Installation Sheet DIN Rail Mount

Rail Mount
InstallationDIN
Sheet
CKR Series
MOUNTING INSTRUCTIONS
FEATURES
24
Operating
Voltage
24: 24-280 VAC
48: 48-530 VAC
60: 48-660 VAC
E
Rated Load Current
10: 10 Amps
20: 20 Amps
30: 30 Amps
!
Cauti
on
Tempe
ratur
e
High
80
60
@ 25°C
20
40
Curre
nt Ratin
g 20A
30
To remove
from DIN Rail
fig.1 Mounting on DIN Rail
P
-10
Switching Type
Blank: Zero Voltage Turn-On
-10: Random Turn-On
Required for valid part number
For options only and not required for valid part number
Do not forget to visit us at: www.crydom.com
30
10
20
20
40
60
Current Rating 20A @ 25°C
80
!
Caution
High Temperature
Locate the panel section on which the CKR SSR will be mounted on.
Overvoltage Protection
Blank: Not Included
P: Included
10
Using reasonable force, push CKR in the direction of the arrow
shown in fig.1.
DIN clip includes tabs for this type of mounting. Tab holes have a
diameter of 4.5 mm. You will need two screws (not included) no
larger than that to mount the SSR onto panel.
Control Voltage
D: 4-32 VDC
B: 90-140 VAC
A: 180-280 VAC
AxxxxE: 18-36 VAC
D
To install
on DIN Rail
Mounting on Panel
PART NUMBER NOMENCLATURE
CKR
Locate rail and align with non moveable end of CKR DIN clip.
For removal pull release tag in direction of arrow using blade of
screwdriver and pull it away from DIN rail.
Mounting clip incorporates tabs for screw mounting to panel
Box Clamp terminals
Bracket fits all standard 35 mm DIN rail profiles
LED input status indicator
Series
Mounting on DIN Rail
20
Crydom CKR Series Solid State Relays were developed to offer the advantages of semiconductor switching
technology in a standard 22.5 mm industrial package. Quick and easy installation is coupled with low drive
power requirements and efficient, reliable power SCR output. This compact new design offers up to 30 Arms
in ambient temperatures of 25ºC.
Choose one of the two mounting options and follow the instructions below.
10
High Power Ready-to-Use DIN Rail Mounted SSRs
Please read all installation instructions before using CKR Series SSRs.
Align SSR tabs with panel surface and screw both top and bottom
sides. Recommended torque is 12 in-lbs (1.36 Nm).
IMPORTANT CONSIDERATIONS
Mounting Air Gap (A)
To achieve maximum ratings, there must be a minimum spacing of 0.8 in (20 mm) between
the devices (horizontally) and of 3.15 in (80 mm) measured between DIN clip tabs (vertically).
Earth Bonding (Grounding)
The CKR heat sink is equiped with an earth bonding screw as is required for Class 1
Protection, in accordance with EN 60950 (VDE 0804). Recommended torque is 20 in-lbs
(2.2 Nm).
Rev: 112613
Copyright © 2014 Custom Sensors & Technologies. Specifications subject to change without notice.
Rail Mount
InstallationDIN
Sheet
(+/ )
DERATING CURVES (B)
( / )
The following deating curves must be observed before installation.
+3/A1 4/A2
25
Wire Size
Maximum wire size of AWG #10 (5.3 mm2) for input and output terminals.
Connections
Ensure that wires ends are stripped to a minimum length of 0.4 in (10 mm).
20
CKRxxx30xxxx
CKRxxx20xxxx
CKRxxx10xxxx
15
10
5
SOLID
S TAT E
C O N TA C T O R
1/L1
2/T1
0
20
40
60
Ambient Temperature (ºC)
Recommended Screw Torque Range
5-6 in-lbs (0.6-0.7 Nm) on input and 10-15 in-lbs (1.1-1.7 Nm) on output terminations.
80
Load
(A) The air gap is the clearance distance adjacent to either side of the relay or assembly measured to
the next closer relay or assembly.
(B) 100% Duty Cycle.
Rev: 112613
Output Current (Arms)
30
WIRING DIAGRAM