bit pair 0,1;1=off, 2=on (Modbus Only)
Bit pair 2,3; 1=normal, 2=lckout (Modbus Only)
Bit pair 4,5; 1=normal, 2=lckout (Modbus Only)
Discrete BACnet alarm objects available –use autodiscover for this unit
40289:0
40289:1
40289:2
BA01_x:0
BA01_x:1
BA01_x:2
BA01_x:3
BA01_x:4
BA01_x:5
BA01_x:6
BA01_x:7
BA01_x:8
BA01_x:9
40289:3
40289:4
40289:5
40289:6
40289:7
40289:8
40289:9
Page 50 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarms (cont.)
Humidifier Problem
Standby Unit On
High Room Temp
Low Room Temp
High Room Humidity
Low Room Humidity
User Alarm #1
User Alarm #2
Unit On
Unit Off
Trends
Return Temperature
Return Humidity
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
BA01_x:10
BA02_X:0
BA02_X:1
BA02_X:2
BA02_X:3
BA02_X:4
BA02_X:5
BA02_X:6
BA02_X:7
BA02_X:8
40289:10
40290:0
40290:1
40290:2
40290:3
40290:4
40290:5
40290:6
40290:7
40290:8
Page 51 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Air Unit – XDP Refrigerant Pumping Unit – XDP W/ iCOM Control
Hardware Compatibility
Liebert Units: XDP Unit w/ iCOM Control
SiteScan Interface Modules: SiteLink-4, SiteLink-12, SiteLink-E (Exec. B Modules)
SiteScan Availability
Status Points (View)
Valve % Open
Pump 1 Status
Pump 2 Status
Supply Temperature
Chilled Water Temperature
Unit Status
Scale F or C
Sensor A Temperature
Sensor A Humidity
Sensor A Dewpoint
Sensor B Temperature
Sensor B Humidity
Sensor B Dewpoint
Run Hours (View)
Pump 1 Run Hours
Pump 2 Run Hours
Setpoints (View)
Temperature Setpoint
High Temp Alarm Setpoint
Low Temp Alarm Setpoint
Dewpoint Alarm Setpoint
Refrigerant Temp Alarm Setpoint
Chilled Water Temp Alarm Setpoint
Dewpoint Margin Setpoint
Temperature Scale F or C
Auto-restart Delay Setpoint
Unit Status
Maintenance Mode Status
Setpoints (Set)
Temperature Setpoint
High Temp Alarm Setpoint
Low Temp Alarm Setpoint
Dewpoint Alarm Setpoint
Modbus
Register
BACnet
Instance
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
40014
40015
BS14_x
BS15_x
40016
40017
40018
40019
40020
40021
40022
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
BS21_x
BS22_x
40023
BS23_x
40024
BS24_x
40350
BC02_x
40351
BC02_x
Notes:
1=On / 0=Off
1=On / 0=Off
Divide by 10 for correct value
Divide by 10 for correct value
Off:1=Rmt, 3=Lcl, 4=Restart, 5=Epo; On=2
43=C / 46=F
0=F 1=C
Page 52 of 146
1=On / 0=Off
On=All alarms disabled
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Setpoints (Set)
Refrigerant Temp Alarm Setpoint
Chilled Water Temp Alarm Setpoint
Temperature Scale F or C
Auto-restart Delay
Unit Run
Alarms (View)
Loss Of Comm
Loss Of Flow Pump 1
Loss Of Flow Pump 2
Fan Failure
Condensation Alarm
Customer Alarm
High Chilled Water Temp
Chilled Water Sensor Fail
High Refrigerant Temp
Low Refrigerant Temp
Refrigerant Sensor Fail
High Temp Sensor A
Low Temp Sensor A
Sensor A Fail
High Temp Sensor B
Low Temp Sensor B
Sensor B Fail
High Dewpoint
Pump Short Cycle
Control Valve Fail
Loss Of Power
Trends (View)
Valve % Open
Refrigerant Supply Temp
Chilled Water Temp
Sensor A Temp
Sensor A Humidity
Sensor A Dewpoint
Sensor B Temp
Sensor B Humidity
Sensor B Dewpoint
Modbus
Register
BACnet
Instance
40349
BC01_x
40289:0
40289:1
40289:2
40289:3
40289:4
40289:5
40289:6
40289:7
40289:8
40289:9
40289:10
40289:11
40289:12
40289:13
40289:14
40289:15
40290:0
40290:1
40290:2
40290:3
40290:4
BA01_x:0
BA01_x:1
BA01_x:2
BA01_x:3
BA01_x:4
BA01_x:5
BA01_x:6
BA01_x:7
BA01_x:8
BA01_x:9
BA01_x:10
BA01_x:11
BA01_x:12
BA01_x:13
BA01_x:14
BA01_x:15
BA02_x:0
BA02_x:1
BA02_x:2
BA02_x:3
BA02_x4
Page 53 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Liebert Power Units
Page 54 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Power Unit – Voltage- Current Monitoring Panel – VCM
Hardware Compatibility
Liebert Units: Datawave, Precision Power Center
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Voltage Out X-Y
Voltage Out Y-Z
Voltage Out Z-X
Voltage Out X-N
Voltage Out Y-N
Voltage Out Z-N
Current Out A
Current Out B
Current Out C
Ground Current
Neutral Current
KVA
Alarm Points
Communications
Output Undervoltage
Output Overvoltage
Transformer Overtemp
Local Alarm #1
Local Alarm #2
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
1
2
3
4
5
6
7
8
9
10
11
12
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
40289:0
40289:1
40289:2
40289:3
40289:4
40289:5
289:0
289:1
289:2
289:3
289:4
289:5
BA01_x:00
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
Page 55 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Trendable Points (Set)
Voltage Out X-Y
Voltage Out Y-Z
Voltage Out Z-X
Voltage Out X-N
Voltage Out Y-N
Voltage Out Z-N
Current Out A
Current Out B
Current Out C
Ground Current
Neutral Current
kVA
Reports
Trend
Status
Page 56 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Power Unit – Power Monitoring Panel – PMP
Hardware Compatibility
Liebert Units: Datawave, Precision Power Center
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current Out A
Current Out B
Current Out C
Ground Current
Neutral Current
KVA
KW
Frequency
% Capacity A
% Capacity B
% Capacity C
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
Divide by 10 for correct value
Divide by 10 for correct value
Discrete BACnet alarm objects available
–use auto-discover for this unit
Alarm Points
Communications
Output Undervoltage
Output Overvoltage
Output Overcurrent
Frequency Deviation
Notes:
40289:00
40289:01
40289:02
40289:03
40289:04
289:00
289:01
289:02
289:03
289:04
Page 57 of 146
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Ground Overcurrent
Transformer Overtemp
Ground Fault
Ground Failure
Liquid Detected
Security Alarm
Phase Rotation/Loss
Datawave Overtemperature
Emergency Shutdown
Load On Bypass
Local Alarm #1
Local Alarm #2
Custom Alarm #1
Custom Alarm #2
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
290:03
290:04
290:05
290:06
290:07
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage In A-N
Voltage In B-N
Voltage In C-N
Page 58 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Trendable Points (Set)
Current Out A
Current Out B
Current Out C
% Capacity A
% Capacity B
% Capacity C
Ground Current
Neutral Current
KW
KVA
Reports
Trend
Status
Page 59 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Power Unit – Voltage-Current-Freq. Monitor Panel – VCF
Hardware Compatibility
Liebert Units: MPU4000, Datawave, Precision Power Center
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Voltage Out X-Y
Voltage Out Y-Z
Voltage Out Z-X
Voltage Out X-N
Voltage Out Y-N
Voltage Out Z-N
Current Out A
Current Out B
Current Out C
Ground Current
Neutral Current
KVA
Frequency
Alarm Points
Communications
Output Undervoltage
Output Overvoltage
Transformer Overtemp
Local Alarm #1
Local Alarm #2
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
1
2
3
4
5
6
7
8
9
10
11
12
13
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
40289:0
40289:1
40289:2
40289:3
40289:4
40289:5
289:0
289:1
289:2
289:3
289:4
289:5
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
Setpoints (View)
None
Control Points (Set)
None
Page 60 of 146
Notes:
Divide by 10 for correct value
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Trendable Points (Set)
Voltage Out X-Y
Voltage Out Y-Z
Voltage Out Z-X
Voltage Out X-N
Voltage Out Y-N
Voltage Out Z-N
Current Out A
Current Out B
Current Out C
Ground Current
Neutral Current
kVA
Reports
Trend
Status
Page 61 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Power Unit – Power Monitoring Panel (Ext. Protocol– PM2)
Hardware Compatibility
Liebert Units: Datawave, Precision Power Center
SiteScan Interface Modules: DC1, DC4, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Voltage In X-Y
Voltage In Y-Z
Voltage In Z-X
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current Out A
Current Out B
Current Out C
Ground Current
Neutral Current
KVA
KW
Frequency
% Capacity A
% Capacity B
% Capacity C
Power Factor
Kilowatt Hours
THD Voltage X
THD Voltage Y
THD Voltage Z
THD Current X
THD Current Y
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_X
BS18_x
BS19_x
BS20_x
BS21_x
Page 62 of 146
Notes:
Divide by 10 for correct value
Divide by 10 for correct value
Divide by 100 for correct value
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
THD Current Z
K Factor Current X
K Factor Current Y
K Factor Current Z
CREST Factor Current X
CREST Factor Current Y
CREST Factor Current Z
Discrete BACnet alarm objects available
–use auto-discover for this unit
Alarm Points
Communications
Output Undervoltage
Output Overvoltage
Output Overcurrent
Frequency Deviation
Ground Overcurrent
Transformer Overtemp
Ground Fault
Ground Failure
Liquid Detected
Security Alarm
Phase Rotation/Loss
Datawave Overtemperature
Emergency Shutdown
Load On Bypass
Local Alarm #1
Local Alarm #2
Output Voltage THD
Custom Alarm #1
Custom Alarm #2
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
290:03
290:04
290:05
290:06
290:07
290:08
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
Setpoints (View)
None
Control Points (Set)
None
Page 63 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage In A-N
Voltage In B-N
Voltage In C-N
Current Out A
Current Out B
Current Out C
% Capacity A
% Capacity B
% Capacity C
Ground Current
Neutral Current
KW
KVA
Power Factor
THD Voltage X
THD Voltage Y
THD Voltage Z
THD Current X
THD Current Y
THD Current Z
K Factor Current X
K Factor Current Y
K Factor Current Z
CREST Factor Current X
CREST Factor Current Y
CREST Factor Current Z
Reports
Trend
Status
Page 64 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Power Unit – Static Transfer Switch PDU – EDS
Hardware Compatibility
Liebert Units: Static Transfer Switch
SiteScan Interface Modules: DC1, DC4, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Transfer Count
Preferred Source
Load On Source 1or 2
Source 1 Voltage A-B
Source 1 Voltage B-C
Source 1 Voltage C-A
Source 1 Current A
Source 1 Current B
Source 1 Current C
Source 1 Frequency
Source 2 Voltage A-B
Source 2 Voltage B-C
Source 2 Voltage C-A
Source 2 Current A
Source 2 Current B
Source 2 Current C
Source 2 Frequency
KW
KVA
Auto Transfer Timer
Nominal Voltage Deviation
Phase Differential Limit
Frequency Deviation
Auto Transfer Enabled
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
40023
40024
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
BS21_x
BS22_x
BS23_x
BS24_x
Page 65 of 146
Notes:
1=Source 1 / 0=Source 2
1=Source 1 / 2=Source 2
Divide by 10 for correct value
Divide by 10 for correct value
Divide by 10 for correct value
1=Enabled / 0=Disabled
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Communications
Logic Failure
Equipment Overtemp
Power Supply 1 Fault
Source 1 Overvoltage
Source 1 Undervoltage
Source 2 Overvoltage
Source 2 Undervoltage
Source 1 Overload
Shorted SCR1
Shorted SCR2
Open SCR1
Open SCR2
Fan Failure
Source 2 Overload
Power Supply 2 Fault
Frequency Deviation
Transfer Inhibit
Auto Retransfer Primed
Out of Synchronization
Source 1 Failure
Source 2 Failure
Auto Retransfer Failed
Overload
Control Fuse 1 Blown
Control Fuse 2 Blown
Source 1 CB1 Open
Source 2 CB2 Open
Output CB3 Open
Custom Alarm 1
Custom Alarm 2
Bypass CB4 Closed
Bypass CB5 Closed
Custom Alarm 3
Custom Alarm 4
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
40291:06
40291:07
40291:08
40291:09
40291:10
40292:00
40292:01
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
290:03
290:04
290:05
290:06
290:07
290:08
290:09
290:10
291:00
291:01
291:02
291:03
291:04
291:05
291:06
291:07
291:08
291:09
291:10
292:00
292:01
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
BA03_x:07
BA03_x:08
BA03_x:09
BA03_x:10
BA04_x:00
BA04_x:01
Page 66 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Custom Alarm 5
Custom Alarm 6
Custom Alarm 7
Custom Alarm 8
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40292:2
40292:3
40292:4
40292:5
292:2
292:3
292:4
292:5
BA04_x:02
BA04_x:03
BA04_x:04
BA04_x:05
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Source 1 Voltage A-B
Source 1 Voltage B-C
Source 1 Voltage C-A
Source 1 Current A
Source 1 Current B
Source 1 Current C
Source 2 Voltage A-B
Source 2 Voltage B-C
Source 2 Voltage C-A
Source 2 Current A
Source 2 Current B
Source 2 Current C
KW
KVA
Reports
Trend
Status
Page 67 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Power Unit – Static Transfer Switch PDU Dual Output – STS
Hardware Compatibility
Liebert Units: Static Transfer Switch with w/ & w/o PDU
SiteScan Interface Modules: DC1, DC4, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Transfer Count
Preferred Source
Load On Source 1 or 2
Source 1 Voltage A-B
Source 1 Voltage B-C
Source 1 Voltage C-A
Source 1 Current A
Source 1 Current B
Source 1 Current C
Source 1 Frequency
Source 2 Voltage A-B
Source 2 Voltage B-C
Source 2 Voltage C-A
Source 2 Current A
Source 2 Current B
Source 2 Current C
Source 2 Frequency
KW
KVA
Auto Transfer Timer
Nominal Voltage Deviation
Phase Differential Limit
Frequency Deviation
Auto Transfer Enabled
Dual Output Breaker Status
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
40023
40024
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
BS21_x
BS22_x
BS23_x
BS24_x
Page 68 of 146
Notes:
1=Source 1 / 0=Source 2
1=Source 1 / 2=Source 2
Divide by 10 for correct value
Divide by 10 for correct value
Divide by 10 for correct value
1=Enabled / 0=Disabled
1=Enabled / 0=Disabled
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Communications
Logic Failure
Equipment Overtemp
Power Supply 1 Fault
Source 1 Overvoltage
Source 1 Undervoltage
Source 2 Overvoltage
Source 2 Undervoltage
Source 1 Overload
Shorted SCR1
Shorted SCR2
Open SCR1
Open SCR2
Fan Failure
Source 2 Overload
Power Supply 2 Fault
Frequency Deviation
Transfer Inhibit
Auto Retransfer Primed
Out of Synchronization
Source 1 Failure
Source 2 Failure
Auto Retransfer Failed
Overload
Control Fuse 1 Blown
Control Fuse 2 Blown
Source 1 CB1 Open
Source 2 CB2 Open
Output CB3 Open
Custom Alarm 1
Custom Alarm 2
Bypass CB4 Closed
Bypass CB5 Closed
Output CB 3B Open
Custom Alarm 4
Custom Alarm 5
Custom Alarm 6
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
40291:06
40291:07
40291:08
40291:09
40291:10
40292:00
40292:01
40292:02
40292:03
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
290:03
290:04
290:05
290:06
290:07
290:08
290:09
290:10
291:00
291:01
291:02
291:03
291:04
291:05
291:06
291:07
291:08
291:09
291:10
292:00
292:01
292:02
292:03
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
BA03_x:07
BA03_x:08
BA03_x:09
BA03_x:10
BA04_x:00
BA04_x:01
BA01_x:02
BA01_x:03
Page 69 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Custom Alarm 7
Custom Alarm 8
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40292:4
40292:5
292:4
292:5
BA01_x:04
BA01_x:05
Setpoints (View)
Auto Transfer Timer
Nominal Voltage Deviation
Phase Differential Limit
Frequency Deviation
Auto Transfer Enabled
Control Points (Set)
None
Trendable Points (Set)
Source 1 Voltage A-B
Source 1 Voltage B-C
Source 1 Voltage C-A
Source 1 Current A
Source 1 Current B
Source 1 Current C
Source 2 Voltage A-B
Source 2 Voltage B-C
Source 2 Voltage C-A
Source 2 Current A
Source 2 Current B
Source 2 Current C
KW
KVA
Reports
Trend
Status
Page 70 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Power Unit – Static Transfer Switch PDU Dual Output – STS-2
Hardware Compatibility
Liebert Units: Static Transfer Switch Extended Protocol w/ & w/o PDU
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Total Transfer Count
Preferred Source
Active Source
Source 1 Volts A-B
Source 1 Volts B-C
Source 1 Volts C-A
Source 1 Current A
Source 1 Current B
Source 1 Current C
Source 1 Frequency
Source 2 Volts A-B
Source 2 Volts B-C
Source 2 Volts C-A
Source 2 Current A
Source 2 Current B
Source 2 Current C
Source 2 Frequency
Output KW
Output KVA
Sync Phase Angle
Total Operating Hours
CB1 Status
CB2 Status
CB3 Status
CB3A Status
CB4 Status
CB5 Status
CB7 Status
CB8 Status
Setpoints (View)
Retransefer Delay
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
40024:0
40024:1
40024:2
40024:3
40024:4
40024:5
40024:6
40024:7
24:0
24:1
24:2
24:3
24:4
24:5
24:6
24:7
BS24_x:00
BS24_x:01
BS24_x:02
BS24_x:03
BS24_x:04
BS24_x:05
BS24_x:06
BS24_x:07
40020
20
BS20_x
Page 71 of 146
Notes:
0=Source 1, 255=Source 2
1=Source 1, 2=Source 2
Divide by 10 for correct value
Divide by 10 for correct value
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Setpoints (Cont)
STS2 Voltage Rating
Max Xfer Phase Angle
Freq. Deviation Trip Point
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40021
40022
40023
21
22
23
BS21_x
BS22_x
BS23_x
Discrete BACnet alarm objects available – use autodiscover for this unit
Alarm Points
Communications Lost
S1 SCR Short
S2 SCR Short
S1 SCR Open
S2 SCR Open
Primary Fan Fail
Control Module Fail
PWR Supply DC A Fail
PWR Supply DC B Fail
PWR Supply SRC 1 AC Fail
PWR Supply SRC 2 AC Fail
PWR Supply Logic Fail
Output Voltage Sense Fail
S1 Voltage Sense Fail
S2 Voltage Sense Fail
S1 SCR Sense Fail
S2 SCR Sense Fail
S1 Current Sense Fail
S2 Current Sense Fail
S1 Gate Drive Fail
S2 Gate Drive Fail
Internal Comm Fail
External Comm Fail
CB1 Shunt Trip Fail
CB2 Shunt Trip Fail
CB6 Neutral Open
Contactor Neutral Fail
Heatsink Overtemp
Equipment Overtemp
Ambient Overtemp
S1 Undervolts
S1 Undervolts (RMS)
S1 Overvolts
S1 Over/Under Freq
Notes:
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40289:11
40289:12
40289:13
40289:14
40289:15
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40290:11
40290:12
40290:13
40290:14
40290:15
40291:00
40291:01
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
289:11
289:12
289:13
289:14
289:15
290:00
290:01
290:02
290:03
290:04
290:05
290:06
290:07
290:08
290:09
290:10
290:11
290:12
290:13
290:14
290:15
291:00
291:01
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA01_x:11
BA01_x:12
BA01_x:13
BA01_x:14
BA01_x:15
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA02_x:11
BA02_x:12
BA02_x:13
BA02_x:14
BA02_x:15
BA03_x:00
BA03_x:01
Page 72 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Discrete BACnet alarm objects available –
use auto-discover for this unit
Alarm Points (cont.)
S1 Fail
S2 Undervolts
S2 Undervolts (RMS)
S2 Overvolts
S2 Over/Under Frequency
S2 Fail
S1 Overcurrent
S2 Overcurrent
S1 I-Peak
S2 I-Peak
Sources Out of Sync
Load On Alternate Source
Auto Retransfer Inhibit
CB1 (S1) Open
CB2 (S2) Open
CB4 (S1 BYP) Closed
CB5 (S2 BYP) Closed
CB3 Output Bkr Open
CB3A Output Bkr Open
S1 Phase Rotation Error
S2 Phase Rotation Error
Transfer Inhibited
Output Undervoltage
History Logs Full
Input Contact #1
Input Contact #2
Input Contact #3
Input Contact #4
Input Contact #5
Input Contact #6
Input Contact #7
Input Contact #8
Notes:
40291:02
40291:03
40291:04
40291:05
40291:06
40291:07
40291:08
40291:09
40291:10
40291:11
40291:12
40291:13
40291:14
40292:00
40292:01
40292:02
40292:03
40292:04
40292:05
40292:06
40292:07
40292:08
40292:09
40292:10
40292:11
40292:12
40292:13
40292:14
40293:00
40293:01
40293:02
40293:03
291:02
291:03
291:04
291:05
291:06
291:07
291:08
291:09
291:10
291:11
291:12
291:13
291:14
292:00
292:01
292:02
292:03
292:04
292:05
292:06
292:07
292:08
292:09
292:10
292:11
292:12
292:13
292:14
293:00
293:01
293:02
293:03
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
BA03_x:07
BA03_x:08
BA03_x:09
BA03_x:10
BA03_x:11
BA03_x:12
BA03_x:13
BA03_x:14
BA04_x:00
BA04_x:01
BA04_x:02
BA04_x:03
BA04_x:04
BA04_x:05
BA04_x:06
BA04_x:07
BA04_x:08
BA04_x:09
BA04_x:10
BA04_x:11
BA04_x:12
BA04_x:13
BA04_x:14
BA05_x:00
BA05_x:01
BA05_x:02
BA05_x:03
Page 73 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Trendable Points (Set)
S1 Amps A
S1 Amps B
S1 Amps C
S2 Amps A
S2 Amps B
S2 Amps C
kVA
kW
Page 74 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Liebert UPS Units
Page 75 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – Multi Module UPS – S600/610 Extended Prot. – MM4
Hardware Compatibility
Liebert Units: Series 600/610 MMS
SiteScan Interface Modules: DC1, DC4, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Input Voltage A-B
Input Voltage B-C
Input Voltage C-A
Output Voltage A-B
Output Voltage B-C
Output Voltage C-A
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
Output Amps Phase B
Output Amps Phase C
DC Bus Voltage
Battery Current
KVA
KW
Critical Bus Frequency
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
Input Amps Phase A
Input Amps Phase B
Input Amps Phase C
Total Operating Hours
Module Number
Total # Battery Discharge
Accumulated Battery Time
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
1
2
3
4
5
6
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
7
8
9
10
11
12
13
14
15
16
17
18
19
20
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
Page 76 of 146
Notes:
Divide by 10 for correct value
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
290:03
290:04
290:05
290:06
290:07
290:08
290:09
290:10
291:00
291:01
291:02
291:03
291:04
291:05
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
Status Points (View)
Accumulated Battery
Amp/Hr
Accumulated Battery kw/Hr
Battery Charge Percent
Battery Time Remaining
Battery Temperature
Alarm Points
Communications
Battery Discharge
Input Failure
Hardware Shutdown
DC Ground Fault
Input CB Open
Output CB Open
DC Cap Fuse Blown
Low Battery Reserve
Output Overload
Rectifier Fuse Blown
Emergency Power Off
Ambient Overtemperature
Battery Disconnected
Control Power Failure
Overload Shutdown
Inverter Fault
Input Current Unbalanced
Inverter Out of Sync
Reverse Power
Low Battery Shutdown
DC Overvoltage Shutdown
Battery Cycle Buffer Full
Equipment Overtemp
Blower/Fan Failure
Overtemperature Shutdown
Battery Room Overtemp
Battery Test Running
Page 77 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Setpoints (View)
Overload Alarm
DC Overvoltage Alarm
Battery Discharging Alarm
Low Battery Alarm
Battery Shutdown 1 Alarm
Battery Shutdown 2 Alarm
Control Points (Set)
None
Trendable Points (Set)
Input Voltage A-B
Input Voltage B-C
Input Voltage C-A
Output Voltage A-B
Output Voltage B-C
Output Voltage C-A
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
Output Amps Phase B
Output Amps Phase C
DC Bus Voltage
KVA
KW
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
Input Amps Phase A
Input Amps Phase B
Input Amps Phase C
Reports
Trend
Status
Page 78 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – Multi Module Series – MMS
Hardware Compatibility
Liebert Units: Series /610MMS, Series 600T MS
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Status Points (View)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current Out A
Current Out B
Current Out C
DC Bus Voltage
Battery Current
KVA
KW
Frequency
% Capacity A
% Capacity B
% Capacity C
Alarm Points
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
Communications
Battery Discharge
Low Battery Reserve
Output Overload
Fuse Cleared
Ambient Overtemperature
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
Notes:
Divide by 10 for correct value
Discrete BACnet alarm objects available –
use auto-discover for this unit
289:00
289:01
289:02
289:03
289:04
289:05
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
Page 79 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Battery Grounded
Battery Disconnected
Module Cooling Failure
Control Power Failure
Overload Shutdown
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40289:06
40289:07
40289:08
40289:09
40289:10
289:06
289:07
289:08
289:09
289:10
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current Out A
Current Out B
Current Out C
% Capacity A
% Capacity B
% Capacity C
DC Bus Voltage
DC Bus Current
kW
kVA
Reports
Trend
Page 80 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – System Control Cabinet – S/610 Ext. Prot. – SC4
Hardware Compatibility
Liebert Units: Series /610 SCC
SiteScan Interface Modules: DC1, DC4, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Input Voltage A-B
Input Voltage B-C
Input Voltage C-A
Output Voltage A-B
Output Voltage B-C
Output Voltage C-A
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
Output Amps Phase B
Output Amps Phase C
KVA
KW
Critical Bus Frequency
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
Bypass Voltage A-B
Bypass Voltage B-C
Bypass Voltage C-A
Output Frequency
Bypass Frequency
Total Operating Hours
Number of Modules in
System
System Number
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
1
2
3
4
5
6
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
7
8
9
10
11
12
13
14
15
16
17
18
19
20
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
Page 81 of 146
Notes:
Divide by 10 for correct value
Divide by 10 for correct value
Divide by 10 for correct value
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Communications
Output Undervoltage
Output Overvoltage
Frequency Deviation
Bypass CB Closed
Output CB Open
Static Switch Disconnected
Output Overload
Emergency Power Off
Load On Bypass
Static Switch Disabled
Control Power Failure
Module #1 Summary Alarm
Module #2 Summary Alarm
Module #3 Summary Alarm
Module #4 Summary Alarm
Module #5 Summary Alarm
Module #6 Summary Alarm
Bypass Not Available
Not OK to Transfer
Bypass Ph Rotation Error
Manual Reset/Transfer
Auto Re-Transfer Primed
Overload Transfer
Module #1 Offline
Module #2 Offline
Module #3 Offline
Module #4 Offline
Module #5 Offline
Module #6 Offline
Custom Alarm #1
Custom Alarm #2
Custom Alarm #3
Custom Alarm #4
Custom Alarm #5
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
40291:06
40291:07
40291:08
40291:09
40291:10
40292:00
40292:01
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
290:03
290:04
290:05
290:06
290:07
290:08
290:09
290:10
291:00
291:01
291:02
291:03
291:04
291:05
291:06
291:07
291:08
291:09
291:10
292:00
292:01
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
BA03_x:07
BA03_x:08
BA03_x:09
BA03_x:10
BA04_x:00
BA04_x:01
Page 82 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Custom Alarm #6
Custom Alarm #7
Custom Alarm #8
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40292:02
40292:03
40292:04
292:02
292:03
292:04
BA04_x:02
BA04_x:03
BA04_x:04
Setpoints (View)
Overload Alarm
Control Points (Set)
None
Trendable Points (Set)
Input Voltage A-B
Input Voltage B-C
Input Voltage C-A
Output Voltage A-B
Output Voltage B-C
Output Voltage C-A
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
Output Amps Phase B
Output Amps Phase C
kVA
KW
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
Bypass Voltage A-B
Bypass Voltage B-C
Bypass Voltage C-A
Reports
Trend
Status
Page 83 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – System Control Cabinet – SCC
Hardware Compatibility
Liebert Units: Series 600/610 SCC
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage In A-N
Voltage In B-N
Voltage In C-N
Current Out A
Current Out B
Current Out C
KVA
KW
Frequency
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
Divide by 10 for correct value
Discrete BACnet alarm objects available –
use auto-discover for this unit
Alarm Points
Communications
Output Overload
Emergency Power Off
Load On Bypass
Static Switch Disabled
Output Out of Limits
Module #1 Summary
Notes:
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
289:00
289:01
289:02
289:03
289:04
289:05
289:06
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
Page 84 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Module #2 Summary
Module #3 Summary
Module #4 Summary
Module #5 Summary
Module #6 Summary
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40289:07
40289:08
40289:09
40289:10
40290:00
289:07
289:08
289:09
289:10
290:00
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage In A-N
Voltage In B-N
Voltage In C-N
Current Out A
Current Out B
Current Out C
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
KW
KVA
Reports
Trend
Status
Page 85 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – Single Module Series – SMS
Hardware Compatibility
Liebert Units: Series 300/500/600 Single Module UPS
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current Out A
Current Out B
Current Out C
DC Bus Voltage
DC Bus Current
KVA
KW
Frequency
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
Alarm Points
Communications
Battery Discharge
Low Battery Reserve
Output Overload
Fuse Cleared
Emergency Power Off
Ambient Overtemperature
Load On Bypass
Static Switch Disabled
Battery Disconnected
Module Cooling Failure
Modbus
Register
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
BACnet
Instance
(Exec. 6
Modules)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
BACnet
Notes:
Instance
(Exec. B
Modules)
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x Divide by 10 for correct value Modbus Only
BS16_x Divide by 10 for correct value Modbus Only
BS17_x Divide by 10 for correct value Modbus Only
BS18_x
BS19_x
BS20_x
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
Page 86 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Control Power Failure
Overload Shutdown
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Voltage In A-B
Voltage In B-C
Voltage In C-A
Voltage Out A-B
Voltage Out B-C
Voltage Out C-A
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current Out A
Current Out B
Current Out C
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
DC Bus Voltage
DC Bus Current
KW
KVA
Reports
Trend
Status
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40290:00
40290:01
290:00
290:01
BA02_x:00
BA02_x:01
Page 87 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – Single Module UPS – S/610 Ext. Prot. – SM4
Hardware Compatibility
Liebert Units: Series /610 SMS
SiteScan Interface Modules: DC1,DC4, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Input Voltage A-B
Input Voltage B-C
Input Voltage C-A
Output Voltage A-B
Output Voltage B-C
Output Voltage C-A
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
Output Amps Phase B
Output Amps Phase C
DC Bus Voltage
Battery Current
KVA
KW
Critical Bus Frequency
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
Bypass Voltage A-B
Bypass Voltage B-C
Bypass Voltage C-A
Input Amps Phase A
Input Amps Phase B
Input Amps Phase C
Bypass Frequency
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
1
2
3
4
5
6
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
40023
40024
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
BS21_x
BS22_x
BS23_x
BS24_x
Page 88 of 146
Notes:
Divide by 10 for correct value
Divide by 10 for correct value
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Status Points (View)
Bypass Frequency
Total Operating Hours
Module Number
Total # Battery Discharge
Accumulated Battery Time
Accumulated Battery
Amp/Hr
Accumulated Battery kW/Hr
Battery Charge Percent
Battery Time Remaining
Battery Temperature
Alarm Points
Communications
Output Undervoltage
Output Overvoltage
Battery Discharge
Frequency Deviation
Input Failure
Hardware Shutdown
DC Ground Fault
Input CB Open
Bypass CB Closed
Output CB Open
Static Switch Disconnected
DC Cap Fuse Blown
Low Battery Reserve
Output Overload
Rectifier Fuse Blown
Emergency Power Off
Ambient Overtemperature
Load On Bypass
Static Switch Disabled
Battery Disconnected
Control Power Failure
Inverter Fault
Input Current Unbalanced
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
290:03
290:04
290:05
290:06
290:07
290:08
290:09
290:10
291:00
291:01
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:01
BA03_x:02
Page 89 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Bypass Not Available
Not OK to Transfer
Bypass Ph Rotation Error
Manual Reset/Transfer
Auto Re-Transfer Primed
Overload Transfer
Reserve Power
Low Battery Shutdown
DC Overvoltage Shutdown
Battery Cycle Buffer Full
Equipment Overtemp
Blower/Fan Failure
Overtemperature Shutdown
Custom Alarm #1
Custom Alarm #2
Custom Alarm #3
Custom Alarm #4
Custom Alarm #5
Custom Alarm #6
Custom Alarm #7
Custom Alarm #8
Battery Room Overtemp
Battery Test Running
Auto-restart Initiated
Auto-restart Failed
Setpoints (View)
Overload Alarm
DC Overvoltage Alarm
Battery Discharging Alarm
Low Battery Alarm
Battery Shutdown 1 Alarm
Battery Shutdown 2 Alarm
Control Points (Set)
None
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40291:02
40291:03
40291:04
40291:05
40291:06
40291:07
40291:08
40291:09
40291:10
40292:00
40292:01
40292:02
40292:03
40292:04
40292:05
40292:06
40292:07
40292:08
40292:09
40292:10
40292:00
40293:01
40293:02
40293:03
40293:04
291:02
291:03
291:04
291:05
291:06
291:07
291:08
291:09
291:10
292:00
292:01
292:02
292:03
292:04
292:05
292:06
292:07
292:08
292:09
292:10
292:00
293:01
293:02
293:03
293:04
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
BA03_x:07
BA03_x:08
BA03_x:09
BA03_x:10
BA04_x:00
BA04_x:01
BA04_x:02
BA04_x:03
BA04_x:04
BA04_x:05
BA04_x:06
BA04_x:07
BA04_x:08
BA04_x:09
BA04_x:10
BA05_x:00
BA05_x:01
BA05_x:02
BA05_x:03
BA05_x:04
Page 90 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Trendable Points (Set)
Input Voltage A-B
Input Voltage B-C
Input Voltage C-A
Output Voltage A-B
Output Voltage B-C
Output Voltage C-A
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Amps Phase A
Output Amps Phase B
Output Amps Phase C
DC Bus Voltage
Battery Current
KVA
KW
% Capacity Phase A
% Capacity Phase B
% Capacity Phase C
Bypass Voltage A-B
Bypass Voltage B-C
Bypass Voltage C-A
Input Amps Phase A
Input Amps Phase B
Input Amps Phase C
Reports
Trend
Status
Page 91 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – Multi-Module SICE 7200 & HiPulse UPS – SMM
Hardware Compatibility
Liebert Units: SICE 7200
SiteScan Interface Modules: DC1, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Output Voltage L1-L2
Output Voltage L2-L3
Output Voltage L3-L1
Output Voltage L1-N
Output Voltage L2-N
Output Voltage L3-N
Output Amps L1
Output Amps L2
Output Amps L3
Output Amps Neutral
Power L1
Power L2
Power L3
Bypass Frequency
Inverter Frequency
Input Voltage L1-L2
Input Voltage L2-L3
Input Voltage L3-L1
Battery Voltage
Battery Amperage
Apparent Power L1
Apparent Power L2
Apparent Power L3
% Load L1
% Load L2
% Load L3
Module Number
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
1
2
3
BS01_x
BS02_x
BS03_x
40004
40005
40006
4
5
6
BS04_x
BS05_x
BS06_x
40007
40008
40009
40010
40011
7
8
9
10
11
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
40012
40013
40014
40015
40016
40017
40018
40019
12
13
14
15
16
17
18
19
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
Page 92 of 146
Notes:
Divide by 10 for correct value
Divide by 10 for correct value
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Status Points (View)
% Battery Charge
Battery Temperature
Battery Time Remaining
Alarm Points
Communications
Bypass Switch Open
Output Switch Open
Rectifier Switch Open
Battery CB Open
Manual Bypass Closed
Bypass Absent
Bypass Overvoltage
Bypass Undervoltage
Bypass Frequency Error
Byp Phase Rotation Error
Bypass SCR Failure
Bypass Off
Bypass Off Via Display
Load On Bypass
Bypass Overtemperature
Rectifier Off
Rectifier Off Via Display
Rectifier Block
Rectifier Current Limit
Rectifier Overtemperature
Rectifier Fuse Failure
Inverter Off
Inverter Off Via Display
Inverter Block
Inverter Current Limit
Inverter Overtemperature
Inverter Non Sync
Inverter Overvoltage
Inverter Undervoltage
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40020
40021
40022
20
21
22
BS20_x
BS21_x
BS22_x
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
40291:06
40291:07
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
290:03
290:04
290:05
290:06
290:07
290:08
290:09
290:10
291:00
291:01
291:02
291:03
291:04
291:05
291:06
291:07
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
BA03_x:07
Page 93 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Inverter Fuse Failure
Output Overvoltage
Output Undervoltage
Output No Voltage
Output Waveform Error
Inverter Frequency Error
Inverter Parallel Error
Contactor Failure
Battery Test
Battery Test Failed
Battery On Load
Battery End of Discharge
Boost Time Expired
DC Slow Overvoltage
DC Undervoltage
Battery Fuse Failure
DC Fast Overvoltage
Transfer Count Block
Overload Shutdown
Overtemperature SD
Emergency Stop
Overload Present
Overload Shutdown TO
Bad EEPROM
Error LRC Par P1
Error LRC Par P2
Error LRC Par P3
Error LRC Alarm History
Error LRC Event History
Internal Battery Low
Error LRC Table
Error LRC Panel
Can Bus No Response
Battery Ground Fault
Back Feed Fault
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40291:08
40291:09
40291:10
40292:00
40292:01
40292:02
40292:03
40292:04
40292:05
40292:06
40292:07
40292:08
40292:09
40292:10
40293:00
40293:01
40293:02
40293:03
40293:04
40293:05
40293:06
40293:07
40293:08
40293:09
40293:10
291:08
291:09
291:10
292:00
292:01
292:02
292:03
292:04
292:05
292:06
292:07
292:08
292:09
292:10
293:00
293:01
293:02
293:03
293:04
293:05
293:06
293:07
293:08
293:09
293:10
BA03_x:08
BA03_x:09
BA03_x:10
BA04_x:00
BA04_x:01
BA04_x:02
BA04_x:03
BA04_x:04
BA04_x:05
BA04_x:06
BA04_x:07
BA04_x:08
BA04_x:09
BA04_x:10
BA05_x:00
BA05_x:01
BA05_x:02
BA05_x:03
BA05_x:04
BA05_x:05
BA05_x:06
BA05_x:07
BA05_x:08
BA05_x:09
BA05_x:10
Page 94 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Alarm Points
Synchronization Inhibited
ECO – Mode On
Setpoints (View)
Power Rating
Configuration
Nominal Voltage
Low Level Input Voltage
Upper Level Input Voltage
Low Level Output Voltage
Upper Level Output
Voltage
Nominal Frequency
Frequency Tolerance
Slew Rate
# of Battery Cells
Rated Capacity
Pre-End Discharge
End of Discharge per Cell
Maximum Voltage per Cell
Year
Month
Day
Hour
Minute
Second
Control Points (Set)
Date & Time Sync
Trendable Points (Set)
Output Voltage L1-L2
Output Voltage L2-L3
Output voltage L3-L1
Page 95 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Trendable Points (Set)
Output Amps L1
Output Amps L2
Output Amps L3
Power L1
Power L2
Power L3
Battery Voltage
Battery Amperage
Apparent Power L1
Apparent Power L2
Apparent Power L3
% Load L1
% Load L2
% Load L3
Reports
Status
Trend
Page 96 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – Systems Cabinet SICE 7200 UPS – SSC
Hardware Compatibility
Liebert Units: SICE 7200
SiteScan Interface Modules: DC1, DC4, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Output Voltage L1-L2
Output Voltage L2-L3
Output Voltage L3-L1
Output Voltage L1-N
Output Voltage L2-N
Output Voltage L3-N
Output Amps L1
Output Amps L2
Output Amps L3
Output Amps Neutral
Power L1
Power L2
Power L3
Bypass Frequency
Input Voltage L1-L2
Input Voltage L2-L3
Input Voltage L3-L1
Battery Voltage
Battery Amperage
Apparent Power L1
Apparent Power L2
Apparent Power L3
% Load L1
% Load L2
% Load L3
Number of Modules in Sys
%Battery Charge
Battery Temperature
Battery Time Remaining
Modbus
Register
40001
40002
40003
BACnet
Instance
(Exec. 6
Modules)
1
2
3
BACnet
Instance
(Exec. B
Modules)
BS01_x
BS02_x
BS03_x
40004
40005
40006
4
5
6
BS04_x
BS05_x
BS06_x
40007
40008
40009
40010
7
8
9
10
BS07_x
BS08_x
BS09_x
BS10_x
40012
40013
40014
40015
40016
40017
40018
40019
12
13
14
15
16
17
18
19
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
40020
40021
40022
20
21
22
BS20_x
BS21_x
BS22_x
Page 97 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
Communications
Bypass Switch Open
Output Switch Open
Battery CB Open
Manual Bypass Closed
Bypass Absent
Bypass Overvoltage
Bypass Undervoltage
Bypass Frequency Error
Bypass Ph Rotation Error
Bypass SCR Failure
Bypass Off
Bypass Off Via Display
Load On Bypass
Bypass Overtemperature
Inverter Non Sync
Output Overvoltage
Output Undervoltage
Output No Voltage
Output Waveform Error
Transfer Count Block
Overload Shutdown
Overtemperature Shutdown
Emergency Stop
Overload Present
Overload Shutdown TO
Bad EEPROM
Error LRC Par P1
Error LRC Par P2
Error LRC Par P3
Error LRC Alarm History
Error LRC Event History
Internal Battery Low
Error LRC Table
Error LRC Panel
Can Bus No Response
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
40291:05
40291:05
40291:05
40291:05
40291:05
40291:05
40291:05
40291:05
BACnet
Instance
(Exec. 6
Modules)
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
290:03
290:04
290:05
290:06
290:07
290:08
290:09
290:10
291:00
291:01
291:02
291:03
291:04
291:05
291:05
291:05
291:05
291:05
291:05
291:05
291:05
291:05
BACnet
Instance
(Exec. B
Modules)
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:05
BA03_x:05
BA03_x:05
BA03_x:05
BA03_x:05
BA03_x:05
BA03_x:05
BA03_x:05
Page 98 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Setpoints ( View)
Power Rating
Configuration
Nominal Voltage
Low Level Input Voltage
Upper Level Input Voltage
Low Level Output Voltage
Upper Level Output Voltage
Nominal Frequency
Frequency Tolerance
Year
Month
Day
Hour
Minute
Second
Trendable Points (Set)
Output Voltage L1-L2
Output Voltage L2-L3
Output Voltage L3-L1
Output Amps L1
Output Amps L2
Output Amps L3
Power L1
Power L2
Power L3
Battery Voltage
Battery Amperage
Apparent Power L1
Apparent Power L2
Apparent Power L3
% Load L1
% Load L2
% Load L3
Reports
Status
Trend
Page 99 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – Single Module SICE 7200 & HiPulse UPS – SSM
Hardware Compatibility
Liebert Units: SICE 7200
SiteScan Interface Modules: DC1, DC4, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Output Voltage L1-L2
Output Voltage L2-L3
Output Voltage L3-L1
Output Voltage L1-N
Output Voltage L2-N
Output Voltage L3-N
Output Amps L1
Output Amps L2
Output Amps L3
Output Amps Neutral
Power L1
Power L2
Power L3
Bypass Frequency
Inverter Frequency
Input Voltage L1-L2
Input Voltage L2-L3
Input Voltage L3-L1
Battery Voltage
Battery Amperage
Apparent Power L1
Apparent Power L2
Apparent Power L3
% Load L1
% Load L2
% Load L3
%Battery Charge
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
1
2
3
BS01_x
BS02_x
BS03_x
40004
40005
40006
4
5
6
BS04_x
BS05_x
BS06_x
40007
40008
40009
40010
40011
7
8
9
10
11
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
40012
40013
40014
40015
40016
40017
40018
40019
40020
12
13
14
15
16
17
18
19
20
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
Page 100 of 146
Notes:
Divide by 10 for correct value
Divide by 10 for correct value
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Status Points (View)
Battery Temperature
Battery Time Remaining
40021
40022
21
22
BS21_x
BS22_x
Alarm Points
Communications
Bypass Switch Open
Output Switch Open
Rectifier Switch Open
Battery CB Open
Manual Bypass Closed
Bypass Absent
Bypass Overvoltage
Bypass Undervoltage
Bypass Frequency Error
Bypass Ph Rotation Error
Bypass SCR Failure
Bypass Off
Bypass Off Via Display
Load On Bypass
Bypass Overtemperature
Rectifier Off
Rectifier Off Via Display
Rectifier Block
Rectifier Current Limit
Rectifier Overtemperature
Rectifier Fuse Failure
Inverter Off
Inverter Off Via Display
Inverter Block
Inverter Current Limit
Inverter Overtemperature
Inverter Non Sync
Inverter Overvoltage
Inverter Undervoltage
Inverter Fuse Failure
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
40291:06
40291:07
40291:08
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
290:03
290:04
290:05
290:06
290:07
290:08
290:09
290:10
291:00
291:01
291:02
291:03
291:04
291:05
291:06
291:07
291:08
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
BA03_x:07
BA03_x:08
Page 101 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Output Overvoltage
Output Undervoltage
Output No Voltage
Output Waveform Error
Inverter Frequency Error
Inverter Parallel Error
Contactor Failure
Battery Test
Battery Test Failed
Battery On Load
Battery End of Discharge
Boost Time Expired
DC Slow Overvoltage
DC Undervoltage
Battery Fuse Failure
DC Fast Overvoltage
Transfer Count Block
Overload Shutdown
Overtemperature Shutdown
Emergency Stop
Overload Present
Overload Shutdown TO
Bad EEPROM
Error LRC Par P1
Error LRC Par P2
Error LRC Par P3
Error LRC Alarm History
Error LRC Event History
Internal Battery Low
Error LRC Table
Error LRC Panel
Can Bus No Response
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40291:09
40291:10
40292:00
40292:01
40292:02
40292:03
40292:04
40292:05
40292:06
40292:07
40292:08
40292:09
40292:10
40293:00
40293:01
40293:02
40293:03
40293:04
40293:05
40293:06
40293:07
40293:08
40293:09
40293:10
40293:10
40293:10
40293:10
40293:10
40293:10
40293:10
40293:10
40293:10
291:09
291:10
292:00
292:01
292:02
292:03
292:04
292:05
292:06
292:07
292:08
292:09
292:10
293:00
293:01
293:02
293:03
293:04
293:05
293:06
293:07
293:08
293:09
293:10
293:10
293:10
293:10
293:10
293:10
293:10
293:10
293:10
BA03_x:09
BA03_x:10
BA04_x:00
BA04_x:01
BA04_x:02
BA04_x:03
BA04_x:04
BA04_x:05
BA04_x:06
BA04_x:07
BA04_x:08
BA04_x:09
BA04_x:10
BA05_x:00
BA05_x:01
BA05_x:02
BA05_x:03
BA05_x:04
BA05_x:05
BA05_x:06
BA05_x:07
BA05_x:08
BA05_x:09
BA05_x:10
BA05_x:10
BA05_x:10
BA05_x:10
BA05_x:10
BA05_x:10
BA05_x:10
BA05_x:10
BA05_x:10
Page 102 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Alarm Points
Setpoints (View)
Power Rating
Configuration
Nominal Voltage
Low Level Input Voltage
Upper Level Input Voltage
Low Level Output Voltage
Upper Level Output Voltage
Nominal Frequency
Frequency Tolerance
Slew Rate
# of Battery Cells
Rated Capacity
Pre-End Discharge
End of Discharge per Cell
Maximum Voltage per Cell
Year
Month
Day
Hour
Minute
Second
Control Points (Set)
Date & Time Sync
Trendable Points (Set)
Output Voltage L1-L2
Output Voltage L2-L3
Output Voltage L3-L1
Output Amps L1
Output Amps L2
Output Amps L3
Power L1
Power L2
Power L3
Battery Voltage
Page 103 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Trendable Points (Set)
Battery Amperage
Apparent Power L1
Apparent Power L2
Apparent Power L3
% Load L1
% Load L2
% Load L3
Reports
Status
Trend
Page 104 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – UPStation S – DCU
Hardware Compatibility
Liebert Units: UPStation S
SiteScan Interface Modules: DCU
BMS interface Modules:
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Status Points (View)
Battery Time Remaining
Last Battery Test Passed
Last Self Test Passed
Voltage In Phase A
Voltage In Phase B
Voltage In Phase C
Current In Phase A
Current In Phase B
Current In Phase C
Voltage Out Phase A
Voltage Out Phase B
Current Out Phase A
Current Out Phase B
Voltage Bypass Phase A
Voltage Bypass Phase B
Current Bypass Phase A
Current Bypass Phase B
VA
Inverter Load
Percentage Load
Inverter Temperature
PFC Temperature
Battery Temperature
Battery Voltage
Battery Current
Input Frequency
Output Frequency
Page 105 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Status Points (View)
Bypass Frequency
Alarm Points
Communications
Inverter
Utility Failure
Ambient Overtemperature
Battery Test In Progress
Input Overvoltage
UPS On Bypass
Receptacle 1 Off
Receptacle 2 Off
Receptacle 3 Off
Receptacle 4 Off
Receptacle 5 Off
Receptacle 6 Off
Receptacle 7 Off
Receptacle 8 Off
Outlet Overload
Input Frequency
Charger Failure
Low Battery
Inverter Undervoltage
Inverter Overvoltage
Bypass Power
UPS Status
Setpoints (View)
None
Control Points (Set)
None
Page 106 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Trendable Points (Set)
Voltage In Phase A
Voltage In Phase B
Voltage In Phase C
Current In Phase A
Current In Phase B
Current In Phase C
Voltage Out Phase A
Voltage Out Phase B
Current Out Phase A
Current Out Phase B
Voltage Bypass Phase A
Voltage Bypass Phase B
Current Bypass Phase A
Current Bypass Phase B
VA
Inverter Load
Percentage Load
Inverter Temperature
PFC Temperature
Battery Temperature
Battery Voltage
Battery Current
Input Frequency
Output Frequency
Bypass Frequency
Reports
Trend
Status
Page 107 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – UPStation S3 – US3
Hardware Compatibility
Liebert Units: UPStation S3
SiteScan Interface Modules: DC1, DC4, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Bypass Voltage A-N
Bypass Voltage B-N
Bypass Voltage C-N
Voltage In A-N
Voltage In B-N
Voltage In C-N
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current Out A
Current Out B
Current Out C
DC Bus Voltage
DC Bus Current
KVA
KW
Inverter Temperature
PFC Temperature
Battery Temperature
Battery Test Status
Input Frequency
Bypass Frequency
Output Frequency
Current In A
Current In B
Current In C
% Capacity
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40016
40017
40018
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40021
40022
40023
16
17
18
1
2
3
4
5
6
7
8
9
10
11
12
13
21
22
23
BS16_x
BS17_x
BS18_x
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS21_x
BS22_x
BS23_x
40024
40014
24
14
BS24_x
BS14_x
40015
15
BS15_x
Page 108 of 146
Notes:
Divide by 10 for correct value Modbus Only
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Status Points (View)
Inverter Status
Utility Status
Bypass Status
Battery Test in Progress
Battery Time Remaining
KVA Size
Alarm Points
Communications
Bypass Failure
Input Failure
Battery Discharging
Low Battery Reserve
Output Overload
Ambient Overtemperature
Output Undervoltage
Output Overvoltage
Input Overvoltage
Charge Failure
UPS Off
Load On Bypass
Utility Failed
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40020
40019
20
19
BS20_x
BS19_x
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
290:01
290:02
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Bypass Voltage A-N
Bypass Voltage B-N
Bypass Voltage C-N
Voltage In A-N
Voltage In B-N
Page 109 of 146
Notes:
Countdown starts at 254
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Trendable Points (Set)
Voltage In C-N
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current In A
Current In B
Current In C
Current Out A
Current Out B
Current Out C
% Capacity
DC Bus Voltage
DC Bus Current
KW
KVA
Battery Time
Reports
Trend
Status
Page 110 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – Single Module Series AP301/302 – SM3
Hardware Compatibility
Liebert Units: Single Module UPS AP301/302
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Bypass Voltage A-N
Bypass Voltage B-N
Bypass Voltage C-N
Voltage in A-N
Voltage in B-N
Voltage in C-N
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current In A
Current In B
Current In C
Current Out A
Current Out B
Current Out C
% Capacity
DC Bus Voltage
DC Bus Current
kVA
kW
Input Frequency
Bypass Frequency
Output Frequency
Last Battery Test Status
Inverter Status
Model Number
KVA Size
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40016
40017
40018
40001
40002
40003
40004
40005
40006
16
17
18
1
2
3
4
5
6
BS16_x
BS17_x
BS18_x
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
40007
40008
40009
40015
40010
40011
40012
40013
7
8
9
15
10
11
12
13
BS07_x
BS08_x
BS09_x
BS15_x
BS10_x
BS11_x
BS12_x
BS13_x
40014
40022
40023
40020
40019
14
22
23
20
19
Page 111 of 146
BS14_x
BS22_x
BS23_x
BS20_x
BS19_x
Notes:
Divide by 10 for correct value
Divide by 10 for correct value
Divide by 10 for correct value Modbus Only
0=failed / 1= passed
0=off / 1=on
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Utility Status
Bypass Status
Battery Test In Progress
Battery Time Remaining
40024
24
BS24_x
0=not present / 1=present
40021
21
BS21_x
Countdown timer starts at 254
Alarm Points
Communications
Bypass Failure
Input Failure
Battery Discharging
Low Battery Reserve
Output Overload
Ambient Overtemperature
Output Undervoltage
Output Overvoltage
Charger Failure
Load On Bypass
Utility Failed
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
290:00
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Bypass Voltage A-N
Bypass Voltage B-N
Bypass Voltage C-N
Voltage In A-N
Voltage In B-N
Voltage In C-N
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current In A
Current In B
Current In C
Current Out A
Current Out B
Page 112 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Current Out C
% Capacity
DC Bus Voltage
DC Bus Current
KW
KVA
Input Frequency
Bypass Frequency
Output Frequency
Battery Time
Reports
Trend
Status
Page 113 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – Single Module UPS – NPower—IMP
Hardware Compatibility
Liebert Units: NPower SMS
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan
Availability
Status Points (View)
Input Voltage A-B
Input Voltage B-C
Input Voltage C-A
Input Frequency
Bypass Voltage A-B
Bypass Voltage B-C
Bypass Voltage C-A
Bypass Frequency
Battery Voltage
Battery Current
Battery Temperature
Battery Time Remaining
Battery Charge Percentage
Output Voltage A-B
Output Voltage B-C
Output Voltage C-A
Output Voltage A-N
Output Voltage B-N
Output Voltage C-N
Output Current A
Output Current B
Output Current C
Output kVA A
Output kVA B
Output kVA C
Output kW A
Output kW B
Modbus
Register
BACnet
Instance
(2.6)
BACnet
SSWEB
40001
40002
40003
1
2
3
BS01_x
BS02_x
BS03_x
40004
40005
40006
4
5
6
BS04_x
BS05_x
BS06_x
40007
40008
40009
7
8
9
BS07_x
BS08_x
BS09_x
40010
40011
40012
10
11
12
BS10_x
BS11_x
BS12_x
40013
40014
40015
40016
40017
40018
40019
40020
13
14
15
16
17
18
19
20
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
Page 114 of 146
Notes:
Scale by 10
Scale by 10
Scale by 10
Scale by 10
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Status Points (View)
Output kW C
Output Frequency
Rated kVA Percentage
Rated kW Percentage
SBS Line Contact On/Off
SBS Load Contact On/Off
Input Delta Contact On/Off
Input Wye Contact On/Off
Output Contact On/Off
Battery Breaker On/Off
Trap Filter Contact On/Off
Int. Mbypass Sw. On/Off
Ext. Mbypass Sw. On/Off
Alarm Points
Communications
Battery Fuse Fail
Rectifier Fuse Fail
Trap Fuse Fail
Battery Overcharged
Bypass Overload Shutdown
Inverter Overload
Inverter Fuse Failure
Overvoltage Transfer
Undervoltage Transfer
Inverter Curr.Lim. Transfer
EPO Shutdown
Rectifier Fail
Inverter Fail
Hardware Shutdown
On Battery
Input Current Limit
Battery CB Open
Battery Discharging
SBS Overload Phase A
SBS Overload Phase B
Modbus
Register
BACnet
Instance
(2.6)
BACnet
SSWEB
40021
40022
40023
40024
21
22
23
24
BS21_x
BS22_x
BS23_x
BS24_x
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40289:11
40289:12
40289:13
40289:14
40289:15
40290:00
40290:01
40290:02
40290:03
40290:04
289:00
289:01
289:02
289:03
289:04
289:05
289:06
289:07
289:08
289:09
289:10
289:11
289:12
289:13
289:14
289:15
290:00
290:01
290:02
290:03
290:04
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA01_x:11
BA01_x:12
BA01_x:13
BA01_x:14
BA01_x:15
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
Page 115 of 146
Notes:
Scale by 10
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarms Points
SBS Overload Phase C
Inverter Current Limit
Inverter Overload Phase A
Inverter Overload Phase B
Inverter Overload Phase C
Low PF Warning
Battery Ground Fault
EPO Latched
SBS Unable
Inverter Off By User
Battery Low Warning
Battery Test Fail
User Shutdown
Battery Not Charged
Load On Bypass
Input Contact #1
Input Contact #2
Input Contact #3
Input Contact #4
Input Contact #5
Input Contact #6
Input Contact #7
Input Contact #8
Common Alarm
Trendable Points
Battery Current
Output Current A
Output Current B
Output Current C
Ouptut kVA A
Ouptut kVA B
Ouptut kVA C
Ouptut kW A
Ouptut kW B
Ouptut kW C
% Rated kVA
% Rated kW
Reports
Trend & Status
Modbus Register
BACnet
Instance
(2.6)
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40290:11
40290:12
40290:13
40290:14
40290:15
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
40291:06
40291:07
40291:08
40291:09
40291:10
40291:11
40291:12
290:05
290:06
290:07
290:08
290:09
290:10
290:11
290:12
290:13
290:14
290:15
291:00
291:01
291:02
291:03
291:04
291:05
291:06
291:07
291:08
291:09
291:10
291:11
291:12
Page 116 of 146
BACnet
SSWEB
Notes:
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA02_x:11
BA02_x:12
BA02_x:13
BA02_x:14
BA02_x:15
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA02_x:11
BA02_x:12 Common Alarm - alarms not listed here
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – Single Module UPS – NX—PNX
Hardware Compatibility
Liebert Units: NX
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Input Frequency
Output Frequency
Bypass Frequency
Battery Voltage
Battery Current
Battery Charge Percentage
Battery Time Remaining
Battery Temperature
Input Voltage Vab
Input Voltage Vbc
Input Voltage Vca
Bypass Volts A
Bypass Volts B
Bypass Volts C
Output Volts A
Output Volts B
Output Volts C
Output Current A
Output Current B
Output Current C
Output % A
Output % B
Output % C
Output Va A
Output Va B
Output Va C
Output Watts A
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
40001
BS01_x
Scale By 10
40002
40003
BS02_x
BS03_x
Scale by 10
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
Scale by 10
Scale by 10
Scale by 10
40017
BS17_x
Average of A,B,C
40018
40019
40020
40021
BS18_x
BS19_x
BS20_x
BS21_x
Page 117 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Available Points
SiteScan Availability
Status Points (View)
Output Watts B
Output Watts C
System Output Va A
System Output Va B
System Output Va C
Alarm Points
Loss Of Communications
Input Switch Open
Generator Input Disconnected
Main AC Neutral Lost
Load On Battery
Reserved
Load On Joint Mode
Load On Bypass
No Power Supplied
Overload Bypass
Max Xfer Bypass
False Operation
UPS Overload
Battery Shutdown Imminent
Inverter Not Sync
DC Under Voltage Shutdown
Inverter Fault
Inverter DC Offset Overrun
Inverter Contactor Fail
Inverter Over Current
Inverter Communication Fail
Rectifier Input Fuse Blown
Rectifier Startup Fail
Rectifier Fault
Rectifier Over Current
Rectifier Communication Fail
Control Power Fail
Fan Fail
Battery Overtemperature
Ambient Overtemperature
Rectifier Overtemperature
Rectifier Inductor Overtemp
Modbus
Register
BACnet BACnet Instance
Instance
(Exec. B
(Exec. 6
Modules)
Modules)
40022
40023
BS22_x
BS23_x
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40289:11
40289:12
40289:13
40289:14
40289:15
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40290:11
40290:12
40290:13
40290:14
40290:15
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA01_x:11
BA01_x:12
BA01_x:13
BA01_x:14
BA01_x:15
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA02_x:11
BA02_x:12
BA02_x:13
BA02_x:14
BA02_x:15
Page 118 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Available Points
SiteScan Availability
Modbus
Register
BACnet
BACnet
Instance (Exec. Instance (Exec.
6 Modules)
B Modules)
Alarm Points
Inverter Overtemperature
Inverter Inductor Overtemp
Battery Converter Overtemp
Battery Balancer Overtemp
Input Power Failure
Input Brown Out
Input Frequency Deviation
Input Phase Rotation
Bypass SBS Unable
Bypass Input Fault
Output Over Voltage
Charger Failure
Battery Fault
Battery Contactor Fail
Battery Converter Fail
Battery Converter Overcurrent
Battery Balancer Fault
Battery Balancer Over Current
Parallel System Low Batt Warn
Parallel Load Share Fault
Parallel System Fault
Parallel Connection Error
Parallel System Over Load
Parallel Transfer To Bypass
Parallel Communication Fail
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
40291:06
40291:07
40291:08
40291:09
40291:10
40291:11
40291:12
40291:13
40291:14
40291:15
40292:00
40292:01
40292:02
40292:03
40292:04
40292:05
40292:06
40292:07
40292:08
Control Points (Set)
None
Trend Points
Output Current Phase A
Output Current Phase B
Output Current Phase C
Output % (Avg 3 Phases)
Page 119 of 146
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
BA03_x:07
BA03_x:08
BA03_x:09
BA03_x:10
BA03_x:11
BA03_x:12
BA03_x:13
BA03_x:14
BA03_x:15
BA04_x:00
BA04_x:01
BA04_x:02
BA04_x:03
BA04_x:04
BA04_x:05
BA04_x:06
BA04_x:07
BA04_x:08
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – HiNet – PHN
Hardware Compatibility
Liebert Units: HiNet
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
UPS Load VA
UPS Load Watt
Input Frequency
Output Frequency
Load On Inverter
UPS Load On Bypass
UPS DC-DC Status
Battery Voltage
Battery Current
Battery Charge Percentage
Ambient Temperature
Input Va
Input Vb
Input Vc
Input Current Ia
Input Current Ib
Input Current Ic
Output Va
Output Vb
Output Vc
Output Current Ia
Output Current Ib
Output Current Ic
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
40023
BACnet
Instance
(Exec. B
Modules)
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
BS21_x
BS22_x
BS23_x
Page 120 of 146
Notes:
Scale By 10
Scale By 10
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Available Points
SiteScan Availability
Alarm Points
Loss Of Communications
Load On Battery
Reserved
Load On Bypass – Permanent
UPS Overload
Battery Shutdown imminent
Inverter Not Sync
Input Power Failure
Bypass SBS SCR Open fault
Bypass Input Fault
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
40024
BS24_x
Setpoints (View)
Device Type
UPS Sub Module Number
UPS Battery Count
UPS Outlet Circuitry Supported
UPS Type Is Offline
UPS Type Is Interactive
UPS Has Dual Inputs
Setpoints (Set)
None
Trend Points
Load VA
Load Watts
Input Current A
Input Current B
Input Current C
Output Current A
Output Current B
Output Current C
Page 121 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – NFinity – PNF
Hardware Compatibility
Liebert Units: Nfinity
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
UPS Load VA
UPS Load Watt
UPS Load Percent
Input Frequency
Output Frequency
Bypass Frequency
UPS Load On Bypass
Power Factor Correction Stat
Battery Voltage
Battery Charge Percentage
Battery Time Remaining
Battery Temperature
Transformer Temperature
Input Voltage
Input Current
Bypass Voltage
Bypass Current
Output Voltage
Output Current
Battery Discharge Count
Battery Discharge Time
Setpoints (View)
Maximum System Capacity
Auto Restart Delay
Auto Battery Test Enable
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
BS21_x
40022
40023
40024
BS22_x
BS23_x
BS24_x
Page 122 of 146
Notes:
Scale By 10
Scale By 10
Scale By 10
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Setpoints (Set)
None
Alarm Points
Loss Of Communications
Load On Battery
Load On Bypass
Overload Bypass
Fault Bypass
Manual Bypass
Manual Xfer Prohibited
UPS Overload
Shutdown Pending
Battery Shutdown imminent
Fan Fail
Air Filter Bad
Transformer Overtemperature
Internal Comm Failure
New Event Logged
Input Power Failure
Red Power Module Low
Device Active Alarm
Main Control Module Alarm
Redundant Module Alarm
Power Module Alarm
Battery Module Alarm
Main Control Module Fail
Red. Control Module Fail
User Interface Module Fail
Power Module Failure
Battery Module Failure
Overtemp Shutdown
Overload Shutdown
Output Short Shutdown
Low Battery Shutdown
Remote Shutdown
EPO Shutdown
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40289:11
40289:12
40289:13
40289:14
40289:15
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
40290:09
40290:10
40290:11
40290:12
40290:13
40290:14
40290:15
40291:00
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA01_x:11
BA01_x:12
BA01_x:13
BA01_x:14
BA01_x:15
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA02_x:11
BA02_x:12
BA02_x:13
BA02_x:14
BA02_x:15
BA03_x:00
Page 123 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Trend Points
vA
Watts
Input Current
Bypass Current
Output Current
Page 124 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – GXT – PGX
Hardware Compatibility
Liebert Units: GXT
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
UPS Load VA
UPS Load Watt
UPS Load Percent
Input Frequency
Output Frequency
Bypass Frequency
Load On Inverter
UPS Load On Bypass
Battery Test Result
DC-DC Status
Inverter Ready Status
Power Factor Correction Stat
Battery Charge Comp Status
Replace Battery Status
Battery Test In Progress
Battery Charge Status
Battery Voltage
Battery Charge Percentage
Battery Deplete Time
Ambient Temperature
Input Voltage Vab
Input Voltage Van
Bypass Voltage Vab
Bypass Voltage Van
Output Voltage Vab
Output Voltage Van
Output Current Ia
Output Load % Phase A
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
40007
40008
40009
BS07_x
BS08_x
BS09_x
40010
40011
40012
40013
40014
40015
40016
40017
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
Page 125 of 146
Notes:
Scale By 10
Scale By 10
Scale By 10
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Available Points
SiteScan Availability
Status Points (View)
Output VA Phase A
Output Var Phase A
Output Watt Phase A
Input Voltage Vbn
Bypass Voltage Vbn
Output Voltage Vbn
Output Current Ib
Output Load % Phase B
Output VA Phase B
Output Watt Phase B
UPS Black Out Count
UPS Brown Out Count
PhaseA Maximum Input Va
PhaseA Minimum Input Va
PhaseA Maximum Output Va
PhaseA Minimum Output Va
Load Circuit Output State
Setpoints (View)
Device Type
UPS Sub Module Number
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40018
40019
40020
BS18_x
BS19_x
BS20_x
40021
40022
40023
BS21_x
BS22_x
BS23_x
40024
BS24_x
Outlet Circuitry Supported
Nominal VA
Nominal Input Voltage
Nominal Output Voltage
Nominal Bypass Voltage
Nominal Input Current
Nominal Input Frequency
Nominal Output Frequency
Nominal Power Factor
Nominal Battery Voltage
Auto Restart Delay
Battery Low Alarm time
Auto Restart Enable
Audible Alarm Enable
Auto Battery Test Enable
Page 126 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Setpoints (View)
UPS Type Is Offline
UPS Type Is Interactive
UPS Has Dual Inputs
Setpoints (View)
None
Control Points (Set)
Delayed Output Off
Delayed Output Off/Reboot
Delayed Output On
Battery Test Command
Alarm Silence
Abort Command
Alarm Points
Loss Of Comm
Load On Battery
Reserved
UPS Overload
UPS Shutdown Pending
Battery Shutdown Imminent
Overtemperature
Input Current Unbalance
Input Power Failure
Input Over Voltage
Input Under Voltage
Input Frequency Deviation
Bypass Input Fault
Output Undervoltage
Output Overvoltage
Shutdown – Overtemp
Shutdown – Overload
Shutdown – DC Bus OV
Shutdown - Output Short
Shutdown - L-N Swapped
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40289:11
40289:12
40289:13
40289:14
40289:15
40290:00
40290:01
40290:02
40290:03
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA01_x:11
BA01_x:12
BA01_x:13
BA01_x:14
BA01_x:15
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
Page 127 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Alarm Points
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
- Low Battery
- By Remote
- UV Startup
- PFC Startup
- External Signal
40290:04
40290:05
40290:06
40290:07
40290:08
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
Trend Points
Load VA
Load Watts
Output Current A
Output VA A
Output VAR A
Output Watts A
Output Current B
Output VA B
Output Watts B
Page 128 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
UPS Unit – PSI – PPS
Hardware Compatibility
Liebert Units: PSI
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
UPS Load VA
UPS Load Watt
UPS Load Percent
Input Frequency
Output Frequency
Load On Inverter
Battery Test Result
UPS Booster On Status
UPS Buck On Status
UPS DC-DC Status
UPS Battery Charger State
Replace Battery
Battery Test In Progress
UPS Battery Charge Status
Battery Voltage
Battery Charge Percentage
Battery Time Remaining
Ambient Temperature
Input Va
Input Current Ia
Output Va
Output Current Ia
UPS Black Out Count
UPS Brown Out Count
PhaseA Maximum Input Va
PhaseA Minimum Input Va
PhaseA Maximum Output Va
PhaseA Minimum Output Va
Load Circuit Output State
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
40007
BS07_x
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
40023
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
BS21_x
BS22_x
BS23_x
Page 129 of 146
Notes:
Scale By 10
Scale By 10
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Available Points
SiteScan Availability
Set Points (View)
Device Type
Sub Module Number
Outlet Circuitry Supported
Nominal VA
Nominal Input Voltage
Nominal Output Voltage
Nominal Input Current
Nominal Input Frequency
Nominal Output Frequency
Nominal Power Factor
Nominal Battery Voltage
Battery Last Min Rated Load
Battery Float Voltage
Auto Restart Delay
Ambient Overtemp Alarm
Overtemp Failure Threshold
Auto Restart Enable
Audible Alarm Enable
Auto Battery Test Enable
UPS Type Is Offline
UPS Type Is Interactive
UPS Has Dual Inputs
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
40024
BACnet
Instance
(Exec. B
Modules)
BS24_x
Setpoints (Set)
None
Control Points (Set)
Turn Output Off with Delay
Delayed Output Off/Reboot
Delayed Output On
Battery Test Command
Alarm Silent command
Abort previous Command
Reset Battery Stats Cmd
Reset Stat Counters Cmd
Page 130 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Available Points
SiteScan Availability
Alarm Points
Loss Of Comm
Load On Battery
Reserved
UPS Overload
UPS Shutdown Pending
Battery Shutdown
Overtemperature
Input Current Unbalance
Input Power Failure
Input Over Voltage
Input Under Voltage
Input Frequency Deviation
Bypass Input Fault
Output Undervoltage
Output Overvoltage
Shutdown – Overtemp
Shutdown – Overload
Shutdown – DC Bus OV
Shutdown - Output Short
Shutdown - L-N Swapped
Shutdown - Low Battery
Shutdown - By Remote
Shutdown - UV Startup
Shutdown - PFC Startup
Shutdown - External Signal
Modbus
Register
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40289:11
40289:12
40289:13
40289:14
40289:15
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
40290:07
40290:08
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA01_x:11
BA01_x:12
BA01_x:13
BA01_x:14
BA01_x:15
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
BA02_x:07
BA02_x:08
Trend Points
Load VA
Load Watts
Output Current A
Output VA A
Output VAR A
Output Watts A
Output Current B
Output VA B
Output Watts B
Page 131 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Liebert Monitoring Modules
Page 132 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Contact Closure Module – CCM
Hardware Compatibility
Liebert Units: CCM200, RCM8, VSM100
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Contact 1
Contact 2
Contact 3
Contact 4
Contact 5
Contact 6
Contact 7
Contact 8
Contact 9
Contact 10
Contact 11
Contact 12
Contact 13
Contact 14
Contact 15
Contact 16
Contact 17
Contact 18
Contact 19
Contact 20
Contact 21
Contact 22
Contact 23
Contact 24
Contact 25
Contact 26
Contact 27
Page 133 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Contact 28
Contact 29
Contact 30
Contact 31
Contact 32
Discrete BACnet alarm objects available –
use auto-discover for this unit
Alarm Points (See Note)
Communications
40001:0
1:0
BS01_x:00
Contact 1
Contact 2
Contact 3
Contact 4
Contact 5
Contact 6
Contact 7
Contact 8
Contact 9
Contact 10
Contact 11
Contact 12
Contact 13
Contact 14
Contact 15
Contact 16
Contact 17
Contact 18
Contact 19
Contact 20
Contact 21
Contact 22
Contact 23
Contact 24
Contact 25
Contact 26
Contact 27
40001:1
40001:2
40001:3
40001:4
40001:5
40001:6
40001:7
40001:8
40001:9
40001:10
40002:0
40002:1
40002:2
40002:3
40002:4
40002:5
40002:6
40002:7
40002:8
40002:9
40002:10
40003:0
40003:1
40003:2
40003:3
40003:4
40003:5
1:1
1:2
1:3
1:4
1:5
1:6
1:7
1:8
1:9
1:10
2:0
2:1
2:2
2:3
2:4
2:5
2:6
2:7
2:8
2:9
2:10
3:0
3:1
3:2
3:3
3:4
3:5
BS01_x:01
BS01_x:02
BS01_x:03
BS01_x:04
BS01_x:05
BS01_x:06
BS01_x:07
BS01_x:08
BS01_x:09
BS01_x:10
BS02_x:00
BS02_x:01
BS02_x:02
BS02_x:03
BS02_x:04
BS02_x:05
BS02_x:06
BS02_x:07
BS02_x:08
BS02_x:09
BS02_x:10
BS03_x:00
BS03_x:01
BS03_x:02
BS03_x:03
BS03_x:04
BS03_x:05
Page 134 of 146
Note: The first three status registers are used to
report Alarm Points.
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Contact 28
Contact 29
Contact 30
Contact 31
Contact 32
Modbus
Register
40003:6
40003:7
40003:8
40003:9
40003:10
BACnet
Instance
(Exec. 6
Modules)
3:6
3:7
3:8
3:9
3:10
BACnet
Instance
(Exec. B
Modules)
BS03_x:06
BS03_x:07
BS03_x:08
BS03_x:09
BS03_x:10
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
None
Reports
Status
Page 135 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Water/Liquid Detection Unit – WDU
Hardware Compatibility
Liebert Units: LDS1000, LDS750
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Distance
Feet or Meters
Alarm Points
Communications
Cable Fault
Liquid Detected
Modbus Register
BACnet Instance
40001
40002
1
2
40289:0
40289:1
40289:2
289:0
289:1
289:2
Reports
Status
Page 136 of 146
Notes:
1=feet / 0=meters
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Remote Autochangeover – RAC
Hardware Compatibility
Liebert Units: RAC2-8
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Unit 6
Unit 7
Unit 8
Alarm Points
Communications
Common Alarm 1
Common Alarm 2
Common Alarm 3
Common Alarm 4
Common Alarm 5
Common Alarm 6
Common Alarm 7
Common Alarm 8
Emergency Power Operation
EPO All Units
High Temperature
Low Temperature
High Humidity
Low Humidity
Manual Override
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
40001
40002
40003
40004
40005
40006
40007
40008
1
2
3
4
5
6
7
8
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
1=on / 0=0ff
40289:0
40289:1
40289:2
40289:3
40289:4
40289:5
40289:6
40289:7
40289:8
40289:9
40289:10
40290:0
40290:1
40290:2
40290:3
40290:4
289:0
289:1
289:2
289:3
289:4
289:5
289:6
289:7
289:8
289:9
289:10
290:0
290:1
290:2
290:3
290:4
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
Reports
Status
Page 137 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Temperature/Humidity Module – THM
Hardware Compatibility
Liebert Units: THM100
SiteScan Interface Modules: DC1, DC4, DC12, SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Temperature Sensor 1
Humidity Sensor 1
Temperature Sensor 2
Humidity Sensor 2
Temperature Sensor 3
Humidity Sensor 3
Temperature Sensor 4
Humidity Sensor 4
Temperature Sensor 5
Humidity Sensor 5
Temperature Sensor 6
Humidity Sensor 6
Temperature Sensor 7
Humidity Sensor 7
Temperature Sensor 8
Humidity Sensor 8
Alarm Points
Communications
High/Low Temp Sensor 1
High/Low Humidity Sensor 1
High/Low Temp Sensor 2
High/Low Humidity Sensor 2
High/Low Temp Sensor 3
High/Low Humidity Sensor 3
High/Low Temp Sensor 4
High/Low Humidity Sensor 4
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
40289:0
289:0
BA01_x:00
Notes:
Alarm threshold determined by others
Alarm threshold determined by others
Alarm threshold determined by others
Alarm threshold determined by others
Alarm threshold determined by others
Alarm threshold determined by others
Alarm threshold determined by others
Alarm threshold determined by others
Page 138 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
High/Low Temp Sensor 5
High/Low Humidity Sensor 5
High/Low Temp Sensor 6
High/Low Humidity Sensor 6
High/Low Temp Sensor 7
High/Low Humidity Sensor 7
High/Low Temp Sensor 8
High/Low Humidity Sensor 8
Setpoints (View)
High/Low Temp Sensor 1
High/Low Humidity Sensor 1
High/Low Temp Sensor 2
High/Low Humidity Sensor 2
High/Low Temp Sensor 3
High/Low Humidity Sensor 3
High/Low Temp Sensor 4
High/Low Humidity Sensor 4
High/Low Temp Sensor 5
High/Low Humidity Sensor 5
High/Low Temp Sensor 6
High/Low Humidity Sensor 6
High/Low Temp Sensor 7
High/Low Humidity Sensor 7
High/Low Temp Sensor 8
High/Low Humidity Sensor 8
Control Points (Set)
High/Low Temp Sensor 1
High/Low Humidity Sensor 1
High/Low Temp Sensor 2
High/Low Humidity Sensor 2
High/Low Temp Sensor 3
High/Low Humidity Sensor 3
High/Low Temp Sensor 4
High/Low Humidity Sensor 4
High/Low Temp Sensor 5
Page 139 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
Trend Points
Temp Sensor 1
Humidity Sensor 1
Temp Sensor 2
Humidity Sensor 2
Temp Sensor 3
Humidity Sensor 4
Temp Sensor 4
Humidity Sensor 4
Temp Sensor 5
Humidity Sensor 5
Temp Sensor 6
Humidity Sensor 6
Temp Sensor 7
Humidity Sensor 7
Temp Sensor 8
Humidity Sensor 8
Page 140 of 146
BACnet
Instance
(Exec. B
Modules)
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Water/Liquid Detection Unit LDS5000 – WD5
Hardware Compatibility
Liebert Units: LDS5000
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
Installed Cable Footage 1
Installed Cable Footage 2
Not Used – Spare
Not Used – Spare
Leak Det Footage Cable 1
Leak Det Footage Cable 2
Not Used – Spare
Not Used – Spare
Leakage Current Cable 1
Leakage Current Cable 2
Not Used – Spare
Not Used – Spare
Feet / Meters
Alarm Points
Communications
Leak Detected Cable 1
Cable Fault Cable 1
Leak Detected Cable 2
Cable Fault Cable 2
Not Used – Spare
Not Used – Spare
Not Used – Spare
Not Used – Spare
Setpoints (View)
None
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
1
2
3
4
5
6
7
8
9
10
11
12
13
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
289:0
289:1
289:2
289:3
289:4
289:5
289:6
289:7
289:8
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
Control Points (Set)
Alarm Silence
Alarm Reset
Page 141 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Universal Monitor – UVM
Hardware Compatibility
Liebert Units: Universal Monitor – UVM
SiteScan Interface Modules: SiteLink (All)
BMS interface Modules: SiteLink (All)
Available Points
SiteScan Availability
Status Points (View)
I/O Extender Card Status
Input Contact #1 Status
Input Contact #2 Status
Input Contact #3 Status
Input Contact #4 Status
Input Contact #5 Status
Input Contact #6 Status
Input Contact #7 Status
Input Contact #8 Status
Input Contact #9 Status
Input Contact #10 Status
Input Contact #11 Status
Input Contact #12 Status
Input Contact #13 Status
Input Contact #14 Status
Input Contact #15 Status
Input Contact #16 Status
Input Contact #17 Status
Input Contact #18 Status
Input Contact #19 Status
Input Contact #20 Status
Input Contact #21 Status
Input Contact #22 Status
Input Contact #23 Status
Input Contact #24 Status
Output Contact #1 Status
Output Contact #2 Status
Output Contact #3 Status
Output Contact #4 Status
Output Contact #5 Status
Output Contact #6 Status
Output Contact #7 Status
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
BS01_x
40001
Page 142 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Status Points (View)
Output Contact #8 Status
Output Contact #9 Status
Output Contact #10 Status
Output Contact #11 Status
Output Contact #12 Status
Output Contact #13 Status
Output Contact #14 Status
Output Contact #15 Status
Output Contact #16 Status
Sensor #1 High Status
Sensor #1 Low Status
Sensor #2 High Status
Sensor #2 Low Status
Sensor #3 High Status
Sensor #3 Low Status
Sensor #4 High Status
Sensor #4 Low Status
Sensor #1 Reading
Sensor #2 Reading
Sensor #3 Reading
Sensor #4 Reading
Alarm Points
Input #1 Alarm
Input #2 Alarm
Input #3 Alarm
Input #4 Alarm
Input #5 Alarm
Input #6 Alarm
Input #7 Alarm
Input #8 Alarm
Input #9 Alarm
Input #10 Alarm
Input #11 Alarm
Input #12 Alarm
Input #13 Alarm
Input #14 Alarm
Input #15 Alarm
Input #16 Alarm
Input #17 Alarm
Input #18 Alarm
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40002
40003
40004
40005
BS02_x
BS03_x
BS04_x
BS05_x
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
Page 143 of 146
Notes:
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Alarm Points
Input #19 Alarm
Input #20 Alarm
Input #21 Alarm
Input #22 Alarm
Input #23 Alarm
Input #24 Alarm
Sensor #1 High Alarm
Sensor #1 Low Alarm
Sensor #2 High Alarm
Sensor #2 Low Alarm
Sensor #3 High Alarm
Sensor #3 Low Alarm
Sensor #4 High Alarm
Sensor #4 Low Alarm
Loss of Power
Low Battery Alarm
Battery Unplugged
Check Battery
Exp board loss of comm
Configuration Changed
Loss of Comm
Setpoints (View)
Sensor #1 High Threshold SP
Sensor #1 Low Threshold SP
Sensor #2 High Threshold SP
Sensor #2 Low Threshold SP
Sensor #3 High Threshold SP
Sensor #3 Low Threshold SP
Sensor #4 High Threshold SP
Sensor #4 Low Threshold SP
Control Points (Set)
Sensor High Threshold
Sensor Low Threshold
Alarm Silence
Alarm Reset
Trendable Points (Set)
Sensor Readings
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
40290:07
40290:08
40290:09
40290:10
40291:00
40291:01
40291:02
40291:03
40291:04
40291:05
40291:06
40291:07
40291:08
40291:09
40291:10
40292:00
40292:01
40292:02
40292:03
40292:04
40292:05
BA02_x:07
BA02_x:08
BA02_x:09
BA02_x:10
BA03_x:00
BA03_x:01
BA03_x:02
BA03_x:03
BA03_x:04
BA03_x:05
BA03_x:06
BA03_x:07
BA03_x:08
BA03_x:09
BA03_x:10
BA04_x:00
BA04_x:01
BA04_x:02
BA04_x:03
BA04_x:04
BA04_x:05
40006
40007
40008
40009
40010
40011
40012
40013
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
Notes:
Sensors 1-4
Sensors 1-4
Sensors 1-4
Page 144 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
Autochangeover Controller – AC8
Hardware Compatibility
Liebert Units: Autochangeover Controller – AC8
SiteScan Interface Modules: SiteLink-4, SiteLink-12, SiteLink-E series
BMS interface Modules: SiteLink-4, SiteLink-12, SiteLink-E series
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Output #1 Status
Output #2 Status
Output #3 Status
Output #4 Status
Output #5 Status
Output #6 Status
Output #7 Status
Output #8 Status
Device #1 Status
Device #2 Status
Device #3 Status
Device #4 Status
Device #5 Status
Device #6 Status
Device #7 Status
Device #8 Status
Temp. Sensor #1 Reading
Temp. Sensor #2 Reading
Temp. Sensor #3 Reading
Temp. Sensor #4 Reading
BS01_x
BS02_x
BS03_x
BS04_x
BS05_x
BS06_x
BS07_x
BS08_x
BS09_x
BS10_x
BS11_x
BS12_x
BS13_x
BS14_x
BS15_x
BS16_x
BS17_x
BS18_x
BS19_x
BS20_x
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
Control Points (Set)
Enable Date & Time Sync
Output #1
Output #2
Output #3
Output #4
Output #5
Output #6
Output #7
Output #8
0=Off, 1=On, 2=Forced Off, 3=Forced On,
4=Hardware On
30=Not Used, 31=Operating, 32=Standby,
33=Pending, 34=Forced On, 35=Forced
Off, 36=Hardware On, 37=Alarm,
38=Event
Modbus Format – Signed Integer
Force On, Force Off, Return to Normal
Page 145 of 146
Revision B.31 10/14/2009
Liebert Monitoring Group - Development
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Alarm Points
Loss Of Comm.
Input #1 Alarm
Input #2 Alarm
Input #3 Alarm
Input #4 Alarm
Input #5 Alarm
Input #6 Alarm
Input #7 Alarm
Input #8 Alarm
Sensor #1 High Alarm
Sensor #2 High Alarm
Sensor #2 Low Alarm
Sensor #3 High Alarm
Sensor #3 Low Alarm
Sensor #4 High Alarm
Sensor #4 Low Alarm
Loss of Power
Low Battery Alarm
Battery Unplugged
Check Battery
Emergency Power Op
Configuration Changed
Common Alarm
40289:00
40289:01
40289:02
40289:03
40289:04
40289:05
40289:06
40289:07
40289:08
40289:09
40289:10
40289:11
40289:12
40289:13
40289:14
40289:15
40290:00
40290:01
40290:02
40290:03
40290:04
40290:05
40290:06
BA01_x:00
BA01_x:01
BA01_x:02
BA01_x:03
BA01_x:04
BA01_x:05
BA01_x:06
BA01_x:07
BA01_x:08
BA01_x:09
BA01_x:10 Note: Discrete BACnet objects available
BA01_x:11 using auto-discover
BA01_x:12
BA01_x:13
BA01_x:14
BA01_x:15
BA02_x:00
BA02_x:01
BA02_x:02
BA02_x:03
BA02_x:04
BA02_x:05
BA02_x:06
Trendable points (Set)
Sensor #1
Sensor #2
Sensor #3
Sensor #4
Page 146 of 146