Power Distribution & Terminal Blocks

Power Distribution &
Terminal Blocks
Section Contents
Page
Selection table for SCCR PDBs & Power
terminal blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
Power distribution blocks
Series PDBFS enclosed, with high SCCR . . . . . . . . . . . . 295
Series PDB with high SCCR . . . . . . . . . . . . . . . . . . . . . 296
Power terminal blocks
Series 163 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297-298
Series 11675 2- to 12-Pole quick-connect . . . . . . . . . . . 299
Series 11725 2- to 4-Pole quick-connect . . . . . . . . . . . . 299
Series 160, 162, 163 & 165 . . . . . . . . . . . . . . . . . . . . . . 299
Series 162, 163 & 165 power stud terminal blocks . . . 300
Series 160, 162, 163 & 165 power splicer blocks . . . . 300
Series 14002 Barrier terminal blocks . . . . . . . . . . . . . . 301
Series 14004 Dead front terminal block . . . . . . . . . . . . 301
Power
Distribution
& Terminal
Blocks
293
Power Distribution & Terminal Blocks
Selection Table for SCCR Power Distribution Blocks and
Power Terminal Blocks
Control Panels. Marking the SCCR on Industrial Control
Panels (NEC® 409.110), Industrial Machinery Electrical
Panels (NEC® 607.3(A)), and HVAC equipment (NEC®
440.4(B)) is now required by the National Electrical Code.
PDBs or PTBs not marked with a SCCR, typically are the
weakest link and may limit an assembly to no more than 10kA
SCCR. The PDBFS and PDB Series have increased spacing
required where used in feeder circuits in equipment listed to
UL508A (UL1059 PTBs must be evaluated for proper spacings). Also, for building wiring systems, the PDBFS Series
and PDB Series power distribution blocks can be used to
meet the new 2008 NEC® requirements in section 376.56(B)
for PDBs in wireways.
Short-Circuit Current Rated Power Distribution
Blocks
Cooper Bussmann offers three distinctly different styles of
short-circuit current rated power distribution blocks (PDBs)
and power terminal blocks (PTBs) to match different
application needs. The differences are whether the power
distribution blocks are enclosed or not, and whether they are
UL1953 Listed PDBs or UL1059 Recognized PTBs, which
have different minimum spacing requirements. The table on
this page can assist in the selection of the right series for
your application requirements.
Why these are important?
Assembly short-circuit current ratings (SCCRs) are now
required in the 2008 NEC® and UL 508A Listed Industrial
Selection Table
Description
High
Enclosed SCCR*
Spacing**
1” Air
2” Surface
Industrial
Control
Panels
UL 508A
Branch
Circuit
Industrial
Control
Panels
UL 508A
Feeder
Circuit
Catalog
Page
UL
Series PDBFS
295
UL 1953 Listed
Yes†
Yes
Yes
Yes
Series PDB
296
UL 1953 Listed
No***
Yes
Yes
Yes
HVAC
UL
1995
Wireways
NEC®
376.56(B)
(Requires
UL 1953)
Yes
Yes
Yes
Yes
Yes
Yes
w/optional
cover
† IP20 finger-safe under specific conditions, see datasheet 1149.
*When protected by proper fuse class with maximum ampere rating specified or less.
** See PDB Spacing Requirements for Equipment table below.
***Optional covers are available. Not IP20, but provide a safety benefit.
****No, except: Yes, if single pole units installed with proper spacings.
PDB & PTB Minimum Spacing
Requirements for Equipment
UL Standard
Spacing between
Spacing between
live parts of
live parts and
opposite polarity
grounded parts
or enclosure
Through air Over surface
@600V
@600V
@600V
508A Feeder
Circuits
508A Branch
Circuits
1995 HVAC
1˝
2˝
1˝
3
1
1
⁄8˝
3⁄ ˝
8
⁄2˝
1⁄ ˝
2
Series PDB
⁄2˝
⁄2˝
1
Note: Refer to Specific UL standards for complete spacing details.
Series PDBFS
Data Sheet: 1049
294
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
Power Distribution & Terminal Blocks
Series PDBFS of Power Distribution Blocks
Electrical
• 600Vac/dc (UL 1953), 690Vac/dc (IEC)
• IP20 finger-safe under specific conditions
• Short-circuit current ratings up to 200kA, see table
• Ampacities up to 760 amps
• Cu wire range 14 AWG to 500 kcmil or 2.5 to 240 mm2
Feature/Benefits
• Enclosed, safer
installation; IP20
finger-safe under specific
conditions
• High short-circuit current
ratings up to 200kA:
PDBs do not have to be
the weak link in achieving
high SCCR for an
industrial control panel
• Small footprint saves
panel space
• Listed to UL 1953 which has minimum spacing
requirements at 600V of at least 1” through air and 2” over
surface required for feeders in UL 508A Industrial Control
Panels
• For 2D CAD drawings visit www.cooperbussmann.com
Mechanical
• DIN rail or panel mount; PDBFS330 & PDBFS504 panel
mount only
• Captive termination screws; screws do not get misplaced
• Wire ready: captive termination screws shipped backed out
to save time on conductor installations
• Sliding DIN rail latch for easy mounting
• Single pole, gang mountable for multiple pole applications
with interlocking dovetail accessory (optional)
• Flammability, UL 94V0
• Tin-plated Al connectors suitable for Cu conductors
• Elongated hole for panel mounting; easier mounting with
greater flexibility in matching up with drilled panel holes
• Part 2A1279: Interlocking dovetail pin accessory
One pin interlocks two units, two pins to interlock three units
• DIN rail end anchors required to prevent damage to block
when torquing
Agency/Standards
• UL Listed 1953, Guide QPQS, File E256146
• CSA Certified, Class 6228-01, File 15364
• IEC 60947-7-1
• IEC 60529, IP20 (finger-safe) under specific wiring
conditions
Series PDBFS
Terminal Copper Conductor Capability
Line
Load
Configuration
Electrical
(All Single
Pole)
Openings per Pole
Amps
Wire Range
Wire Range
Line
Load
Line
Load
J
T
RK1
RK5
AWG or
kcmil
AWG or
kcmil
LPJ
JJS
JJN
LPS-RK
LPN-RK
FRS-R
FRN-R
2/0 to 8 200
200
100
60
200kA
4 to 12
200
175
200
200
175
200
100
100
100
60
60
60
200kA
100kA
50kA
350 to 6 400
400
200
100
200kA
4 to 8
4
6 to 14
400
200
175
600
600
200
400
200
175
600
600
200
200
100
100
400
400
100
100
30
30
200
200
30
200kA
50kA
100kA
200kA
50kA
50kA
350
600
600
400
200
200kA
300 to 4 600
800*
600
200
100kA
600
500
600
400 to 6 600
800*
800*
600
600
600
400
400
600
200
200kA
100kA
100kA
PDBFS204
175A
2/0 to 8 AWG
70 to 10 mm2
2/0 to 8 AWG
70 to 10 mm2
2/0 to 8
PDBFS220
175A
2/0 to 8 AWG
70 to 10 mm2
4 to 14 AWG
25 to 2.5 mm2
2/0 to 8
PDBFS303
310A
350kcmil to 6 AWG 350kcmil to 6 AWG
185 to 16 mm2
185 to 16 mm2
350 to 6
PDBFS330
380A
500kcmil to 6 AWG
240 to 16 mm2
2 to 14 AWG
35 to 2.5 mm2
500 to 6
PDBFS377
570A
300kcmil to 4 AWG
150 to 12 mm2
4 to 14 AWG
25 to 2.5 mm2
PDBFS500
620A
350kcmil to 4 AWG 350kcmil to 4 AWG
185 to 12 mm2
185 to 12 mm2
PDBFS504
760A 500kcmil to 6 AWG 500kcmil to 6 AWG
240 to 16 mm2
240 to 16 mm2
14
2 to 6
300
250 to 4
350
300 to 4
500
400 to 6
8 to 14
SCCR
®
Ampacities 75ºC per NEC Table 310.16 and UL 508A Table 28.1
*Class L 800A (KRP-C 800_SP) or less fuses suitable for this particular SCCR case.
** Class G 60A (SC-60) or less or Class CC 30A (LP-CC-30, FNQ-R-30, KTK-R-30) or less are suitable for all SCCRs in this table.
Data Sheet: 1049
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
295
Power
Distribution
& Terminal
Blocks
Catalog
Number
Short-Circuit Current Rating Data
Conductors
Max Fuse Class & Amp**
Power Distribution & Terminal Blocks
Series PDB of Power Distribution Blocks
Electrical
• 600Vac/dc (UL 1953)
• Short-circuit current ratings up to 200kA, see table
• Wire range 14 AWG to 350 kcmil Cu
• Spacing between uninsulated opposite polarities or ground
meets UL 1953 which requires at least 1” through air and
2” over surface
• Ratings available with circuit breakers
Feature/Benefits
• High short-circuit current ratings up to 200kA. These
PDBs do not have to be the weak link in achieving high
SCCR for an industrial control panel
• Listed to UL 1953 which has minimum spacing
requirements at 600V of at least 1” through air and 2” over
surface required for feeder in UL 508A Industrial Control
Panels
• For 2D CAD drawings visit www.cooperbussmann.com
Agency/Standards
• UL Listed 1953, Guide QPQS, File E256146
Mechanical
• Panel mount
• Flammability, UL 94V0
• Tin-plated Al connectors suitable for Cu conductors
Optional covers
Covers are ordered for each individual pole, i.e., three
1-pole covers for 3-pole block, see table A.
Except PDB321 blocks have one cover for 1, 2 or 3 pole
versions, see table B.
Table A
Table B
Block
Cover
Block
Cover
PDB2XX-(pole): CPB162-1
PDB321-1
CPDB-1
PDB3XX-(pole): CPDB-1
PDB321-2
CPDB-2
PDB321-3
CPDB-3
Series PDB
Terminal Copper Conductor Capability
Line
Load
Configuration
Catalog
Number
Openings per Pole
Amps
-
Wire Range
Wire Range
Line
Pole
Load
Short-Circuit Current Rating Data
Conductors
Max Fuse Class & Amp*
Line
Load
J
T
RK1
RK5
AWG or
kcmil
AWG or
kcmil
LPJ
JJS
JJN
LPS-RK
LPN-RK
FRS-R
FRN-R
2/0 - 8
200
200
200
60
200kA
4 - 12
200 200
175† 175†
200† 200†
200†
100†
100†
60†
60†
60†
200kA
100kA
50kA
200
200
100
60
200kA
400
400†
14
175†
400
4-8
400†
10 - 12 175†
4-8
400
400†
10 - 14
175†
1/0 - 6 400†
400
8 - 12 175†
400
400†
175†
400
400†
175†
400
400†
175†
400
400†
175†
200†
400†
100†
200†
400†
100†
200†
400†
100†
200†
400†
100†
100†
100†
60†
100†
100†
60†
100†
100†
60†
100†
100†
60†
200kA
100kA
100kA
200kA
100kA
100kA
200kA
100kA
100kA
200kA
100kA
100kA
PDB204-1
PDB204-3
175A
2/0 - 8 AWG
2/0 - 8 AWG
2/0 - 8
PDB220-1
PDB220-3
175A
2/0 - 8 AWG
4 - 14 AWG
2/0 - 8
PDB280-1
PDB280-3
175A
2/0 - 8 AWG
1/4-20 X 3/4 STUD
2/0 - 8
PDB321-1
PDB321-2
PDB321-3
175A
PDB323-1
PDB323-3
2/0 - 8 AWG
4 - 14 AWG
2/0 - 8
310A 300kcmil - 4 AWG
4 - 12 AWG
300 - 4
PDB370-1
PDB370-3
310A 350kcmil - 4 AWG
4 - 14 AWG
350 - 4
PDB371-1
PDB371-3
310A 350kcmil - 4 AWG
(6) 2 - 12 AWG
(3) 1/0-12
350 - 4
14
Stud
4 -12
Ampacities 75ºC per NEC® Table 310.16 and UL508A Table 28.1
* Class G 60A (SC-60) or less or Class CC 30A (LP-CC-30, FNQ-R-30_SP, KTK-R-30) or less are suitable for all these SCCR in this table.
† Higher SCCR may be available, check data sheet 1149.
Data Sheet: 1049
296
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
SCCR
Power Distribution & Terminal Blocks
Series 163 Power Terminal Blocks
163 Series
Replaces Cooper Bussmann®
164 Series
Specifications
Description: Power terminal
block.
Dimensions: See Dimensions
illustrations.
Construction: Tin-plated
aluminum connectors.
Poles: 1- to 3-Poles, See
Catalog Numbers table on the
following page.
Wire Range: See Catalog
Numbers table on the following
page.
Ratings:
Volts: — 600Vac/dc
Amps: — See catalog Numbers table on the following page.
SCCR:— 10kA per UL 508A table SB4.1
Agency Information: CE, UL Recognized: Guide XCFR2,
UL E221592, General Industrial Class per UL1059, CSA
Certified: CSA LR15364
Flammability Rating: UL 94V0
Supplied with (4) #4 thread-cutting
screws assembled as shown
4.14"
Textured surface for marking
Power
Distribution
& Terminal
Blocks
Dimensions
1-pole
1.96"
2-pole
3.58"
CPDB-1 (single pole)
CPDB-2 (two pole)
CPDB-3 (three pole)
3-pole
5.20"
2.10"
3.72"
5.34"
.31"
3.37"
4.00"
0.97"
1.62"
3.25"
3.32"
Mtg. hole 0.21 x 0.41,
c'bore 0.42 x 0.62 x 0.12 deep
(See Following Page for Ratings)
Data Sheet: 1049
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
297
Power Distribution & Terminal Blocks
Series 163 Power Terminal Blocks
Catalog Numbers
Basic
Catalog
Numbers
Wire Size
(Poles) Lineside
(Poles) Loadside
Amps/
Pole
16301*
250kcmil-6 AWG Cu Only
250kcmil-6 AWG Cu Only
255
16303
350kcmil-6 AWG Cu-Al
350kcmil-6 AWG Cu-Al
310
16306
500kcmil-6 AWG Cu-Al
500kcmil-6 AWG Cu-Al
380
16321
2/0-14 AWG CU, 2/0-8Al
(6)4-14 AWG Cu, 4-8 AWG Al
175
16323
350kcmil-6 AWG Cu-Al
(6)4-14 AWG Cu, 4-12 AWG Al
310
16325
(2)2/0-14 AWG Cu, 2/0-8 AWG Al
(6)4-14 AWG Cu, 4-8 AWG Al
350
16330
500kcmil-6 AWG Cu-Al
(6) 2-14 AWG Cu, 2-12 AWG Al
380
16332
350kcmil-6 AWG Cu-Al
(3) 2-14 AWG Cu, 2-8 AWG Al
(2) 1/0-14 AWG Cu, 1/0-8 AWG Al
310
16335
500kcmil-6 AWG Cu-Al
(3) 2-14 AWG Cu, 2-8 AWG Al
(2) 1/0-14 AWG Cu, 1/0-8 AWG Al
380
16370
350kcmil-6 AWG Cu-Al
(12)4-14 AWG Cu, 4-12 AWG Al
310
16371
350kcmil-6 AWG Cu-Al
(6) 2-14 AWG Cu, 2-8 AWG Al
(3) 1/0-14 AWG Cu, 1/0-8 AWG Al
310
16372
350kcmil-6 AWG Cu-Al
(21) 10-14 AWG Cu, 10 AWG Al
310
16373
350kcmil-6 AWG Cu-Al
(14) 10-14 AWG Cu, 10 AWG Al
(3) 1/0-14 AWG Cu-Al
310
16375
600kcmil-2 AWG Cu-Al
(12)4-14 AWG Cu, 4-12 AWG Al
420
16376
600kcmil-2 AWG Cu-Al
(6) 2-14 AWG Cu, 2-8 AWG Al
(3) 1/0-14 AWG Cu, 1/0-8 AWG Al
420
16377
(2)300kcmil-4 AWG Cu-Al
(12)4-14 AWG Cu, 4-12 AWG Al
570
16378
500kcmil-6 AWG Cu-Al
Stud Size (2) 1/4-20 x 1
380
16383
500kcmil-6 AWG Cu-Al
Stud Size (1) 3/8-16 x 1
380
16390
3
⁄8-16 x 11⁄8 Stud Size
250
16394
1
16395
3
⁄8-16 x 11⁄8 Stud Size
3
⁄2-13 x 11⁄16 Stud Size
1
⁄2-13 x 11⁄16 Stud Size
400
⁄8-16 x 17⁄16 Stud Size
(2) 1⁄4-20 x 9⁄16 Stud Size
310
*Copper connectors for use with copper wire only.
Ordering Information
163 Series blocks are available in 1-, 2- or 3-poles. To order: Basic Catalog Number + Number of poles.
Examples:
16301-1 = one-pole block
16301-3 = three-pole block
Data Sheet: 1049
298
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
Line/Load
Power Distribution & Terminal Blocks
Power Terminal Blocks
Series 11675
Series 160, 162, 163
& 165
Specifications
Description: Screw
connection line side, (3)
0.250" quick-connect
load side power
terminal block.
Poles:
2- to 12-poles.
Wire Range:
8 – 14 AWG Cu.
Ratings:
Volts: — 250Vac/dc
Amps: — Up to 40A
SCCR:— 10kA per UL 508A table SB4.1
Agency Information: CE, Guide XCFR2, UL E62622;
CSA LR15364.
Torque Rating: 9 lb-in max.
Catalog Numbers
Catalog
Numbers
11675-2
11675-3
11675-4
11675-5
11675-6
11675-7
Poles
2
3
4
5
6
7
Catalog
Numbers
11675-8
11675-9
11675-10
11675-11
11675-12
Poles
8
9
10
11
12
Specifications
Description: Screw
connection line side, (4) 0.250"
quick-connect load side power
terminal block.
Poles: 2-, 3- or 4-poles.
Wire Range: 2 – 14 AWG
Cu/8 AWG Al.
Ratings:
Volts: — 600Vac/dc
Amps: — Up to 70A
SCCR:— 10kA per UL 508A table SB4.1
Agency Information: CE, UL Guide XCFR2, E62622;
CSA LR15364.
Torque Rating: 45 lb-in max.
Catalog Numbers
Catalog
Numbers
11725-2
11725-3
11725-4
Poles
2
3
4
Description: Power
terminal blocks.
Construction: Molded black
thermoplastic.
Wire Range: See Catalog
Numbers table.
Poles:
Series 160: 2-, 3- or 4-poles
Series 162, 163 and 165: 1-, 2- or 3-poles
Ratings:
Volts: — 600Vac/dc
Amps: — Up to 1520A
SCCR:— 10kA per UL 508A table SB4.1
Agency Information: CE, Guide XCFR2, UL E221592
General Industrial Class per UL 1059; CSA Class 6228-01,
File 53787.
Flammability Rating: UL 94V0.
Catalog Numbers
Connector
Load
Material &
Ag ency
Connection
Ampacity
Information
(6)#4-#14Cu, #4-#8Al
175A
UL/CSA
(6)#4-#14Cu, #4-#12Al
310A
UL/CSA
(4)#4-#14Cu, #4-#8Al
175A
UL/CSA
(6)#4-#14Cu, #4-#8Al
175A
UL/CSA
(6)#4-#14Cu, #4-#12Al
310A
UL/CSA
(6)#4-#14Cu, #4-#8Al
350A
UL/CSA
(6)#2-#14Cu, #2-#12Al
380A
UL/CSA
(3)#2-#14Cu, #2-#8Al
310A
UL/CSA
(2)1/0-#14Cu, 1/0-#8Al
16335
500kcmil-#6Cu/Al
(3)#2-#14Cu, #2-#8Al
380A
UL/CSA
(2)1/0-#14Cu, 1/0-#8Al
16370
350kcmil-#6Cu/Al
(12)#4-#14Cu, #4-#12Al 310A
UL/CSA
16371
350kcmil-#6Cu/Al
(6)#2-#14Cu, #2-#8Al
310A
UL/CSA
(3)1/0-#14Cu, 1/0-#8Al
16372
350kcmil-#6Cu/Al
(21)#10-#14Cu, #10Al
310A
UL/CSA
16373
350kcmil-#6Cu/Al
(3)1/0-#14Cu/Al
310A
UL/CSA
(14)#10-#14Cu, #10Al
16375
600kcmil-#2Cu/Al
(12)#4-#14Cu, #4-#12Al 420A
UL/CSA
16376
600kcmil-#2Cu/Al
(6)#2-#14Cu, #2-#8Al
420A
UL/CSA
(3)1/0-#14Cu, 1/0-#8Al
16377
(2)300kcmil-#4Cu/Al
(12)#4-#14Cu, #4-#12Al 570A
UL/CSA
16400
(4)500kcmil-#6Cu/Al
(22)#2-#14Cu/Al
1520A
UL/CSA
16528
(2)600kcmil-#2Cu/Al
(4)3/0-#6Cu/Al
840A
UL/CSA
(4)#4-#14Cu/Al
16530
(2)500kcmil-#6Cu/Al
(12)#4-#14Cu/Al
760A
UL/CSA
16541
(1)500kcmil-#6Cu/Al
(21)#6-#14Cu/Al
380A
UL/CSA
*160 Series Bases have mounting holes outside the barriers. Other bases (162 through 165)
have mounting holes within barriers. See Data Sheet for dimensional drawings.
Catalog Line
Numbers Connection
16021* 2/0-#14Cu, 2/0-#8Al
16023* 350kcmil-#6Cu/Al
16220
2/0-#14Cu, 2/0-#8Al
16321
2/0-#14Cu, 2/0-#8Al
16323
350kcmil-#6Cu/Al
16325
(2)2/0-#14Cu, 2/0-#8Al
16330
500kcmil-#6Cu/Al
16332
350kcmil-#6Cu/Al
How To Order
Catalog Number + # of Poles
Example: 16021 – 3 (complete part number)
Optional Covers:
160
162
163
165
Series:
Series:
Series:
Series:
CPB160 - (pole)
CPB162 - (pole)
CPDB- (pole)
CPDB165 (1 for each pole)
Data Sheets: 1117 (Series 160, 162, 165); 1148 (Series 163)
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
299
Power
Distribution
& Terminal
Blocks
Series 11725
Specifications
Power Distribution & Terminal Blocks
Power Terminal Blocks: Stud & Splicer
Series 162, 163 & 165
Series 160, 162,
163 & 165
Specifications
Description: Power stud
terminal blocks.
Construction: Molded black
thermoplastic.
Poles: 1-, 2- or 3-poles.
Wire Range: See Catalog
Numbers table.
Ratings:
Volts: — 600Vac/dc
Amps: — Up to 760A
SCCR:— 10kA per UL 508A
table SB4.1
Agency Information: CE,
Guide XCFR2, UL E221592
General Industrial Class per UL
1059; CSA Class 6228-01, File 53787.
Flammability Rating:
UL 94V0.
Specifications
Description: Power
splicer
terminal blocks.
Construction: Molded
black thermoplastic.
Wire Range: See
Catalog Numbers table.
Poles: Series 160: 2-, 3- or 4-poles
Series 162, 163 and 165: 1-, 2- or 3-poles
Ratings:
Volts: — 600Vac/dc
Amps: — Up to 620A
SCCR:— 10kA per UL 508A table SB4.1
Agency Information: CE, Guide XCFR2, UL E221592
General Industrial Class per UL 1059; CSA Class 6228-01,
File 53787.
Flammability Rating: UL 94V0.
Stud Block Catalog Numbers
Catalog
Line
Numbers Connection (Poles)
Connector to Stud
16280
2/0-#14Cu-Al
16281
2/0-#14Cu-Al
16378
500kcmil-#6Cu-Al
16383
500kcmil-#6Cu-Al
16582
(2)500kcmil-#6Cu-Al
Stud to Stud
1
16290
⁄4-20 x 3⁄4 Stud
3
16390
⁄8-16 x 11⁄8 Stud
1
16394
⁄2-13 x 11⁄16 Stud
3
16395
⁄8-16 x 17⁄16 Stud
3
16591
⁄8-16 x 17⁄16 Stud
1
16593
⁄2-13 X 1 Stud
Load
Connection (Poles)
Material &
Ampacity
Connector
Ag ency
Information
⁄4-20 X 3⁄4 Stud
⁄4-20 Tapped hole
(2)1⁄4-20 x 1 Stud
(1)3⁄8-16 x 1 Stud
(2)3⁄8-16 x 15⁄8 Stud
Al-175A
Al-175A
Al-380A
Al-380A
Al-760A
UL
UL
UL
UL
UL
—
—
CSA
CSA
CSA
⁄4-20 x 3⁄4 Stud
⁄8-16 x 11⁄8 Stud
1
⁄2-13 x 11⁄16 Stud
(2)1⁄4-20 x 9⁄16 Stud
(2)3⁄8-16 x 17⁄16 Stud
1
⁄2-13 X 1 Stud
Cu-175A
Cu-250A
Cu-400A
Cu-310A
Cu-400A
Cu-600A
UL
UL
UL
UL
UL
UL
—
CSA
CSA
CSA
CSA
CSA
1
1
1
3
Nuts are not supplied with blocks
How To Order
Catalog Number + # of Poles
Example: 16000 – 3 (complete part number)
Series:
Series:
Series:
Series:
How To Order
Catalog Number + # of Poles
Example: 16000 – 3 (complete part number)
Optional Covers:
Optional Covers:
160
162
163
165
Catalog Numbers
Connector
Catalog Line
Load
Material &
Ag ency
Numbers Connection
Connection
Ampacity
Information
16000* 2/0-#8Cu/Al
2/0-#8Cu/Al
Al-175A
UL
16003* 250kcmil-#6Cu Only
250kcmil-#6Cu Only
Cu-255A
UL
16005* 350kcmil-#6Cu/Al
350kcmil-#6Cu/Al
Al-310A
UL
16200
#2-#14Cu, #2-#8Al
#2-#14Cu, #2-#8Al
Al-115A
UL
16201
1/0-#14Cu Only
1/0-#14Cu Only
Cu-150A
UL
16204
2/0-#8Cu/Al
2/0-#8Cu/Al
Al-175A
UL
16301
250kcmil-#6Cu Only
250kcmil-#6Cu Only
Cu-255A
UL/CSA
16303
350kcmil-#6Cu/Al
350kcmil-#6Cu/Al
Al-310A
UL/CSA
16306
500kcmil-#6Cu/Al
500kcmil-#6Cu/Al
Al-380A
UL/CSA
16500
(2)350kcmil-#4Cu/Al
(2)350kcmil-#4Cu/Al
Al-620A
UL/CSA
16504
(2)500kcmil-#6Cu/Al
(2)500kcmil-#6Cu/Al
Al-760A
UL/CSA
*160 Series Bases have mounting holes outside the barriers. Other bases (162 through 165)
have mounting holes within barriers. See Data Sheet for dimensional drawings.
CPB160 - (pole)
CPB162 - (pole)
CPDB - (pole)
CPDB165 (1 for each pole) - new style
CPB165 - (pole) - old style
160 Series: CPB160 - (pole)
162 Series: CPB162 - (pole)
163 Series: CPDB - (pole)
For Short-circuit current rated stud power distribution
blocks, go to the Series PDB and Series 162 & 163
with high SCCR.
For Short-circuit current rated and/or finger-safe
splicer blocks, go to the Series PDBFS, Series PDB or
Series 162 & 163 with high SCCR.
Data Sheets: 1117 (Series 162, 165); 1148 (Series 163)
Data Sheets: 1117 (Series 160, 162, 165); 1148 (Series 163)
300
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
Power Distribution & Terminal Blocks
Power Terminal Blocks: Barrier & Dead Front
Series 14002
Specifications
Description: Barrier
terminal block.
Poles: 2- to 6-poles.
Wire Range: 2 – 14
AWG Cu/8 AWG Al.
Ratings:
Volts: — 600Vac/dc
Amps: — 115A
SCCR:— 10kA per
UL 508A table SB4.1
Agency Information: CE, Guide XCFR2, UL E62622;
CSA LR15364.
Torque Ratings*: 2-3, 50 lb-in; 4-6, 45 lb-in; 8, 40 lb-in;
10-14, 35 lb-in.
*Consult factory for torque ratings for CP and Q options.
Marking: Marking strip optional, consult factory.
Options For Load Side Connector
CP: Sems pressure plate, rated 60A, 600V
Q: Quick-Connect, rated 50A, 600V
To order options, enter letter code in front of Catalog
Number: i.e., CP14002-2.
Catalog Numbers
Poles
2
3
4
Catalog
Numbers
14002-5
14002-6
Poles
5
6
Power
Distribution
& Terminal
Blocks
Catalog
Numbers
14002-2
14002-3
14002-4
Series 14004
Specifications
Description: Dead
front terminal block.
Poles: 2 to 12 poles.
Wire Range:
4 – 14 AWG Cu/8
AWG Al.
Ratings:
Volts: — 600Vac/dc
Amps: — 90A
SCCR:— 10kA per UL 508A table SB4.1
Agency Information: CE, Guide XCFR2, UL E62622;
CSA LR15364.
Marking: Marking strip optional, consult factory.
Catalog Numbers
Catalog
Numbers
14004-2
14004-3
14004-4
14004-5
14004-6
14004-7
Poles
2
3
4
5
6
7
Catalog
Numbers
14004-8
14004-9
14004-10
14004-11
14004-12
Poles
8
9
10
11
12
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
301
302