Liebert® Mini-Mate2™–5-Ton

Liebert® Mini-Mate2™–5-Ton (17.5 kW) Capacity
Technical Data Manual–Air, Water, Glycol, Chilled Water; 50&60Hz
TABLE OF CONTENTS
1.0
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1
Designed to Match Computer and Electronic Equipment Needs—From Installation
to Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.0
STANDARD FEATURES—5 TON SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.1
Evaporator Section—Split System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2
Condensing Unit Section—Split System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2.1
Indoor Centrifugal Fan Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2.2
Outdoor Prop Fan Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2.3
Indoor Water/Glycol Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3
Chilled Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.4
System Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.4.1
Other Standard Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.0
OPTIONAL FACTORY-INSTALLED FEATURES - EVAPORATOR/CHILLED WATER UNITS . . . . . .4
3.1
Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2
Humidifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.3
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.4
Switches and Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.5
Free-Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.6
Optional Configurations—Prop Fan Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.7
Optional Configurations—Water/Glycol Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.8
Optional Configurations—Chilled Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.0
SHIP-LOOSE ACCESSORIES—FIELD-INSTALLED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4.1
Remote Monitoring, Autochangeover and Leak Detection Equipment . . . . . . . . . . . . . . . . . . 7
5.0
FLEXIBLE CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
6.0
AIR-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.0
WATER/GLYCOL-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . 17
8.0
CHILLED WATER SYSTEMS—CAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . 22
9.0
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10.0
REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.0
GLYCOL LOOP PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
12.0
MODEL NUMBER NOMENCLATURE—ALL SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
GUIDE SPECIFICATIONS FOR LIEBERT MINI-MATE2- 5-TON SYSTEMS . . . . . . . . . . . . . . . . . . . . . . 37
1.0
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
2.0
Product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.0
Execution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
i
FIGURES
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
Figure 12
Figure 13
Figure 14
Figure 15
Figure 16
Figure 17
Figure 18
Figure 19
Figure 20
Figure 21
Figure 22
Figure 23
Wall-box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Free-cooling arrangement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Flexible configurations—all systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
General arrangement diagram, air-cooled split systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Free-cooling arrangement, air-cooled units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dimensions—Evaporator module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dimensions—Indoor air-cooled condensing module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Dimensions—Air-cooled systems, standard ambient outdoor condensing module . . . . . . . . . . . . 15
Dimensions—Air-cooled systems, high ambient and Quiet-Line condensing module . . . . . . . . . 16
General arrangement diagram water/glycol split systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
General arrangement, free-cooling coil with water/glycol condensing units . . . . . . . . . . . . . . . . . 19
Dimensions—Evaporator module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Dimensions—Water/glycol-cooled indoor condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
General arrangement, chilled water systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
General arrangement, hot water reheat, chilled water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Dimensions—Chilled water module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Refrigerant piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Heat rejection loop, multiple drycoolers and multiple indoor units. . . . . . . . . . . . . . . . . . . . . . . . 33
Split system evaporators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Air-cooled systems—indoor centrifugal condensing units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Air-cooled systems—outdoor prop fan condensing units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Water/glycol-cooled systems—indoor condensing units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Chilled water systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
ii
TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
Table 9
Table 10
Table 11
Table 12
Table 13
Table 14
Table 15
Table 16
Table 17
Table 18
Table 19
Table 20
Table 21
Table 22
Table 23
Table 24
Table 25
Table 26
Air-cooled data, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air-cooled data, 50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evaporator module net weights—air-cooled systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Net weight, indoor condensing module, air-cooled systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Weights for standard ambient outdoor condensing modules, air-cooled systems . . . . . . . . . . . . .
Net weight, high ambient and Quiet-Line condensing modules, air-cooled systems . . . . . . . . . .
Water/glycol data, 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Water/glycol data, 50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module net weights—split system evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Net weight, indoor condensing modules, water/glycol systems . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chilled water data, 60 & 50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Capacity correction factors for MMD91C & MMD92C based on 10°F (5.6°C) water rise. . . . . . .
Net weight—chilled water module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evaporator and chilled water electrical data, standard 1.5hp motor . . . . . . . . . . . . . . . . . . . . . .
Evaporator and chilled water electrical data, optional 2hp motor. . . . . . . . . . . . . . . . . . . . . . . . .
Indoor condensing unit electrical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outdoor prop fan condensing unit electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single-point power kit, air-cooled split system electrical data, standard 1.5hp motor. . . . . . . . .
Single-point power kit, air-cooled split system electrical data, optional 2hp motor . . . . . . . . . . .
Single-point power kit water/glycol-cooled split system electrical data, standard 1.5hp
motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single-point power kit water/glycol-cooled split system electrical data, optional 2hp motor . . . .
Refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recommended refrigerant line sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe length and condenser elevation relative to evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Line charges - refrigerant per 100 ft. (30m) of Type L copper tube . . . . . . . . . . . . . . . . . . . . . . . .
Equivalent lengths for various pipe fittings, ft (m). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii
10
11
13
14
15
16
17
18
20
21
22
23
24
25
26
26
26
27
28
29
30
31
31
31
31
32
iv
Introduction
1.0
INTRODUCTION
1.1
Designed to Match Computer and Electronic Equipment Needs—From Installation
to Operation
Installed above the ceiling, Liebert Mini-Mate2 Precision Cooling systems control the cooling,
humidity and air distribution required by sensitive electronic equipment. A range of sizes and
configurations is available to meet varying sites’ needs.
The Liebert Mini-Mate2 is also easy to use. Advanced microprocessor technology allows easy, precise
control, and menu-driven monitoring keeps you informed of system operation through the LCD
readout. These features, combined with Emerson quality construction and reliable components,
guarantee satisfaction from installation through operation.
Liebert Precision Cooling
Liebert Precision Cooling systems are designed to control the environment required for computers
and other sensitive electronic equipment. The Liebert Mini-Mate2 provides complete control on an
around-the-clock basis and the high sensible heat ratio required by sensitive electronic equipment.
Easy Installation
The Liebert Mini-Mate2 is a split-system evaporator combined with an air-, water- or glycol-cooled
condensing unit or is a self-contained, chilled water unit. Each split system has thermostat-type
wiring to controls and condensing unit. Optional sweat adapters assist with field refrigerant piping.
Easy to Service
Low-maintenance components are easily accessed through removable front panels. Spare parts are
always in Emerson inventory and available on short notice.
Advanced Control Technology
A menu-driven microprocessor control system provides precise temperature and humidity control and
accurate alarm setpoints. Using touch-sensitive buttons, the wall-mounted monitor/control panel
allows you to select and display temperature and other monitored parameters.
High Efficiency
High sensible heat ratio, scroll compressor and precise microprocessor control allow the system to
operate efficiently.
Space Saving Design
All indoor components are installed above the ceiling, so no floor space is required.
Reliable
The Liebert Mini-Mate2 family installed base is a testimony to the system reliability. Components
include a rugged scroll compressor, high-efficiency copper tube, aluminum-fin evaporator coil and a
double inlet, direct drive fan.
Agency Listed
Standard 60Hz units are CSA certified to the harmonized U.S. and Canadian product
safety standard, CSA C22.2 No 236/UL 1995 for “Heating and Cooling Equipment” and
are marked with the CSA c-us logo.
R
C
US
Location
When considering installation locations, consider that these units contain water and that water leaks
can cause damage to sensitive equipment below. Do not mount these units above sensitive equipment.
A field-supplied pan with drain must be supplied beneath cooling units and water/glycol condensers.
Do not mount units in areas where normal unit operating sound might disturb the working
environment.
Liebert® Mini-Mate2™
1
Standard Features—5 Ton Systems
2.0
STANDARD FEATURES—5 TON SYSTEMS
2.1
Evaporator Section—Split System
The evaporator section is designed for ceiling installation. The cabinet and chassis are constructed of
heavy gauge galvanized steel. The unit can be serviced using only one side increasing its versatility in
mounting locations. Mounting brackets are factory-attached to the cabinet. Internal cabinet
insulation meets ASHRAE 62.1 requirements for Mold Growth, Humidity & Erosion, tested per
UL 181 & ASTM 1338 standards. The evaporator section includes the evaporator coil, R-407C unit
charge, filter-drier, factory-mounted disconnect switch, adjustable belt-drive blower assembly and
microprocessor control with wall-mounted control box. The unit is provided with supply and return
air openings for field-supplied ducting. Evaporators can be configured with canister humidifier and/or
reheat. An indoor or outdoor condensing unit must be selected for each evaporator.
2.2
Condensing Unit Section—Split System
2.2.1
Indoor Centrifugal Fan Condensing Units
Indoor Air-Cooled Centrifugal Fan Condensing Units include scroll compressor, factory-mounted
disconnect switch, condenser coil, R-407C unit charge, belt-driven centrifugal blower assembly,
high-pressure switch, Liebert Lee-Temp™ head pressure control system, hot gas bypass and liquidline solenoid valve. Unit must be mounted indoors. Condensing unit is designed to use outdoor air
with temperatures ranging from -30°F to 95°F (-34°C to 35°C).
2.2.2
Outdoor Prop Fan Condensing Units
Outdoor Prop Fan Condensing Units include scroll compressor, condenser coil, R-407C unit charge,
prop fan, liquid-line solenoid valve, high pressure switch, Liebert Lee-Temp head pressure control
and hot gas bypass. Condensing unit is designed for outdoor locations with operating ambients
ranging from -30°F to 95°F (-34°C to 35°C).
2.2.3
Indoor Water/Glycol Condensing Units
Indoor Water/Glycol Condensing Units includes scroll compressor, R-407C unit charge,
factory-mounted disconnect, coaxial condenser, hot gas bypass, high head pressure switch and
two-way water regulating valve designed for 150psi (1034.3kPa). Condensing units can be used on
either a water or glycol cooling loop.
2.3
Chilled Water Units
Chilled Water Units are designed for ceiling installation. The cabinet and chassis are constructed of
heavy gauge galvanized steel. The unit can be serviced using only one side increasing its versatility in
mounting locations. Mounting brackets are factory-attached to the cabinet. Internal cabinet
insulation meets ASHRAE 62.1 requirements for Mold Growth, Humidity & Erosion, tested per
UL 181 & ASTM 1338 standards. Chilled water models are self-contained and include a chilled water
coil, belt-driven centrifugal blower, factory-mounted disconnect switch and two-way, slow-close
motorized valve. Design pressure is 300psi (2068kPa), 60psi (414kPa) close-off differential.
2
Liebert® Mini-Mate2™
Standard Features—5 Ton Systems
2.4
System Controls
System controls include a microprocessor control board mounted in the evaporator/chilled water
unit and a wall-mounted interface with a two-line, 16-character liquid crystal display. A seven-key,
membrane keypad for setpoint/program control, unit On/Off and alarm silence is below the LCD
screen. It provides temperature setpoint and sensitivity adjustment, humidity setpoint and
sensitivity adjustment, digital display of temperature, humidity, setpoints, sensitivities and alarm
conditions.
The wall-box is field-wired to the microprocessor control using standard four-conductor thermostat
wire (field-supplied). The temperature and humidity sensors are in the wall box, which can be
installed up to 300 feet (91.4m) from the evaporator unit. The unit-mounted control board also
includes common alarm terminals and shutdown terminals. The unit automatically restarts after a
power outage.
Figure 1
2.4.1
Wall-box
Other Standard Control Features
• Adjustable auto restart
• Calibrate sensors
• 5 day/2 day setback
• Predictive humidity control
• Password protection
• Common alarm output
• Alarm enable/disable
• Remote shutdown terminals
• Self-diagnostics
Liebert® Mini-Mate2™
3
Optional Factory-Installed Features - Evaporator/Chilled Water Units
3.0
OPTIONAL FACTORY-INSTALLED FEATURES - EVAPORATOR/CHILLED WATER
UNITS
3.1
Reheat
Electric Reheat includes 304/304 stainless steel finned tubular reheat elements, with high limit
safety switch.
SCR Electric Reheat uses an SCR controller and unit control software to provide full cooling with
modulating of the electric reheat elements to control air temperatures. Reheat capacity is up-sized to
offset the cooling capacity. (The SCR Electric Reheat is not available on chilled water, free-cooling or
575V units.)
Hot Water Reheat includes hot water coil, 2-way solenoid valve and Y-strainer.
NOTE
This option is available only on Chilled Water units, but not with other reheat options.
3.2
Humidifier
The Canister Humidifier includes a steam-generating type humidifier with automatic flushing
circuit, inlet strainer, drain, 1" (25.4mm) air gap on fill line and solenoid valves. Humidifier problem
alarm annunciates at the wall-mounted display panel.
Remote Humidifier Contact allows the unit’s humidity controller to control a humidifier outside
the unit. Power to operate the remote humidifier does not come from the Liebert Mini-Mate2.
Available on units with or without internal humidifier.
3.3
Sensors
Smoke Sensor checks return air, shuts down the unit upon sensing smoke and activates visual and
audible alarms at the wall-box display. This smoke sensor is not intended to function as or replace
any smoke sensor system that may be required by local or national codes.
High-Temperature Sensor senses the return air temperature and shuts down unit if the
temperature reaches 125°F (52°C). This device is not meant to replace any fire detection system that
may be required by local or national codes.
3.4
Switches and Motors
Filter Clog senses pressure drop across the filters and activates visual and audible alarms at the
wall-box display. The wall-box display annunciates the alarm audibly and flashes a notification upon
reaching a customer setpoint.
A Factory-Installed Non-Fused Disconnect Switch allows unit to be turned off for maintenance.
A disconnect switch is standard for the evaporators, chilled water units and indoor condensing units,
but these units may be specified without the switch.
2hp Blower Motor is available for high static applications (0.9 to 1.5 in. [23 to 38 mm] w.g.).
4
Liebert® Mini-Mate2™
Optional Factory-Installed Features - Evaporator/Chilled Water Units
3.5
Free-Cooling
Free-cooling option includes separate cooling coil, three-way slow-close valve and separate supply and
return piping. Free-cooling is activated when the water temperature reaches a field-adjustable
temperature, typically 45°F (7°C). The valve is rated for 300psi (2068kPa) working pressure.
Air-cooled condensing units can be matched with evaporators using free-cooling coils with chilled
water sources to serve as backup cooling. When matched with a water/glycol condensing unit, a
three-way water regulating valve is recommended for the condensing unit to simplify piping to the
main supply pipes. The coil is designed for closed-loop applications using properly treated and
circulated fluid. Not available with SCR reheat options.
Figure 2
Free-cooling arrangement
Drycooler
Free-cooling option: A second
cooling coil allows the system to take
advantage of colder outdoor
temperatures and bypass compressor
operation.
When the water temperature goes
below 45°F (7°C), cooling switches
over to free-cooling operation. A
separate chilled water source can
also be used with air-cooled systems.
Liebert Mini-Mate2
Free Cooling
Coil
Water Temperature
Sensor
Water/Glycol
Condenser
Field Piping
NOTE
If free-cooling is applied to an open water tower, an optional cupro-nickel (CuNi) coil is
required to prevent premature corrosion, or a heat exchanger must separate the tower water
from the free-cooling loop. The cupro-nickel coil requires an extended lead time.
3.6
Optional Configurations—Prop Fan Condensing Units
Outdoor Prop Fan Condensing Units are also available in the following optional configurations:
• High ambient, top discharge models for catalog capacities at ambient temperatures up to 105°F
(40°C).
• Quiet-Line models for low noise level conditions (below 58 dBA) and catalog capacities for
ambient temperatures up to 95°F (35°C).
• Condenser coil(s) can be phenolic-coated for extended coil life in coastal areas.
3.7
Optional Configurations—Water/Glycol Condensing Units
Indoor Water/Glycol Condensing Units are also available with the following piping options:
• Two-way water reg. valve with 350 psi (2413kPa) design pressure.
• Three-way water reg. valve with 150psi (1034kPa) design pressure.
• Three-way water reg. valve with 350psi (2413kPa) design pressure.
Liebert® Mini-Mate2™
5
Optional Factory-Installed Features - Evaporator/Chilled Water Units
3.8
Optional Configurations—Chilled Water Units
Chilled Water Units are also available with the following valve options:
• Three-way, slow-close, motorized chilled water valve rated for 300 psi (2068kPa) working
pressure. Valve is non-spring return.
• Two-way modulating chilled water valve, rated for 400psi (2758kPa) operating pressure,
72psi (496kPa) close-off rating. Valve is non-spring return.
• Three-way modulating chilled water valve, rated for 400psi (2758kPa) operating pressure. Valve
is non-spring return.
6
Liebert® Mini-Mate2™
Ship-Loose Accessories—Field-Installed
4.0
SHIP-LOOSE ACCESSORIES—FIELD-INSTALLED
Filter Box includes filter box with 1" (25.4mm) duct flange connection, quantity 2, 20" x 20" x 4"
nominal (508mm x 508mm x 102mm) filters and a 1" (25.4 mm) duct flange for use on the supply air
opening. Filters are MERV 8 efficiency per ASHRAE Standard 52.2-2007.
Condensate Pump is equipped with a discharge check valve. The pump is supplied with a mounting
bracket for field-mounting onto ductwork and can be field-wired to the unit power block. A secondary
float can be field-wired to shut down the unit upon high condensate level.
Condensate Pump Mounting Bracket is available for a mounting condensate pump on the end of
the unit instead of on the duct work for easy alignment and installation of the condensate pump.
Remote Temperature and Humidity Sensors include sensors mounted in an attractive case with
30 ft. (9m) of cable. Installing the remote temperature and humidity sensor module disable the
temperature and humidity sensors mounted in the wall box.
Field-installed kits are available for filter clog, smoke sensor, high temperature sensor, electric
reheat and humidifier. The kits include installation instructions and are designed to be added to the
evaporator unit before it is installed in the ceiling. Electric reheat kits cannot be installed in units
with free-cooling.
Refrigerant-line sweat adapter kit contains two suction and two liquid-line compatible fittings
that allow use of field-supplied, interconnecting refrigerant lines.
Single Point Power Kit contains the necessary electrical components to interconnect the high
voltage sections of a close-coupled evaporator and indoor condensing unit.
4.1
Remote Monitoring, Autochangeover and Leak Detection Equipment
The Liebert RCM4™ is a four-point, normally open, dry contact monitoring panel. One Form-C, dry
contact common alarm relay output (rated at 24VAC, 3A) is provided. Four red LEDs illuminate on
the respective alarm and the alarm buzzer is silenced by a front panel switch. The RCM4 requires a
24VAC or 24VDC power source. Power supply is not included.
The Liebert AC4™ Autochangeover Controller provides autochangeover and autosequence
control for up to four Liebert Mini-Mate2 units within a room. The Liebert AC4 will enable redundant
units in an alarm condition, balance usage and test standby units at programmed intervals. Two
common alarm relay outputs are available. A built-in LCD and RS-232 port for direct PC/terminal
connection provides two options for configuration and monitoring of the product. The Liebert AC4
requires 24VAC input power.
The Liebert AC8™ is ideal for coordinated control of systems with redundant units. The Liebert AC8
enables redundant devices during an alarm condition, balances usage of devices and tests standby
devices at programmable intervals. Supports four zones and can use the 4-20mA temperature sensor
(TW420) for temperature staging in each zone. Two programmable output control relays are available
for auxiliary control such as humidity lockout. Emergency power operation input provided for device
control during an emergency. Two common alarm relay outputs are available. A built-in LCD and
RS-232 port for direct PC/terminal connection provides two options for configuration and monitoring
of the product.
The Liebert ENV-DO™ interface card provides 16 discrete outputs, corresponding to status and
major alarm conditions of Environmental units. The Liebert ENV-DO-ENCL1 packages one
Environmental DO interface card in its own steel enclosure and the ENV-DO-ENCL2 packages two
Environmental DO interface cards in one enclosure for installation external to the Liebert
Mini-Mate2. The self-contained kit includes an external 120VAC-to-24VAC power transformer.
Wiring harnesses are not provided. Power and communication wiring is field-provided.
The Liebert Liqui-tect® 410 Point Leak Detection Sensor detects the presence of conductive
liquid using a pair of corrosion-resistant, gold-plated probes mounted in a painted, height-adjustable
enclosure. Dual Form-C, dry contact common alarm relays (rated at 24VAC, 3A) signal a leak
detected as well as loss of power and cable fault. The Liebert Liqui-tect 410 requires an external
24VAC or 24VDC power source.
Liebert LT460 Zone Leak Detection Kits include one LT460 sensor, a specified length of
LT500-xxY cable (maximum length is 100 ft [30.5m]) and a corresponding number of hold-down clips.
The Liebert LT460 requires an external 24VAC, 0.12A power source, such as EXT-XFMR or XFMR24.
Liebert® Mini-Mate2™
7
Ship-Loose Accessories—Field-Installed
Liebert SiteScan® is a monitoring solution that gives you decision-making power to effectively
manage the equipment critical to your business.
Liebert SiteScan enables communication from Liebert Precision Cooling and Power Protection units,
as well as many other pieces of analog or digital equipment, to a front-end software package that
provides real-time status and alarms so you can react quickly to changing situations.
Liebert SiteScan is designed with flexibility for both small systems and large, complex systems such
as those in computer rooms, telecommunications facilities or industrial process control rooms.
Contact your local Emerson representative for assistance with a Liebert SiteScan system.
The NIC-ENCL1 and NIC-ENCL2 package one or two Liebert IntelliSlot® Web/485 Cards with
Adapters, respectively, in one steel enclosure for installation external to the Liebert Mini-Mate2 . The
Liebert IntelliSlot Web/485 Card with Adapter provides communication with the Liebert
Mini-Mate2™ via SNMP, HTTP, RTU Modbus 485 and BACnet IP. The self-contained kit includes an
external 120VAC-to-24VAC transformer as a power source. Wiring harnesses are not provided. Power
and communication wiring are field-provided.
8
Liebert® Mini-Mate2™
Flexible Configurations
5.0
FLEXIBLE CONFIGURATIONS
Figure 3
Flexible configurations—all systems
Air-Cooled Systems
Evaporator
Evaporator
Prop Fan
Condensing Unit
Centrifugal Fan
Condensing Unit
Water-Cooled System
Glycol-Cooled System
Cooling Tower
Drycooler
Evaporator
Water/Glycol
Condensing Unit
Evaporator
Water/Glycol
Condensing Unit
Chilled Water System
Close-Coupled Components
Filter Box
(Air-Cooled System Shown)
Chilled Water Ducted
Evaporator
Condensing Unit
Condensate
Pump
30" Service Clearance
Liebert® Mini-Mate2™
9
Air-Cooled Systems—Capacities and Dimensions
6.0
Table 1
AIR-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS
Air-cooled data, 60Hz
With Outdoor Condensing Unit
With Centrifugal Condensing Unit
Evaporator Model
MMD60E or MMD60K
Condensing Unit Type
PFH - Outdoor
MCD - Indoor
DX Evaporator- Net Capacity Data - kW (Btuh)
Total
19.2 (65,400)
19.3 (65,700)
80°F DB, 62.8°F WB
(26.7°C DB, 17.1°C WB) 38% RH
Sensible
18.5 (63,000)
18.5 (63,200)
Total
18.4 (62,700)
18.5 (63,000)
75°F DB, 61°F WB
(23.9°C DB, 16.1°C WB) 45% RH
Sensible
16.4 (55,800)
16.4 (56,000)
Total
17.9 (61,200)
18.0 (61,500)
72°F DB, 60°F WB
(22.2°C DB, 15.5°C WB) 50% RH
Sensible
15.0 (51,300)
15.1 (51,500)
Fan Data - Evaporator
CFM (CMH)
2500 (4248)
Fan Motor hp (W)
1.5 (1119)
External Static Pressure, in (mm) water gauge
0.5 (13)
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area, ft2 (m2)
5.6 (0.52)
Coil Rows
4
Max Face Velocity, fpm (m/s)
444 (2.26)
Unit Refrigerant Charge, oz. (kg)
4 (0.11)
Unit Operating Weight
498 (226)
Electric Reheat Capacity (Includes Fan Motor), kW (Btuh)
All Voltages
11.5 (39,100)
SCR Reheat Capacity (Includes Fan Motor), kW (Btuh)
All Voltages, except 575-3-60
16.5 (56,200)
Humidifier Data - Steam Generator Type
Steam capacity, lb/hr (kg/hr)
8 (3.6)
Electrical Input Power, kW
2.8
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip Coupling Size
1/2" - #10 Female
Suction Line Diameter - Aeroquip Coupling Size
1-1/8" - #12 Female
Humidifier Supply
1/4" OD Cu Compression Fitting
Evaporator/Condensate Drain
3/4" NPT-Female
MERV 8 Filter - Nominal Size, qty 2; in. (mm)
4x20x20 (102x508x208)
PFH067A-_L7 *
MCD65AL_H7
Condensing Unit Model Number
Condensing Unit Rating Conditions
95°F (35°C) Inlet Air Temperature
Coil Face Area, ft2 (m2)
10.5 (0.98)
7.3 (0.68)
Rows of Coil
3
4
CFM (CMH)
4200 (7140)
3500 (5947)
Motor, Hp (W)
0.5 (373)
2.0 (1.5)
External Static Pressure, in wg. (mm)
N/A
0.50 (13)
Unit Refrigerant Charge, oz. (kg)
426 (12.1)
432 (12.2)
Unit Operating Weight, lb. (kg)
351 (159)
449 (204)
Free-Cooling Coil Option Net Capacity Data - kW (Btuh) using 45°F EWT
Total
18.9 (64,500)
80°F DB, 62.8°F WB
(26.7°C DB, 17.1°C WB) 38% RH
Sensible
18.0 (61,500)
Total
16.3 (55,600)
75°F DB, 61°F WB
(23.9°C DB, 16.1°C WB) 45% RH
Sensible
15.1 (51,500)
Total
14.8 (50,400)
72°F DB, 60°F WB
(22.2°C DB, 15.5°C WB) 50% RH
Sensible
13.3 (45,400)
Flow Rate, GPM (l/m)
12.0 (45.5)
Pressure Drop, ft. water (kPa)
12.4 (37.1)
Free-Cooling Coil - Copper Tube/Aluminum Fin
Face Area, ft2 (m2)
5.6 (0.52)
Coil Rows
4
Max Face Velocity, fpm (m/s)
444 (2.26)
Internal Fluid Volume, gal (l)
2.3 (8.7)
Water supply and return connections, in (mm) OD
1-1/8 (28.6)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45%RH, is the standard
rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
* Capacities are also valid for Liebert Quiet-Line PFH at 95F (35C) inlet air temperature and for High Ambient PFH models at 105°F (41°C)
inlet air temperature.
10
Liebert® Mini-Mate2™
Air-Cooled Systems—Capacities and Dimensions
Table 2
Air-cooled data, 50Hz
Evaporator Model
Condensing Unit Type
DX Evaporator- Net Capacity Data, kW (Btuh)
Total
80°F DB, 62.8°F WB
(26.7°C DB, 17.1°C WB) 38% RH
Sensible
Total
75°F DB, 61°F WB
(23.9°C DB, 16.1°C WB) 45% RH
Sensible
Total
72°F DB, 60°F WB
(22.2°C DB, 15.5°C WB) 50% RH
Sensible
Fan Data - Evaporator
CFM (CMH)
Fan Motor hp (W)
External Static Pressure, in (mm) water gauge
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area ft2 (m2)
Coil Rows
Max Face Velocity-fpm (m/s)
Unit Refrigerant Charge, oz. (kg)
Unit Operating Weight
With Outdoor Condensing Unit With Centrifugal Condensing Unit
MMD59E or MMD59K
PFH - Outdoor
MCD - Indoor
18.1 (61,600)
17.8 (60,700)
17.2 (58,800)
15.8 (53,900)
16.8 (57,300)
14.5 (49,500)
17.9 (61,000)
17.7 (60,400)
17.1 (58,300)
15.7 (53,700)
16.7 (56,900)
14.4 (49,300)
2500 (4248)
1.5 (1119)
0.5 (13)
5.6 (0.52)
4
444 (2.26)
4 (0.11)
498 (226)
Electric Reheat Capacity (Includes Fan Motor)-kW (Btuh)
Input Voltage-380-3-50
Input Voltage-400-3-50
10.5 (35,800)
9
SCR Reheat Capacity (Includes Fan Motor)-kW (Btuh)
Input Voltage-380-3-50
Input Voltage-400-3-50
Humidifier Data - Steam Generator Type
Steam capacity - lbs/hr (kg/hr)
Electrical Input Power - kW
15.0 (51,200)
16.5 (56,200)
8 (3.6)
2.8
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip Coupling Size
1/2" - #10 Female
Suction Line Diameter - Aeroquip Coupling Size
1-1/8" - #12 Female
Humidifier Supply
1/4" OD Cu Compression Fitting
Evaporator/Condensate Drain
3/4" NPT-Female
MERV 8 Filter - Nominal Size, qty 2; in. (mm)
4x20x20 (102x508x208)
PFH066A-_L7
MCD64AL_H7
Condensing Unit Model Number
Condensing Unit Rating Conditions
95°F (35°C) Inlet Air Temperature
10.5 (0.98)
7.3 (0.68)
Coil Face Area ft2 (m2)
Rows of Coil
3
4
CFM (CMH)
3600 (6116)
3500 (5947)
Motor Hp (W)
0.5 (373)
2.0 (1.5)
External Static Pressure, in wg. (mm)
N/A
0.50 (13)
Unit Refrigerant Charge, oz. (kg)
426 (12.1)
432 (12.2)
Unit Operating Weight, lb. (kg)
351 (159)
449 (204)
Free-Cooling Coil Option Net Capacity Data - kW (Btuh) using 45°F EWT
Total
18.9 (64,500)
80°F DB, 62.8°F WB
(26.7°C DB, 17.1°C WB) 38% RH
Sensible
18.0 (61,500)
Total
16.3 (55,600)
75°F DB, 61°F WB
(23.9°C DB, 16.1°C WB) 45% RH
Sensible
15.1 (51,500)
Total
14.8 (50,400)
72°F DB, 60°F WB
(22.2°C DB, 15.5°C WB) 50% RH
Sensible
13.3 (45,400)
Flow Rate - GPM (l/m)
12.0 (45.5)
Pressure Drop - ft. water (kPa)
12.4 (37.1)
Free-Cooling Coil - Copper Tube/Aluminum Fin
5.6 (0.52)
Face Area ft2 (m2)
Coil Rows
4
Max Face Velocity-fpm (m/s)
444 (2.26)
Internal Fluid Volume - gal (l)
2.3 (8.7)
Water supply and return connections, in (mm) OD
1-1/8 (28.6)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45%RH, is the standard rating condition for
ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
* Capacities are also valid for Quiet-Line PFH at 95F (35C) inlet air temperature and for High Ambient PFH models at 105F (41C) inlet air temperature.
Liebert® Mini-Mate2™
11
Air-Cooled Systems—Capacities and Dimensions
Figure 4
General arrangement diagram, air-cooled split systems
Condenser
Coil
Scroll
Compressor
High-Pressure
Switch
Hot Gas
Bypass
Solenoid
Valve
Liquid Injection
Valve Bulb
Suction Line Male Quick
Connect Coupling
Suction Line Female Quick
*
Connect Coupling
Sensing Bulb
External Equalizer
3-Way Head
Pressure
Relief
Valve
Hot Gas Bypass
Control Valve
3/8" SAE 45° Male Flare
(MCD) or Atmospheric (PFH)
Pressure Relief Valve
Check
Valve
Sight Glass
Liquid Injection
Valve
Service Access
Ports
Filter
Drier
Expansion
Valve
Liebert
Lee-Temp
Receiver
Liquid Line
Solenoid Valve
*
Liquid Line Male Quick
Connect Coupling
Liquid Line Female Quick
Connect Coupling
Pressure Balancing
Valve
FIELD PIPING
FACTORY PIPING
Evaporator
Coil
Figure 5
* Use Liebert sweat adapter kit with field
hard piping. Close-coupling option available with MCD.
** Components are not supplied by Liebert but are
recommended for proper circuit operation and maintenance.
DPN000215
Rev. 3
Free-cooling arrangement, air-cooled units
Bleed Valve
Fluid
Supply
To Unit
Shutoff*
Valves
Hose*
Bibs
Free-Cooling
Fluid
Control
Return
Valve
From Unit
Free-Cooling
Coil
Temperature
Stat
* Components are not supplied by Emerson
but are recommended for proper circuit
operation and maintenance.
FIELD PIPING
FACTORY PIPING
DPN000219
Rev. 3
12
Liebert® Mini-Mate2™
Air-Cooled Systems—Capacities and Dimensions
Figure 6
Dimensions—Evaporator module
Optional Discharge Air
Duct Flange Supplied
when Optional Filter Box
is Ordered
46-1/2"
(1181.1mm)
Cabinet
Dimension
Air
Outlet
14 1/2"
(368.3mm)
13-3/8"
(339.7mm)
Air
Inlet
13-3/8"
(339.7mm)
7-5/8"
(193.5mm)
3-1/8"
(79.4mm)
14-1/2"
(368.3mm)
24"
(610mm)
Cabinet
Dimension 22-7/16 "
Removable
Access
Panels
7/8" (22mm) Holes
for Module Rigging
(typ. 2 each end)
(570mm)
13/16" (20.6mm)
1-1/8 "
(28.6mm)
36 7/8"
(936.6mm)
MODULE DIMENSIONAL DATA
Hanging
Bracket
49" (1244.6mm)
Cabinet
Dimension
Customer-Supplied
Threaded Rods for
Module Support from
Ceiling (typ. 4)
1-1/16"
(27mm)
43-1/2"
(1104.9mm)
Threaded Rod
Centers
50-5/8"
(1285.9mm)
Threaded Rod
Centers
39-3/8"
(1000.1mm)
1" (25.4mm)
1"
(25.4mm)
19-3/4"
(501.7mm)
17-5/8"
(447.7mm)
Duct Flange
Table 3
OPTIONAL FILTER BOX
24"
(609.6mm)
37-3/8"
(949.3mm)
3/4"
(19mm)
8"
(203.2mm)
Evaporator module net weights—air-cooled systems
Model #
Weight, lb (kg)
60Hz
50Hz
MM*60E
MM*59E
498 (226)
MM*60K
MM*59K
530 (240)
Liebert® Mini-Mate2™
Shaded Area Indicates a
Recommended Clearance
of 30" (762mm) for Access
and Filter Removal
13
DPN000218
Rev. 3
Air-Cooled Systems—Capacities and Dimensions
Figure 7
Dimensions—Indoor air-cooled condensing module
54"
(1371.6mm)
Cabinet
Dimension
Field-supplied threaded
rods for module support
from ceiling (typ. 4)
1-5/8"
(41.1mm)
32"
(812.8mm)
Cabinet
Dimension
15-3/4"
(400mm)
8-15/16"
(227mm)
48"
(1219.2mm)
3-3/8"
(85.7mm)
14-1/2"
(368.3mm)
24"
(610mm)
Cabinet
Dimension
21-1/4"
(539.8mm)
1-3/4"
(44.5mm)
33-5/8"
(854.1mm)
NOTE: Unit is spaced evenly Threaded Rod
in reference to threaded
Centers
rod centers.
1/2" (12.7mm) dia. holes for
threaded rods (typ. 2 each end)
50"
(1270mm)
Threaded Rod
Centers
Shaded area indicates a
recommended clearance of
30" (762mm) for component
access and removal
Hanger Bracket
AIR-COOLED DIMENSIONAL DATA
7/8" (22.2mm) & 1-1/8" (28.6mm)
dia. knockouts electrical entrance
for high-voltage connection
(Single Point Power Kit).
7/8" (22.2mm) & 1-1/8" (28.6mm)
dia. knockouts electrical entrance
for high-voltage connection
Single Point Power Kit
connection to Evaporator
Air Inlet
Air Outlet
Liquid Line male quick
connect location
Suction Line male quick
connect location
7/8" (22.2mm) dia. knockout
electrical entrance for alternate
control panel low voltage routing
Table 4
7/8" (22.2mm) dia. electrical
entrance for low-voltage connection.
DPN000225
Rev. 2
Net weight, indoor condensing module, air-cooled systems
Model #
60Hz
50Hz
MC*65A
MC*64A
Weight, lb (kg)
449 (204)
14
Liebert® Mini-Mate2™
Air-Cooled Systems—Capacities and Dimensions
Figure 8
Dimensions—Air-cooled systems, standard ambient outdoor condensing module
Fan Rotation
Counteclockwise
(left side)
Removable (Right) Panel
for Access to Refrigeration Component
Right Air
Discharge
53"
(1343mm)
Left Air
Intake
36-1/4"
(918mm)
C18"
(457mm)
Shaded area indicates
a minimum clearance of
18" (457mm) for proper
air flow
Table 5
Removable front panel
for access to high-voltage
and low-voltage connections
and to refrigeration components
Shaded area indicates
a minimum clearance o
18" (457mm) for proper
air flow
Shaded area indicates
a minimum clearance of
24" (610mm) for component
access and removal
Weights for standard ambient outdoor condensing modules, air-cooled systems
Model #
60Hz
50Hz
PFH067A-L
PFH066A-L
Liebert® Mini-Mate2™
Weight, lb (kg)
351 (159)
15
DPN000130
Rev. 1
Air-Cooled Systems—Capacities and Dimensions
Figure 9
Dimensions—Air-cooled systems, high ambient and Quiet-Line condensing module
Guard Height
5-1/2" (140mm)
Top Air
Discharge
Right Air
Intake
36-1/4" (918)
Left Air
Intake
Shaded area indicates
a minimum clearance of
18" (457mm) for proper
air flow
2"
(51mm)
53"
(1346mm)
Shaded area indicates
a minimum clearance of
18" (457mm) for proper
air flow
Table 6
38-1/2"
(978)
Removable front panel
for access to high-voltage
and low-voltage connections
and to refrigeration components
Shaded area indicates
a minimum clearance of
24" (610mm) for component
access and removal
DPN000131
Rev. 0
Net weight, high ambient and Quiet-Line condensing modules, air-cooled systems
Model #
60Hz
50Hz
PFH067A- H
PFHZ67A- L
PFH066A- H
PFHZ66A-L
Module
Net Weight
lb. (kg)
488 (222)
16
Liebert® Mini-Mate2™
Water/Glycol-Cooled Systems—Capacities and Dimensions
7.0
Table 7
WATER/GLYCOL-COOLED SYSTEMS—CAPACITIES AND DIMENSIONS
Water/glycol data, 60Hz
MMD60E or MMD60K
Water-Cooled
Glycol-Cooled
Evaporator Model
Condensing Unit Fluid
Net Capacity Data DX Evaporator, kW (Btuh)
80°F DB, 62.8°F WB
(26.7°C DB, 17.1°C WB) 38% RH
75°F DB, 61°F WB
(23.9°C DB, 16.1°C WB) 45% RH
72°F DB, 60°F WB
(22.2°C DB, 15.5°C WB) 50% RH
Total
Sensible
Total
Sensible
Total
Sensible
21.5 (73,500)
19.6 (67,000)
20.8 (70,800)
17.5 (59,600)
20.3 (69,200)
16.1 (55,000)
18.2 (62,200)
17.9 (61,200)
17.4 (59,500)
15.9 (54,300)
17.0 (58,000)
14.6 (49,800)
Fan Data - Evaporator
CFM (CMH)
2500 (4248)
Fan Motor, hp (W)
1.5 (1119)
External Static Pressure, in (mm) water gauge
0.5 (13)
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area, ft2 (m2)
5.6 (0.52)
Coil Rows
4
Max Face Velocity-fpm (m/s)
444 (2.26)
Unit Refrigerant Charge, oz. (kg)
4 (0.11)
Unit Operating Weight
498 (226)
Electric Reheat Capacity (Includes Fan Motor), kW (Btuh)
All Voltages
11.5 (39,100)
SCR Reheat Capacity (Includes Fan Motor), kW (Btuh)
All Voltages, except 575-3-60
16.5 (56,200)
Humidifier Data - Steam Generator Type
Steam capacity, lbs/hr (kg/hr)
8 (3.6)
Electrical Input Power, kW
2.8
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip Coupling Size
1/2" - #10 Female
Suction Line Diameter - Aeroquip Coupling Size
1-1/8" - #12 Female
Humidifier Supply
1/4" OD Cu Compression Fitting
Evaporator/Condensate Drain
3/4" NPT-Female
MERV 8 Filter - Nominal Size, qty 2; in. (mm)
4 x 20 x 20 (102 x 508 x 208)
MCD69W
Condensing Unit Model Number
Condenser Fluid Requirements
85°F (29.4°C) EWT
110°F (43.3°C) EGT - 40% PG
THR - kW (Btuh) @ 75F/45%RH
27.6 (94,200)
25.9 (88,400)
Flow Rate, GPM (l/m)
16.4 (62.2)
20.1 (76.2)
Pressure Drop, ft. of H20 (kPa)
21.7 (64.9)
38.9 (116.3)
Water-Cooled Condensing Temperature
105°F (40.6°C)
N/A
Unit Volume, gal (l)
2.0 (7.5)
Unit Refrigerant Charge, oz. (kg)
94 (2.7)
Unit Operating Weight, lb. (kg)
282 (128)
Free-Cooling Coil Option Net Capacity Data, kW (Btuh) using 45°F EWT
Entering Fluid Requirements
45°F (29.4°C) EWT
45°F (29.4°C) EGT - 40% PG
Total
18.9
(64,500)
14.1 (48,500)
80°F DB, 62.8°F WB
(26.7°C DB, 17.1°C WB) 38% RH
Sensible
18.0 (61,500)
14.1 (48,500)
Total
16.3 (55,600)
11.7 (40,000)
75°F DB, 61°F WB
(23.9°C DB, 16.1°C WB) 45% RH
Sensible
15.1 (51,500)
11.7 (40,000)
Total
14.8 (50,400)
10.7 (36,400)
72°F DB, 60°F WB
(22.2°C DB, 15.5°C WB) 50% RH
Sensible
13.3 (45,400)
10.7 (36,400)
Flow Rate, GPM (l/m)
12.0 (45.5)
20.1 (76.2)
Pressure Drop, ft. water (kPa)
12.4 (37.1)
50.4 (150.7)
Free-Cooling Coil - Copper Tube/Aluminum Fin
Face Area, ft2 (m2)
5.6 (0.52)
Coil Rows
4
Max Face Velocity, fpm (m/s)
444 (2.26)
Internal Fluid Volume, gal (l)
2.3 (8.7)
Water supply and return connections, in (mm) OD
1-1/8 (28.6)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45%RH, is the standard
rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
Liebert® Mini-Mate2™
17
Water/Glycol-Cooled Systems—Capacities and Dimensions
Table 8
Water/glycol data, 50Hz
Evaporator Model
Condensing Unit Fluid
Net Capacity Data DX Evaporator- kW (Btuh)
80°F DB, 62.8°F WB
(26.7°C DB, 17.1°C WB) 38% RH
75°F DB, 61°F WB
(23.9°C DB, 16.1°C WB) 45% RH
72°F DB, 60°F WB
(22.2°C DB, 15.5°C WB) 50% RH
Water-Cooled
Total
Sensible
Total
Sensible
Total
Sensible
20.7 (70,700)
19.3 (65,700)
19.9 (68,000)
17.1 (58,300)
19.5 (66,500)
15.7 (53,700)
MMD59E or MMD59K
Glycol-Cooled
16.9 (57,800)
16.9 (57,800)
16.1 (54,900)
15.2 (52,000)
15.7 (53,500)
14.0 (47,700)
Fan Data - Evaporator
CFM (CMH)
2500 (4248)
Fan Motor hp (W)
1.5 (1119)
External Static Pressure, in (mm) water gauge
0.5 (13)
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area ft2 (m2)
5.6 (0.52)
Coil Rows
4
Max Face Velocity-fpm (m/s)
444 (2.26)
Unit Refrigerant Charge, oz. (kg)
4 (0.11)
Unit Operating Weight
498 (226)
Electric Reheat Capacity (Includes Fan Motor)-kW (Btuh)
Input Voltage-380-3-50
10.5 (35,800)
Input Voltage-400-3-50
11.5 (39,100)
SCR Reheat Capacity (Includes Fan Motor)-kW (Btuh)
Input Voltage-380-3-50
15.0 (51,200)
Input Voltage-400-3-50
16.5 (56,200)
Humidifier Data - Steam Generator Type
Steam capacity - lb/hr (kg/hr)
8 (3.6)
Electrical Input Power - kW
2.8
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip Coupling Size
1/2" - #10 Female
Suction Line Diameter - Aeroquip Coupling Size
1-1/8" - #12 Female
Humidifier Supply
1/4" OD Copper Compression Fitting
Evaporator/Condensate Drain
3/4" NPT-Female
MERV 8 Filter - Nominal Size, qty 2; in. (mm)
4x20x20 (102x508x208)
Condensing Unit Model Number
MCD68W
Condenser Fluid Requirements
85°F (29.4°C) EWT
110°F (43.3°C) EGT - 40% PG
THR - kW (Btuh) @ 75F/45%RH
25.3 (86,400)
24.7 (84,300)
Flow Rate - GPM (l/m)
15.6 (59.1)
19.0 (72.0)
Pressure Drop - ft. of H20 (kPa)
19.5 (58.3)
34.7 (103.8)
Water-Cooled Condensing Temperature
105°F (40.6°C)
N/A
Unit Volume - Gal (l)
2.0 (7.5)
Unit Refrigerant Charge, oz. (kg)
94 (2.7)
Unit Operating Weight, lb. (kg)
282 (128)
Free-Cooling Coil Option Net Capacity Data - kW (Btuh) using 45°F EWT
Entering Fluid Requirements
45°F (29.4°C) EWT
45°F EGT - 40% PG
Total
18.9 (64,500)
14.0 (47,700)
80°F DB, 62.8°F WB
(26.7°C DB, 17.1°C WB) 38% RH
Sensible
18.0 (61,500)
14.0 (47,700)
Total
16.3 (55,600)
11.8 (40,400)
75°F DB, 61°F WB
(23.9°C DB, 16.1°C WB) 45% RH
Sensible
15.1 (51,500)
11.8 (40,400)
Total
14.8 (50,400)
10.5 (35,900)
72°F DB, 60°F WB
(22.2°C DB, 15.5°C WB) 50% RH
Sensible
13.3 (45,400)
10.5 (35,900)
Flow Rate - GPM (l/m)
12.0 (45.5)
19.0 (72.0)
Pressure Drop - ft. water (kPa)
12.4 (37.1)
45.5 (136.0)
Free-Cooling Coil - Copper Tube/Aluminum Fin
Face Area ft2 (m2)
5.6 (0.52)
Coil Rows
4
Max Face Velocity-fpm (m/s)
444 (2.26)
Internal Fluid Volume - gal (l)
2.3 (8.7)
Water supply and return connections, in (mm) OD
1-1/8 (28.6)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45%RH, is the standard
rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
18
Liebert® Mini-Mate2™
Water/Glycol-Cooled Systems—Capacities and Dimensions
Figure 10 General arrangement diagram water/glycol split systems
Scroll
Compressor
High-Pressure
Switch
Liquid Injection
Valve Bulb
Suction Line Male Quick
Connect Coupling
External
Equalizer
Tube-in-Tube
Condenser
Hot Gas
Bypass
Solenoid
Valve
Tube-in-Tube
Condenser
ass
Byp
Gas alve
t
o
H
tr o l V
Con
Suction Line Female Quick
*
Connect Coupling
Sensing Bulb
Water/Glycol
Return Line
Water/Glycol
Fluid Return
Supply Line
Liquid Injection
Valve
From Unit
Shutoff **
Valves
Liquid Line
Male Quick
Filter
*
Connect
Drier
Hose
Liquid Line Coupling
Bibs **
Female Quick
Connect
Expansion Coupling
Valve
Service Access
Ports
Fluid Supply
To Unit
2 - Way Water
Regulating Valve
Fluid
Return
From Unit
FIELD PIPING
FACTORY PIPING
Evaporator
Coil
Figure 11
3 - Way Water
Regulating Valve
(Optional)
Fluid Supply
To Unit
* Use Liebert sweat adapter kit with field
hard piping. Close-coupling option available with MCD.
** Components are not supplied by Liebert but are
recommended for proper circuit operation and maintenance.
DPN000214
Rev. 1
General arrangement, free-cooling coil with water/glycol condensing units
Bleed Valve
Fluid
Return
From Unit
Fluid
Supply
To Unit
Shutoff*
Valves
Free-Cooling
Control
Valve
Temperature
Stat
Hose*
Bibs
NOTE: RECOMMENDED PIPING FOR UNITS
WITH FREE-COOLING COIL OPTION
AND WATER/GLYCOL CONDENSER.
Liebert® Mini-Mate2™
Free-Cooling
Coil
Shutoff*
Valves
Hose*
Bibs
Tube in
Tube
Condenser
Fluid
Return
From
Unit
Fluid
Supply
To Unit
3-Way Water
Regulating
Valve
(Optional)
FIELD PIPING
FACTORY PIPING
* Components are not supplied by Emerson
but are recommended for proper circuit
operation and maintenance.
19
DPN000219
Rev. 3
Water/Glycol-Cooled Systems—Capacities and Dimensions
Figure 12 Dimensions—Evaporator module
Optional Discharge Air
Duct Flange Supplied
when Optional Filter Box
is Ordered
46-1/2"
(1181.1mm)
Cabinet
Dimension
Air
Outlet
14 1/2"
(368.3mm)
13-3/8"
(339.7mm)
Air
Inlet
13-3/8"
(339.7mm)
7-5/8"
(193.5mm)
3-1/8"
(79.4mm)
14-1/2"
(368.3mm)
24"
(610mm)
Cabinet
Dimension 22-7/16 "
Removable
Access
Panels
7/8" (22mm) Holes
for Module Rigging
(typ. 2 each end)
(570mm)
13/16" (20.6mm)
1-1/8 "
(28.6mm)
36 7/8"
(936.6mm)
MODULE DIMENSIONAL DATA
Hanging
Bracket
49" (1244.6mm)
Cabinet
Dimension
Customer-Supplied
Threaded Rods for
Module Support from
Ceiling (typ. 4)
1-1/16"
(27mm)
43-1/2"
(1104.9mm)
Threaded Rod
Centers
50-5/8"
(1285.9mm)
Threaded Rod
Centers
39-3/8"
(1000.1mm)
1" (25.4mm)
1"
(25.4mm)
19-3/4"
(501.7mm)
17-5/8"
(447.7mm)
Duct Flange
Table 9
Shaded Area Indicates a
Recommended Clearance
of 30" (762mm) for Access
and Filter Removal
OPTIONAL FILTER BOX
24"
(609.6mm)
37-3/8"
(949.3mm)
3/4"
(19mm)
8"
(203.2mm)
DPN000218
Rev. 3
Module net weights—split system evaporator
Model #
Weight, lb (kg)
60Hz
50Hz
MM*60E
MM*59E
498 (226)
MM*60K
MM*59K
530 (240)
20
Liebert® Mini-Mate2™
Water/Glycol-Cooled Systems—Capacities and Dimensions
Figure 13 Dimensions—Water/glycol-cooled indoor condensing unit
NOTE: Unit is evenly spaced
in reference to threaded
rod centers.
32"
(812.8mm)
Cabinet
Dimension
32"
(812.8mm)
Cabinet
Dimension
Field-supplied threaded
rods for module support
from ceiling typ. 4).
Removable
Access
Panel
1/2" (12.7mm) dia.
holes for module
rigging (typ. 2
each end)
24"
(610mm)
Cabinet
Dimension
Hanger
Bracket
Shaded area indicates a
recommended clearance of
30" (762mm) for component
access and removal
33 5/8"
(854.1mm)
Threaded Rod
Centers
28"
(711mm)
Threaded Rod
Centers
WATER/GLYCOL DIMENSIONAL DATA
7/8" (22.2mm) & 1 1/8" (28.6mm)
dia. knockouts electrical entrance for
line voltage connection (Single Point
Power Kit)
7/8" (22.2mm) & 1-1/8" (28.6mm)
dia. knockouts electrical entrance for
line voltage connection
8-7/16"
(214.4mm)
3-3/4"
(95.2mm)
Suction Line male
quick connect
location
Liquid Line
male quick
connect location
1-1/8" (28.6mm) OD CU Water/Glycol
Inlet Connection. Extends
3-1/2" (88.9mm) beyond panel exterior
7/8" (22.2mm) dia. electrical entrance
for low-voltage connection
Table 10
60Hz
50Hz
MC*69W
MC*68W
Liebert® Mini-Mate2™
1-1/8" (28.6mm) OD Cu Water/Glycol
Outlet Connection Extends
3-1/2" (88.9mm) beyond panel exterior
7/8" (22.2mm) dia. knockout
DPN000227
electrical entrance for alternate
Rev. 3
control panel low-voltage routing.
Net weight, indoor condensing modules, water/glycol systems
Model #
7"
(177.8mm)
Weight, lb (kg)
282 (128)
21
Chilled Water Systems—Capacities and Dimensions
8.0
CHILLED WATER SYSTEMS—CAPACITIES AND DIMENSIONS
Table 11
Chilled water data, 60 & 50Hz
MMD92C/MMD91C
CW Model
Net Capacity Data - kW (Btuh) based on 45°F (7.2°C) EWT & 10°F (5.6°C) temperature rise
Total
20.1 (68,700)
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38% RH
Sensible
18.7 (63,900)
Flow Rate - GPM (l/m)
14.6 (55.3)
Pressure Drop - ft. water (kPa)
18.7 (55.9)
Total
16.3(55,600)
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45% RH
Sensible
15.1 (51,500)
Flow Rate, GPM (l/m)
12.0 (45.5)
Pressure Drop, ft. water (kPa)
12.9 (38.6)
Total
13.8 (47,200)
72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50% RH
Sensible
12.8 (43,700)
Flow Rate, GPM (l/m)
10.3 (39.0)
Pressure Drop, ft. water (kPa)
9.7 (29.0)
Fan Data - Evaporator
CFM (CMH)
2500 (4248)
Fan Motor, hp (W)
1.5 (1119)
External Static Pressure, in (mm) water gauge
0.5 (13)
CW Coil - Copper Tube/Aluminum Fin
Face Area, ft2 (m2)
5.6 (0.52)
Coil Rows
4
Max Face Velocity, fpm (m/s)
444 (2.26)
Electric Reheat Capacity (Includes Fan Motor), kW (Btuh)
Input Voltage-208/230/460/575-3-60
11.5 (39,100)
Input Voltage-380-3-50
10.5 (35,800)
Input Voltage-400-3-50
11.5 (39,100)
Hot Water Reheat Coil - Copper Tube/Aluminum Fin
Capacity (with fan motor heat) using 180°F (82°C) EWT, kW (Btuh)
19.6 (66,800)
Flow Rate, GPM (l/m)
1.5 (5.7)
Pressure Drop, ft. water (kPa)
1.5 (4.5)
Face Area, ft2 (m2)
5.6 (0.52)
Coil Rows
1
HWRH supply and return connections, in (mm) OD
5/8 (15.8)
Humidifier Data - Steam Generator Type
Steam capacity, lb/hr (kg/hr)
8 (3.6)
Electrical Input Power, kW
2.8
Connections, Volume, Filters, Weight
CW supply and return connections, in (mm) OD
1-1/8 (28.6)
Humidifier Supply
1/4" OD Copper Compression Fitting
Evaporator/Condensate Drain
3/4" NPT-Female
Unit Internal Fluid Volume, gal (l)
2.3 (8.7)
MERV 8 Filter - Nominal Size, qty 2; in. (mm)
4x20x20 (102x508x208)
Unit Operating Weight
498 (226)
On/Off Slow Close
Modulating
Unit Valve Types
Valve Size
Valve Cv
Maximum Static Operating Pressure, psi (kPa)
Close-Off Pressure, psi (kPa)
1"
7
300 (2068)
60 (414)
1"
11.6
400 (2758)
72 (496)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9°C), 45%RH, is the
standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
22
Liebert® Mini-Mate2™
Chilled Water Systems—Capacities and Dimensions
Table 12
Capacity correction factors for MMD91C & MMD92C based on 10°F (5.6°C) water rise
72°F (22.2°C) 50% RH
75°F (23.9°C) 45%RH
EWT
TCC
SCC
TCC
SCC
42°F (5.6°C)
1.28
1.14
1.23
1.12
43°F (6.1°C)
1.18
1.09
1.14
1.07
44°F (6.7°C)
1.09
1.05
1.07
1.03
45°F (7.2°C)
1.00
1.00
1.00
1.00
46°F (7.8°C)
0.92
0.95
0.93
0.96
47°F (8.3°C)
0.85
0.90
0.87
0.92
48°F (8.9°C)
0.79
0.85
0.81
0.88
49°F (9.4°C)
0.73
0.79
0.77
0.82
EWT = Entering Water Temperature
TCC = Total Cooling Capacity
SCC = Sensible Cooling Capacity
Figure 14 General arrangement, chilled water systems
Bleed Valve
Chilled
Water Coil
Chilled Water
Control Valve
Chilled
Water
Return
Chilled Water
Supply
3 - Way Chilled Water
Control Valve (Optional)
Shutoff **
Valves
* Use Liebert sweat adapter kit with field
hard piping. Close-coupling option
available with MCD.
** Components are not supplied by Liebert
but are recommended for proper circuit
operation and maintenance.
Chilled Water
Return
Chilled Water
Supply
Hose Bibs**
DPN000215
Rev. 3
Figure 15 General arrangement, hot water reheat, chilled water units
Bleed Valve
Water
Return
From Unit
Water
Supply
To Unit
Shutoff*
Valves
Hot Water
Reheat
Control
Valve
Hot Water
Reheat
Coil
Y-Strainer
Note: Hot water reheat available only
on chilled water units.
* Components are not supplied by Emerson
but are recommended for proper circuit
operation and maintenance.
FIELD PIPING
Hose*
Bibs
FACTORY PIPING
DPN000219
Rev. 3
Liebert® Mini-Mate2™
23
Chilled Water Systems—Capacities and Dimensions
Figure 16 Dimensions—Chilled water module
Optional Discharge Air
Duct Flange Supplied
when Optional Filter Box
is Ordered
46-1/2"
(1181.1mm)
Cabinet
Dimension
Air
Outlet
14 1/2"
(368.3mm)
13-3/8"
(339.7mm)
Air
Inlet
13-3/8"
(339.7mm)
7-5/8"
(193.5mm)
3-1/8"
(79.4mm)
14-1/2"
Removable
(368.3mm)
Access
Panels
24"
(610mm)
Cabinet
Dimension 22-7/16 "
7/8" (22mm) Holes
for Module Rigging
(typ. 2 each end)
(570mm)
13/16" (20.6mm)
1-1/8 "
(28.6mm)
36 7/8"
(936.6mm)
MODULE DIMENSIONAL DATA
Hanging
Bracket
49" (1244.6mm)
Cabinet
Dimension
Customer-Supplied
Threaded Rods for
Module Support from
Ceiling (typ. 4)
1-1/16"
(27mm)
1" (25.4mm)
43-1/2"
(1104.9mm)
Threaded Rod
Centers
50-5/8"
(1285.9mm)
Threaded Rod
Centers
39-3/8"
(1000.1mm)
1"
(25.4mm)
19-3/4"
(501.7mm)
17-5/8"
(447.7mm)
Duct Flange
Table 13
Shaded Area Indicates a
Recommended Clearance
of 30" (762mm) for Access
and Filter Removal
OPTIONAL FILTER BOX
24"
(609.6mm)
37-3/8"
(949.3mm)
3/4"
(19mm)
8"
(203.2mm)
DPN000218
Rev. 3
Net weight—chilled water module
Model #
60Hz
50Hz
MM*92C
MM*91C
Weight, lb (kg)
498 (226)
24
Liebert® Mini-Mate2™
Electrical Data
9.0
ELECTRICAL DATA
Table 14
Evaporator and chilled water electrical data, standard 1.5hp motor
Base Evaporator
Model Number
208-3-60
230-3-60
460-3-60
575-3-60
380/415-3-50
MMD60E/K
MMD92C
MMD60E/K
MMD92C
MMD60E/K
MMD92C
MMD60E/K
MMD92C
MMD59E/K
MMD91C
Cooling Only
FLA
5.6
5.6
2.8
2
3.2
WSA
7.0
7.0
3.5
2.5
N/A
OPD
15
15
15
15
N/A
with Electric Reheat
FLA
33.4
30.7
15.4
12.0
17.6
WSA
41.8
38.4
19.3
15.0
N/A
OPD
45
40
20
15
N/A
with Humidifier
FLA
15.4
14.5
7.2
5.5
8.3
WSA
19.3
18.1
9.0
6.9
N/A
OPD
20
20
15
15
N/A
with Electric Reheat and Humidifier
FLA
43.2
39.6
19.8
15.5
22.7
WSA
54.0
49.5
24.8
19.4
N/A
OPD
60
50
25
20
N/A
MMD60E
only
MMD60E
only
MMD60E
only
MMD60E
only
MMD59E
only
FLA
47.2
43.3
21.6
N/A
24.9
WSA
59.0
54.1
27.0
N/A
N/A
OPD
60
60
30
N/A
N/A
Base Evaporator
Model Number
with SCR Reheat
with SCR Reheat and Humidifier
FLA
57.0
52.2
26.0
N/A
30.0
WSA
71.3
65.3
32.5
N/A
N/A
OPD
80
70
35
N/A
N/A
1. For Chilled Water units with Hot Water Reheat, use appropriate "Cooling Only" or "with Humidifier" values.
2. SCR reheat not available with Chilled Water Units or units with free-cooling option
Liebert® Mini-Mate2™
25
Electrical Data
Table 15
Evaporator and chilled water electrical data, optional 2hp motor
Base Evaporator
Model Number
Cooling Only
208-3-60
230-3-60
460-3-60
575-3-60
380/415-3-50
MMD60E/K
MMD92C
MMD60E/K
MMD92C
MMD60E/K
MMD92C
MMD60E/K
MMD92C
MMD59E/K
MMD91C
5.8
7.3
15
5.8
7.3
15
2.9
3.6
15
2.3
2.9
15
3.7
N/A
N/A
33.6
42.0
45
30.9
38.6
40
15.5
19.4
20
12.3
15.4
20
18.1
N/A
N/A
7.3
9.1
15
5.8
7.3
15
8.8
N/A
N/A
19.9
24.9
25
MMD60E
only
15.8
19.8
20
MMD60E
only
23.2
N/A
N/A
MMD59E
only
43.5
54.4
60
21.7
27.1
30
N/A
N/A
N/A
25.4
N/A
N/A
52.4
65.5
70
26.1
32.6
35
N/A
N/A
N/A
30.5
N/A
N/A
FLA
WSA
OPD
with Electric Reheat
FLA
WSA
OPD
with Humidifier
FLA
15.6
14.7
WSA
19.5
18.4
OPD
20
20
with Electric Reheat and Humidifier
FLA
43.4
39.8
WSA
54.3
49.8
OPD
60
50
MMD60E
MMD60E
Base Evaporator
only
only
Model Number
with SCR Reheat
FLA
47.4
WSA
59.3
OPD
60
with SCR Reheat and Humidifier
FLA
57.2
WSA
71.5
OPD
80
1. For Chilled Water Units with Hot Water Reheat, use appropriate “Cooling Only” or “with Humidifier” values.
2. SCR reheat not available with Chilled Water Units or units with free-cooling option.
Table 16
Indoor condensing unit electrical
data
Table 17
208/230-3-60 460-3-60 575-3-60 380/415-3-50
MCD65A
Outdoor prop fan condensing unit
electrical data
208/230-3-60
460-3-60
575-3-60 380/415-3-50
PFH067A-_L7
FLA
26.5
12.9
9.7
—
FLA
24.1
11.7
9.1
11.7
WSA
31.7
15.4
11.6
—
WSA
29.3
14.2
11.1
N/A
OPD
50
25
15
—
OPD
45
20
15
—
MCD69W
PFH067A-_H7 or PFH066A-_H7 High Ambient
FLA
20.7
10.0
7.4
—
FLA
24.2
11.7
9.3
11.7
WSA
25.9
12.5
9.3
—
WSA
29.4
14.2
11.3
N/A
OPD
45
20
15
—
OPD
50
20
15
—
—
—
—
13.7
—
—
—
10.0
MCD64A
FLA
PFHZ67A-_L7 or PFHZ66A-_L7 Quiet-Line
MCD68W
FLA
26
FLA
22.5
10.9
8.3
10.9
WSA
27.7
13.4
10.2
N/A
OPD
45
20
15
—
Liebert® Mini-Mate2™
Electrical Data
Table 18
Single-point power kit, air-cooled split system electrical data, standard 1.5hp motor
208-3-60
230-3-60
460-3-60
575-3-60
380/415-3-50
MMD60E/K
MMD60E/K
MMD60E/K
MMD60E/K
MMD590E/K
MCD65A
MCD65A
MCD65A
MCD65A
MCD64A
FLA
32.1
32.1
15.7
11.7
16.9
WSA
37.3
37.3
18.2
13.6
N/A
OPD
50
50
25
20
N/A
FLA
59.9
57.2
28.3
21.7
31.3
WSA
72.0
68.7
34.0
26.1
N/A
OPD
80
80
40
30
N/A
FLA
41.9
41.0
20.1
15.2
22.0
WSA
47.1
46.2
22.6
17.1
N/A
OPD
60
60
30
20
N/A
FLA
59.9
57.2
28.3
21.7
31.3
WSA
72.0
68.7
34.0
26.1
N/A
OPD
80
80
40
30
N/A
Base Evaporator Model
MMD60E
MMD60E
MMD60E
MMD60E
MMD590E
Base Condensing Unit Model
MCD65A
MCD65A
MCD65A
MCD65A
MCD64A
Base Evaporator Model
Base Condensing Unit Model
Cooling Only
with Electric Reheat
with Humidifier
with Electric Reheat and Humidifier
with SCR Reheat
FLA
73.7
69.8
34.5
N/A
38.6
WSA
89.3
84.4
41.7
N/A
N/A
OPD
90
90
45
N/A
N/A
with SCR Reheat and Humidifier
Liebert® Mini-Mate2™
FLA
83.5
78.7
38.9
N/A
43.7
WSA
99.1
93.3
46.1
N/A
N/A
OPD
100
100
50
N/A
N/A
27
Electrical Data
Table 19
Single-point power kit, air-cooled split system electrical data, optional 2hp motor
208-3-60
230-3-60
460-3-60
575-3-60
380/415-3-50
MMD60E/K
MMD60E/K
MMD60E/K
MMD60E/K
MMD590E/K
MCD65A
MCD65A
MCD65A
MCD65A
MCD64A
FLA
32.3
32.3
15.8
12.0
17.4
WSA
37.5
37.5
18.3
13.9
N/A
OPD
50
50
25
20
N/A
FLA
60.1
57.4
28.4
22.0
31.8
WSA
72.2
68.9
34.1
26.4
N/A
OPD
80
80
40
30
N/A
FLA
42.1
41.2
20.2
15.5
22.5
WSA
47.3
46.4
22.7
17.4
N/A
OPD
60
60
30
20
N/A
FLA
60.1
57.4
28.4
22.0
31.8
WSA
72.2
68.9
34.1
26.4
N/A
OPD
80
80
40
30
N/A
Base Evaporator Model
MMD60E
MMD60E
MMD60E
MMD60E
MMD590E
Base Condensing Unit Model
MCD65A
MCD65A
MCD65A
MCD65A
MCD64A
Base Evaporator Model
Base Condensing Unit Model
Cooling Only
with Electric Reheat
with Humidifier
with Electric Reheat and Humidifier
with SCR Reheat
FLA
73.9
70.0
34.6
N/A
39.1
WSA
89.5
84.6
41.8
N/A
N/A
OPD
90
90
45
N/A
N/A
with SCR Reheat and Humidifier
FLA
83.7
78.9
39.0
N/A
44.2
WSA
99.3
93.5
46.2
N/A
N/A
OPD
100
100
50
N/A
N/A
28
Liebert® Mini-Mate2™
Electrical Data
Table 20
Single-point power kit water/glycol-cooled split system electrical data, standard 1.5hp motor
208-3-60
230-3-60
460-3-60
575-3-60
380/415-3-50
MMD60E/K
MMD60E/K
MMD60E/K
MMD60E/K
MMD59E/K
MCD69W
MCD69W
MCD69W
MCD69W
MCD68W
FLA
26.3
26.3
12.8
9.4
13.2
WSA
31.5
31.5
15.3
11.3
N/A
OPD
50
50
25
15
N/A
FLA
54.1
51.4
25.4
19.4
27.6
WSA
66.2
62.9
31.1
23.8
N/A
OPD
70
70
35
25
N/A
Base Evaporator Model
Base Condensing Unit Model
Cooling Only
with Electric Reheat
with SCR Reheat
FLA
67.9
64.0
31.6
N/A
34.9
WSA
83.5
78.6
38.8
N/A
N/A
OPD
90
80
40
N/A
N/A
FLA
36.1
35.2
17.2
12.9
18.3
WSA
41.3
40.4
19.7
14.8
N/A
OPD
60
60
25
20
N/A
FLA
54.1
51.4
25.4
19.4
27.6
WSA
66.2
62.9
31.1
23.8
N/A
OPD
70
70
35
25
N/A
Base Evaporator Model
MMD60E
MMD60E
MMD60E
MMD60E
MMD59E
Base Condensing Unit Model
MCD69W
MCD69W
MCD69W
MCD69W
MCD68W
FLA
67.9
64.0
31.6
N/A
34.9
WSA
83.5
78.6
38.8
N/A
N/A
OPD
90
80
40
N/A
N/A
FLA
77.7
72.9
36.0
N/A
40.0
WSA
93.3
87.5
43.2
N/A
N/A
OPD
100
90
45
N/A
N/A
with Humidifier
with Electric Reheat and Humidifier
with SCR Reheat
with SCR Reheat and Humidifier
Liebert® Mini-Mate2™
29
Electrical Data
Table 21
Single-point power kit water/glycol-cooled split system electrical data, optional 2hp motor
208-3-60
230-3-60
460-3-60
575-3-60
380/415-3-50
MMD60E/K
MMD60E/K
MMD60E/K
MMD60E/K
MMD59E/K
MCD69W
MCD69W
MCD69W
MCD69W
MCD68W
FLA
26.5
26.5
12.9
9.7
13.7
WSA
31.7
31.7
15.4
11.6
N/A
OPD
50
50
25
15
N/A
FLA
54.3
51.6
25.5
19.7
28.1
WSA
66.4
63.1
31.2
24.1
N/A
OPD
80
70
35
25
N/A
Optional 2.0 hp Motor
Base Evaporator Model
Base Condensing Unit Model
Cooling Only
with Electric Reheat
with Humidifier
FLA
36.3
35.4
17.3
13.2
18.8
WSA
41.5
40.6
19.8
15.1
N/A
OPD
60
60
25
20
N/A
FLA
54.3
51.6
25.5
19.7
28.1
WSA
66.4
63.1
31.2
24.1
N/A
OPD
80
70
35
25
N/A
with Electric Reheat and Humidifier
Base Evaporator Model
MMD60E
MMD60E
MMD60E
MMD60E
MMD59E
Base Condensing Unit Model
MCD69W
MCD69W
MCD69W
MCD69W
MCD68W
with SCR Reheat
FLA
68.1
64.2
31.7
N/A
35.4
WSA
83.7
78.8
38.9
N/A
N/A
OPD
90
90
40
N/A
N/A
FLA
77.9
73.1
36.1
N/A
40.5
WSA
93.5
87.7
43.3
N/A
N/A
OPD
100
90
45
N/A
N/A
with SCR Reheat and Humidifier
30
Liebert® Mini-Mate2™
Refrigerant Piping
10.0 REFRIGERANT PIPING
Table 22
Refrigerant charge
Model #
60Hz
50Hz
R-407C, oz (kg)
MM*60E
MM*59E
4 (0.11)
MM*60K
MM*59K
4 (0.11)
MC*65A
MC*64A
432 (12.3)
MC*69W
MC*68W
PFH067A-_L7
PFH066A-_L7
426 (12.1)
94 (2.7)
PFH067A-_H7
PFH066A-_H7
827 (23.4)
PFHZ67A-_L7
PFHZ66A-_L7
827 (23.4)
All evaporator units and condensing units are fully factory-charged with refrigerant. If field-supplied refrigerant piping is
installed, refrigerant must be added; refer to Table 25 to determine the additional charge.
Table 23
Recommended refrigerant line sizes
Equivalent Pipe
Length, ft (m)
Liquid
Suction
50 (15)
1/2"
1-1/8"
100 (30.5)
5/8"
1-1/8"
150 (45.7)
5/8"
1-3/8"
Suction line and liquid line sizing based on < 3 psi pressure drop in each and suction line refrigerant velocities
>1000FPM (5.1m/s) for proper oil return.
Table 24
Pipe length and condenser elevation relative to evaporator
Nominal System
Size Tons
Max. Equiv. Pipe
Length, ft. (m)
Maximum PFH Level
Above Evaporator, ft. (m)
Maximum PFH Level
Below Evaporator, ft. (m)
5
150 (45)
50 (15)
15 (4.6)
Maximum recommended total equivalent pipe length is 150 ft (46m). Suction and liquid lines may require
additional specialty items when vertical lines exceed 20 ft. (6m) and/or condensing unit installation is more than
15 ft. (4.6m) below the evaporator. Contact Emerson Application Engineering for assistance.
Table 25
Line charges - refrigerant per 100 ft. (30m) of Type L copper tube
R-407C, lb/100 ft. (kg/30m)
Line Size,
O.D., in.
Liquid Line
Suction Line
3/8
3.7 (1.7)
—
1/2
6.9 (3.1)
—
5/8
11.0 (5.0
0.4 (0.2)
3/4
15.7 (7.1)
0.6 (0.3)
7/8
23.0 (10.4)
1.0 (0.4)
1-1/8
—
1.7 (0.7)
1-3/8
—
2.7 (1.1)
Liebert® Mini-Mate2™
31
Refrigerant Piping
Table 26
Equivalent lengths for various pipe fittings, ft (m)
Copper Pipe
OD, in.
90 Degree
Elbow Copper
90 Degree
Elbow Cast
45 Degree
Elbow
Tee
Gate
Valve
Globe
Valve
Angle
Valve
1/2
0.8 (0.24)
1.3 (0.39)
0.4 (0.12)
2.5 (0.76)
0.26 (0.07)
7.0 (2.13)
4.0 (1.21)
5/8
0.9 (0.27)
1.4 (0.42)
0.5 (0.15)
2.5 (0.76)
0.28 (0.08)
9.5 (2.89)
5.0 (1.52)
3/4
1.0 (0.3)
1.5 (0.45)
0.6 (0.18)
2.5 (0.76)
0.3 (0.09)
12.0 (3.65)
6.5 (1.98)
7/8
1.45 (0.44)
1.8 (0.54)
0.8 (0.24)
3.6 (1.09)
0.36 (0.1)
17.2 (5.24)
9.5 (2.89)
1-1/8
1.85 (0.56)
2.2 (0.67)
1.0 (0.3)
4.6 (1.4)
0.48 (0.14)
22.5 (6.85)
12.0 (3.65)
1-3/8
2.4 (0.73)
2.9 (0.88)
1.3 (0.39)
6.4 (1.95)
0.65 (0.19)
32.0 (9.75)
16.0 (4.87)
1-5/8
2.9 (0.88)
3.5 (1.06)
1.6 (0.48)
7.2 (2.19)
0.72 (0.21)
36.0 (10.97)
19.5 (5.94)
Refrigerant trap = Four times equivalent length of pipe per this table
Figure 17 Refrigerant piping diagram
Pitch down 1/2" (13mm) per 10 ft. (3m)
Evaporator
Suction Line Piping
Condensing Unit
Below Evaporator
NOTE
When installing remote condensing units below the
evaporator, the suction gas line should be trapped with
an inverted trap to the height of the evaporator . This
prevents refrigerant migration to the compressors
during off cycles . Maximum recommended vertical
level drop to condensing unit is 15 ft. (4.6m) .
Condensing
Unit
Condensing
Unit
Evaporator
See Table 24 for recommended maximum
vertical rise above evaporator/maximum
vertical fall below evaporator.
Suction Line Piping
Condensing Unit Above Evaporator
Traps recommended at the base of riser exceeding
5 ft (1.5m) and every 20 feet (6m) of vertical rise.
Pitch down 1/2" (13mm) per 10 ft. (3m)
32
Liebert® Mini-Mate2™
Glycol Loop Piping
11.0 GLYCOL LOOP PIPING
Contact Emerson Application Engineering for assistance in choosing correct drycooler models. Refer
to Figure 18.
Figure 18 Heat rejection loop, multiple drycoolers and multiple indoor units
Expansion Tank
______ Gal. (L)
HP
GPM (l/s)
ft.
____(kW) ____ Per Pump @ ____(kPa)
FS
PUMP PACKAGE
Drycooler No. 1 Model ______
GPM (l/s) ____ P: ___ ft (kPa)
See Note 3
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Drycooler No. 2 Model ______
GPM (l/s) ____ P: ___ ft (kPa)
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
LEGEND
Gate Valve
Check Valve
Butterfly Valve
Relief Valve
Union
Ball or Flow Control Valve
FS
P:
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Flow Switch
Pressure Drop
Strainer/Filter
Notes:
1. Pressure and temperature gauges (or ports for same) are
recommended to monitor component pressure drops and performance.
2. Flow measuring devices, drain and balancing valves to be supplied
by others and located as required.
3. See product literature for installation guidelines and clearance dimensions.
4. Drawing shows dual pump package. Alternate pump packages with more
pumps may be considered; consult supplier
Liebert® Mini-Mate2™
33
Total
GPM
(L/s): _____
Pipe
Diam.: _____ In. (mm)
P: _____ Ft. (kPa)
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
DPN000991
Rev. 0
Model Number Nomenclature—All Systems
12.0 MODEL NUMBER NOMENCLATURE—ALL SYSTEMS
Figure 19 Split system evaporators
M = Liebert Mini-Mate2
M = Microprocessor Control
D = Disconnect Switch
0 = No Disconnect Switch
Nominal Capacity kBtuh
E = Split Evaporator
K = Evaporator w/ Free-Cooling Coil (3-way valve)
M M D 60 E 7 C H E L A
7 = R-407C DX Evaporator
0 = None
A = Filter Clog
B = Smoke Sensor
C = High-Temperature Sensor
D = Filter Clog & Smoke Sensor
E = Filter Clog & High-Temperature Sensor
F = Smoke Sensor & High-Temperature
Sensor
G = Filter Clog, Smoke Sensor & High
Temperature Sensor
A = 460V – 3ph-60Hz
B = 575V – 3ph-60Hz
C = 208V – 3ph-60Hz
D = 230V – 3ph-60Hz
M= 380/415V – 3ph-50Hz
H = Canister Humidifier
0 = No Humidifier
R = Remote Humidifier Contact
J = Canister Humidifier
& Remote Humidifier contact
0 = No Reheat
E = Electric Reheat
S = SCR Reheat
(N/A with Free-Cooling)
L = Low Static Blower, 1.5hp Motor
H = High Static Blower, 2hp Motor
Figure 20 Air-cooled systems—indoor centrifugal condensing units
M = Liebert Mini-Mate2
C = Condensing Unit
D = Disconnect Switch
0 = No Disconnect Switch
Nominal Capacity kBtuh
M C D 65 A L A H 7
A = Air-cooled Unit
7 = R-407C Refrigerant
H = Hot Gas Bypass
L = 95°F Ambient Liebert Lee-Temp (Air)
A = 460V – 3ph-60Hz
B = 575V – 3ph-60Hz
Y = 208/230V – 3ph-60Hz
M = 380/415V – 3ph-50Hz
34
Liebert® Mini-Mate2™
Model Number Nomenclature—All Systems
Figure 21 Air-cooled systems—outdoor prop fan condensing units
PFH = Prop Fan Condensing Unit w/HGBP
0 = Standard Sound Level
Z = Quiet-Line
Nominal Capacity, kBtuh
PFH 0 67 A - A L 7
A = Air-Cooled Unit
7 = R-407C Refrigerant
L = 95°F (35°C) Ambient Liebert Lee-Temp™
H = 105°F (41°C) Ambient Liebert Lee-Temp
- = Standard Coil
C = Coated Coil
A = 460V – 3ph-60Hz
B = 575V – 3ph-60Hz
Y = 208/230V – 3ph-60Hz
M = 380/415V – 3ph-50Hz
Figure 22 Water/glycol-cooled systems—indoor condensing units
M = Liebert Mini-Mate2™
C = Condensing Unit
D = Disconnect Switch
0 = No Disconnect Switch
Nominal Capacity (kBtuh)
M C D 69 W 2 A H 7
7 = R-407C Refrigerant
W = Water/Glycol-Cooled Unit
H = Hot Gas Bypass
2 = 2-Way Std. Pressure Valve
3 = 3-Way Std. Pressure Valve
D = 2-Way High Pressure Valve
T = 3-Way High Pressure Valve
Liebert® Mini-Mate2™
A = 460V – 3ph-60Hz
B = 575V – 3ph-60Hz
Y = 208/230V – 3ph-60Hz
M = 380/415V – 3ph-50Hz
35
Model Number Nomenclature—All Systems
Figure 23 Chilled water systems
M = Liebert Mini-Mate2
M= Microprocessor Control
D = Disconnect Switch
0 = No Disconnect Switch
Nominal Capacity (kBtuh)
C = Chilled Water
M M D 92 C 2 C H E L A
2 = 2-Way Chilled Water Valve (Motorized On/Off)
3 = 3-Way Chilled Water Valve (Motorized On/Off)
D = 2-Way Chilled Water Valve (Modulating)
T = 3-Way Chilled Water Valve (Modulating)
A = 460V – 3ph-60Hz
B = 575V – 3ph-60Hz
C = 208V – 3ph-60Hz
D = 230V – 3ph-60Hz
M= 380/415V – 3ph-50Hz
H =Canister Humidifier
0 = No Humidifier
R = Remote Humidifier Contact
J = Canister Humidifier &
Remote Humidifier contact
0 = No Reheat
E = Electric Reheat
H = Hot Water Reheat
L = Low Static Blower, 1.5hp Motor
H = High Static Blower, 2hp Motor
0 = None
A = Filter Clog
B = Smoke Sensor
C = High-Temperature Sensor
D = Filter Clog & Smoke Sensor
E = Filter Clog & High-Temperature Sensor
F = Smoke Sensor & High-Temperature Sensor
G = Filter Clog, Smoke Sensor & High-Temperature Sensor
36
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2- 5-Ton Systems
GUIDE SPECIFICATIONS FOR LIEBERT MINI-MATE2- 5-TON SYSTEMS
1.0
General
1.1
Summary
These specifications describe requirements for an environmental control system. The system shall be
designed to control temperature and relative humidity conditions within the room.
The manufacturer shall design and furnish all equipment in the quantities and configurations shown
on the project drawings.
System shall be supplied with CSA Certification to the harmonized U.S. and Canadian product safety
standard CSA C22.2 No 236/UL 1995 for “Heating and Cooling Equipment” and marked with the CSA
c-us logo (60 Hz only).
The system model number(s) shall be_________________________________________________________.
1.2
Design Requirements
The environmental control system shall be a Liebert Mini-Mate2 factory-assembled unit. On direct
expansion models, the refrigeration system shall be split, with the compressor located in a remote or
close-coupled condensing unit.
The evaporator section shall be designed for above dropped-ceiling installation. Condensing units
shall be designed for either outdoor or above-dropped-ceiling installation.
The system shall have a total cooling capacity of _______ BTU/hr (kW) and a sensible cooling capacity
of ________ BTU/hr (kW), based on the entering air condition of _____°F (°C) dry bulb and _____°F (°C)
wet bulb.
The unit is to be supplied for operation on a ______ volt, ______ phase, ______ Hz power supply.
1.3
Submittals
Submittals shall be provided with the proposal and shall include: Dimensional, Electrical and
Capacity data; and Piping and Electrical Connection Drawings.
1.4
Quality Assurance
The specified system shall be factory-tested before shipment. Testing shall include, but shall not be
limited to: Quality Control Checks, “Hi-Pot” Test (two times rated voltage plus 1000 volts, per NRTL
agency requirements), and Metering Calibration Tests. The system shall be designed and
manufactured according to world-class quality standards. The manufacturer shall be ISO 9001
certified.
Liebert® Mini-Mate2™
37
Guide Specifications for Liebert Mini-Mate2- 5-Ton Systems
2.0
Product
2.1
Standard Features/ All Systems
2.1.1
Evaporator Cabinet Construction
The cabinet and chassis shall be constructed of heavy gauge galvanized steel, and shall be serviceable
from one side. Mounting brackets shall be factory-attached to the cabinet. Internal cabinet insulation
shall meet ASHRAE 62.1 requirements for Mold Growth, Humidity & Erosion, tested per UL 181 &
ASTM 1338 standards.
2.1.2
Air Distribution
The fan shall be the centrifugal type, double width, double inlet. The shaft shall be heavy-duty steel
with self-aligning ball bearings with minimum life of 100,000 hours. The fan motor shall be 1750 rpm
(1450 rpm @ 50Hz) and mounted on an adjustable base. The drive package shall be equipped with an
adjustable motor pulley. The fan/motor assembly shall be mounted on vibration isolators.
The evaporator system shall be capable of delivering ____CFM (CMH) at ___ inches (mm) of external
static pressure. The fan motor shall be ____hp (W).
System shall be suitable for ducted air distribution.
2.1.3
Microprocessor Control
The control system shall be microprocessor-based, factory-wired into the system and tested prior to
shipment. The wall-mounted control enclosure shall include a 2-line by 16-character LCD providing
continuous display of operating status and alarm condition. A 7-key membrane keypad for setpoint/
program control and unit On/Off shall be located below the display. The control display shall be fieldwired to the control board using 4-conductor field-supplied thermostat wire.
Temperature and humidity sensors shall be located in the wall box, which shall be capable of being
located up to 300 ft (91.4m) from the evaporator unit.
2.1.3.1
Monitoring
The LCD shall provide On/Off indication, operating mode indication (cooling, heating, humidifying,
dehumidifying) and current day, time, temperature and humidity (if applicable) indication. The
monitoring system shall be capable of relaying unit operating parameters and alarms to the Liebert
SiteScan® monitoring system.
2.1.3.2
•
•
•
•
Control Setpoint Parameters
Temp. Setpoint 65-85°F (18 to 29°C)
Temp. Sensitivity 1 to 9.9°F (1 to 5°C)
Humidity Setpoint 20-80% RH
Humidity Sensitivity 1-30% RH
2.1.3.3
2.1.3.3.1
Unit Controls
Compressor Short-Cycle Control
The control system shall prevent compressor short-cycling by a 3 minute timer from compressor stop
to the next start.
2.1.3.3.2
Common Alarm and Remote On/Off
A common alarm relay shall be provided to provide a contact closure to a remote alarm device. Two (2)
terminals shall also be provided for remote On/Off control. Individual alarms shall be “enabled” or
“disabled” from reporting to the common alarm.
2.1.3.3.3
Setback Control
The control shall be user configurable to use a manual setpoint control or a programmable time-based
setback control. The setback control will be based on a 5 day/2 day program weekly schedule with
capability of accepting 2 events per program day.
2.1.3.3.4
Temperature Calibration
The control shall include the capabilities to calibrate the temperature and humidity sensors and
adjust the sensor response delay time from 10 to 90 seconds. The control shall be capable of displaying
temperature values in °F or °C.
38
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2- 5-Ton Systems
2.1.3.3.5
System Auto Restart
For startup after power failure, the system shall provide automatic restart with a programmable (up
to 9.9 minutes in 6-second increments) time delay. Programming can be performed either at the wallmounted controller or from the central site monitoring system.
2.1.4
Alarms
2.1.4.1
Unit Alarm
The control system shall monitor unit operation and activate an audible and visual alarm in the event
of the following factory preset alarm conditions:
• High Temperature
• Low Temperature
• High Humidity
• Low Humidity
• High Water Alarm - Lockout Unit Operation
• High Head Pressure
• Loss of Power
• Compressor Short Cycle
2.1.4.2
Custom Alarms (2x)
• Humidifier Problem
• Filter Clog
• Water Detected
• Smoke Detected
User customized text can be entered for the two (2) custom alarms.
2.1.4.3
Alarm Controls
Each alarm (unit and custom) shall be separately enabled or disabled, selected to activate the
common alarm (except for high head pressure).
2.1.4.4
Audible Alarm
The audible alarm shall annunciate any alarm that is enabled by the operator.
2.1.4.5
Common Alarm
A programmable common alarm shall be provided to interface user selected alarms with a remote
alarm device.
2.1.4.6
Remote Monitoring
All alarms shall be communicated to the Liebert site monitoring system with the following
information: date and time of occurrence, unit number and present temperature and humidity.
Liebert® Mini-Mate2™
39
Guide Specifications for Liebert Mini-Mate2- 5-Ton Systems
2.2
2.2.1
Direct Expansion System Evaporator Components
Direct Expansion Coil
The evaporator section shall include evaporator coil, thermostatic expansion valve and filter drier.
The evaporator coil shall have 5.6 sq.ft. (0.52 sq.m) face area, four rows deep. It shall be constructed of
copper tubes and aluminum fins and have a maximum face velocity of 444 FPM (2.26 m/s) at
2500 CFM (4248 CMH). An externally equalized thermostatic expansion valve shall control
refrigerant flow. The evaporator coil shall be factory-charged with R-407C refrigerant and sealed. The
evaporator unit can be coupled directly with the condensing unit or mounted remote to the
condensing unit.
The coil shall be provided with a condensate drain pan with an internally trapped drain line. The
evaporator drain pan shall include a factory-installed float switch to shut down the evaporator upon
high water condition.
2.2
Chilled Water System Components
2.2.1
Chilled Water Control Valve (On/Off)
The (2-way) (3-way) control valve shall be motorized slow-acting, non-spring return type to reduce
water hammer. Design pressure shall be 300psig (2067kPa) static pressure, with a maximum close-off
pressure of 60psi (414kPa).
2.2.2
Chilled Water Control Valve (Modulating)
A (2-way) (3-way) modulating, non-spring return valve controlled by the microprocessor to position
the valve in response to room conditions. Design pressure shall be 400psig (2758kPa) static pressure,
with a maximum close-off pressure of 72psi (496kPa).
2.2.3
Chilled Water Coil
The cooling coil shall have a minimum of 5.6 sq.ft. (0.52 sq.m) face area, 4 rows deep. It shall be
constructed of copper tubes and aluminum fins and have a maximum face velocity of 444 FPM (2.26
m/s) at 2500 CFM (4248 CMH). The coil shall be supplied with 45°F (7.2°C) entering water
temperature. The coil shall be supplied with ______ GPM (l/s) of chilled water and the pressure drop
shall not exceed ______ psi (kPa). The coil assembly shall be mounted in a condensate drain pan with
internally trapped drain line. The evaporator drain pan shall include a factory-installed float switch
to shut down the evaporator upon high water condition.
2.3
Indoor Air-Cooled Centrifugal Fan Condensing Unit
Condensing unit components shall include condenser coil, scroll compressor, high-pressure switch,
Liebert Lee-Temp™ refrigerant receiver, head pressure control valve, hot gas bypass system and
liquid line solenoid valve. The hot gas bypass circuit shall be provided to reduce compressor cycling
and improve operation under low load conditions.
All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal
piping, brazing, dehydration or charging shall be required. Condensing unit shall be designed for
95°F (35°C) ambient and be capable of operation to -30°F (-34.4°C). The condensing unit can be
coupled directly to the evaporator or can be mounted remote to the evaporator.
The condenser coil shall be constructed of copper tubes and aluminum fins. The condenser fan shall
be centrifugal type, double inlet, heavy-duty steel shaft, with self-aligning bearings. The fan motor
shall operate at 1750 rpm (1450 rpm @ 50 Hz), shall be equipped with adjustable motor pulley, and
shall be mounted on an adjustable base. The fan and motor assembly shall be mounted on vibration
isolators. The fan motor assembly shall be belt-drive.
The condenser fan shall be designed for 3500 CFM (5947 CFH) at 0.5" (13mm) w.g. external static
pressure.
40
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2- 5-Ton Systems
2.3
Outdoor Air-Cooled Prop Fan Condensing Unit
Condensing unit components shall include a condenser coil, a direct-drive propeller-type fan, a scroll
compressor, high pressure switch, Liebert Lee-Temp™ receiver and head pressure control valve, hot
gas bypass system and liquid line solenoid valve. A hot gas bypass system shall be provided to reduce
compressor cycling and improve operation under low load conditions.
All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal
piping, brazing, dehydration or charging shall be required. Condensing unit shall be designed for
95°F (35°C) ambient and be capable of operation to -30°F (-34.4°C).
The condenser coil shall be constructed of copper tubes and aluminum fins.
(Option) The condensing unit shall be designed to operate at a sound level less than 58 dBA.
(Option) The outdoor condensing unit shall be designed for design ambient operation of 105°F
(40.6°C).
2.3
Indoor Water/Glycol-Cooled Condensing Unit
The water/glycol condensing unit components shall include scroll compressor, high-pressure switch,
coaxial condenser, water regulating valve, hot gas bypass system and liquid line solenoid valve. A hot
gas bypass circuit shall be provided to reduce compressor cycling and improve operation under low
load conditions. All components shall be factory-assembled, charged with R-407C refrigerant and
sealed. No internal piping, brazing, dehydration or charging shall be required.
The coaxial condenser shall have a total system pressure drop of ______ ft. of water (kPa) and a flow
rate of ______ GPM (l/s) with ______ °F (°C) entering water/glycol temperature.
The condenser circuit shall be pre-piped with a [(2-way) (3-way)] regulating valve that is headpressure actuated.
The condenser water/glycol circuit shall be designed for a static operating pressure of [(150psi
(1034kPa)) (350psi (2413kPa))].
2.4
Factory-Installed Options
2.4.1
Steam Generating Humidifier
The environmental control system shall be equipped with a steam generating humidifier that is
controlled by the microprocessor control system. It shall be complete with disposable canister, all
supply and drain valves, steam distributor and electronic controls. The need to change canister shall
be annunciated on the microprocessor wall box control panel. The humidifier shall have a capacity of
_______ lb./hr. (kg/h). An LED on the humidifier assembly shall indicate cylinder full, overcurrent
detection, fill system fault and end-of-cylinder-life conditions.
2.4.2
Electric Reheat
The electric reheat shall be low-watt density, 304/304 stainless steel, finned-tubular and shall be
capable of maintaining room dry bulb temperature conditions when the system is calling for
dehumidification. The reheat section shall include a UL-approved safety switch to protect the system
from overheating. The capacity of the reheat coils shall be ______ BTU/HR (kW), with unit input
voltage of _____V, controlled in one stage.
2.4.3
Hot Water Reheat
The hot water reheat coil shall have copper tubes and aluminum fins with a capacity of ______ BTU/
HR (kW) when supplied with ______°F (°C) entering water temperature at _______ GPM (l/s) flow
rate. Maximum pressure drop shall be ______ psi (kPa). The control system shall be factory pre-piped
with a 2-way solenoid valve and cleanable Y-strainer. The hot water reheat coil shall be available on
chilled water units only.
Liebert® Mini-Mate2™
41
Guide Specifications for Liebert Mini-Mate2- 5-Ton Systems
2.4.4
SCR Electric Reheat
The electric reheat shall be low-watt density, 304/304 stainless steel, finned-tubular and shall be
capable of maintaining room dry bulb conditions when the system is calling for dehumidification. The
reheat section shall include an agency-approved safety switch to protect the system from overheating.
The SCR (Silicon Controlled Rectifier) controller shall proportionally control the reheat elements to
maintain the selected room temperature. The rapid cycling made possible by the SCR controller
provides precise temperature control, and the more constant element temperature improves heater
life. The unit microprocessor control shall operate the SCR controller, while cooling is locked on. The
capacity of the reheat coils shall be ______ BTU/HR (kW), with unit input voltage of ______V. Not
available on chilled water or free-cooling units.
2.4.5
Disconnect Switch, Non-Locking
The non-automatic, non-locking, molded case circuit breaker shall be factory-mounted in the highvoltage section of the electrical panel. The switch handle shall be accessible from the front of the
indoor unit.
2.4.6
High-Temperature Sensor
The high temperature sensor shall immediately shut down the system when high temperatures are
detected. The high temperature sensor shall be mounted with the sensing element in the return air.
2.4.7
Smoke Sensor
The smoke sensor shall immediately shut down the environmental control system and activate the
alarm system when activated. The sensing element shall sense the return air conditions. This smoke
sensor shall not function or replace any room smoke detector that may be required by local or national
codes.
2.4.8
Filter Clog Switch
The filter clog switch senses pressure drop across the filters and shall annunciate the wall-box display
upon reaching the adjustable setpoint.
2.4.9
Free-Cooling/Dual Cooling Coil
A free-cooling coil shall be integral to the evaporator cabinet, and shall be constructed of copper tubes
and aluminum fins. The coil shall be rated at ______ BTU/HR (kW) sensible cooling capacity with a
45°F (22°C), ___% glycol solution. The coil shall require ______ GPM (l/s) and the total unit pressure
drop shall not exceed ______ feet of water (kPa) when in the free-cooling mode. Free-cooling shall be
activated by a temperature stat and shall include factory-piped three-way valve and separate supply
and return piping.
Coil is designed for closed-loop applications using properly treated and circulated fluid. Not available
with SCR reheat.
An optional Cu-Ni coil is required to prevent premature corrosion if applied to open water tower loop.
A heat exchanger and pump shall be field-supplied to isolate the open water tower loop from the
free-cooling loop.
2.5
Ship-Loose Accessories
2.5.1
Remote Sensors
The unit shall be supplied with remote temperature and humidity sensors. The sensors shall be
connected to the unit by a ______ ft. (m) shielded cable.
2.5.2
Air Filter Box/Duct Flange
The evaporator section shall be supplied with an air filter box for use with ducted installations.
Two (2) filters shall be included 4" x 20" x 20" (102 mm x 508mm x 508mm) each, pleated type, with a
MERV 8 rating, based on ASHRAE 52.2-2007. A duct flange shall be supplied for use on the supply
air opening of the unit.
2.5.3
Condensate Pump
The condensate pump shall have the capacity of ___ GPH (___ l/h) at ___ ft. head (___ kPa). It shall be
complete with integral float switch, pump, motor assembly, discharge check valve, duct/wall
mountable bracket and reservoir. A secondary float switch shall be provided to permit field wiring to
the unit control to shut down the evaporator upon a high water level condition.
42
Liebert® Mini-Mate2™
Guide Specifications for Liebert Mini-Mate2- 5-Ton Systems
2.5.4
Condensate Pump Bracket
A condensate pump bracket shall be provided to mount condensate pump directly to the end of the
unit, allowing for easier installation and alignment of the condensate pump.
2.5.5
Refrigerant Line Sweat Adapter Kit
2.5.6
Single Point Power Kit
Provide a sweat adapter kit to permit field brazing of refrigerant line connections.
A single point power kit shall be provided for a close-coupled system to allow a single electrical power
feed to supply power to both the evaporator and indoor close-coupled condensing unit.
2.5.7
Liebert SiteScan® Site Monitoring System
A Liebert SiteScan Site Monitoring System Model ___________________________ shall be provided for
remote monitoring of the Liebert Mini-Mate2™ unit and monitoring of other Liebert support
equipment. The Liebert SiteScan system shall have the capability to monitor and change (at the user
direction) the temperature and humidity setpoints and sensitivities of each unit. The printer shall
provide the user with chronological alarm information. It shall also be capable of being programmed
to print out environmental conditions or operating modes at each unit.
Provide indicated quantities of the following:
• ______ Leak Detection System(s) Model ______________________________________
• ______ Remote Monitor(s) Model _____________________________________+_______
• ______ Auto-changeover Control(s) Model _____________________________________
2.5.8
Drycooler
The Liebert drycooler shall be a low-profile, direct-drive propeller fan-type air-cooled unit. The
drycooler shall be constructed with an aluminum cabinet and a copper-tube aluminum fin coil and
multiple direct drive fans. All electrical connections and controls shall be enclosed in an integral
weather-resistant electric control panel section of the drycooler. The unit is quiet and
corrosion-resistant.
The drycooler shall be designed for _____°F (°C) ambient.
2.5.9
Glycol Pump Package
The system shall include a centrifugal pump mounted in a weatherproof and vented enclosure. The
pump shall be rated for ____ GPM (l/s) at ____ ft. (kPa) of head and operate on ____ volt, ___ phase,
____ Hz.
Liebert® Mini-Mate2™
43
Guide Specifications for Liebert Mini-Mate2- 5-Ton Systems
3.0
Execution
3.1
Installation of Air Conditioning Unit
3.1.1
General
Install air conditioning unit in accordance with manufacturer’s installation instructions. Install unit
plumb and level, firmly anchored to support the unit’s weight in location indicated and maintain
manufacturer’s recommended clearances. Do not mount units above sensitive electronic equipment to
minimize risk of water overflow/leakage damage and improve maintenance/service access.
3.1.2
Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be
factory-mounted. Furnish copy of manufacturer’s electrical connection diagram submittal to electrical
contractor.
3.1.3
Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted.
Furnish copy of manufacturer’s piping connection diagram submittal to piping contractor.
3.1.4
Supply and Drain Water Piping
Connect water supply and drains to air conditioning unit. Unit drain shall be trapped internally and
shall not be trapped externally.
3.1.5
Field-Supplied Pan
A field-supplied pan with drain shall be installed beneath cooling units and water/glycol condensing
units.
3.2
Field Quality Control
Startup air conditioning unit in accordance with manufacturer’s startup instructions. Test controls
and demonstrate compliance with requirements.
44
Liebert® Mini-Mate2™
Technical Support / Service
Web Site
www.liebert.com
Monitoring
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2013 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
or registered trademarks of their respective owners.
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
SL-10536_REV5_10-13
Emerson Network Power
Division: Liebert
Web: www.emerson.com
www.EmersonNetworkPower.com