VDRS-100 Datasheet - AC

For more information, please visit the product page.
date
08/23/2012
page
1 of 4
SERIES: VDRS-100 │ DESCRIPTION: AC-DC DIN RAIL
FEATURES
•
•
•
•
•
up to 96 W continuous power
DIN Rail power supplies
universal input (88~264 Vac / 124~370 Vdc)
single output from 12~48 V
over voltage, over load, over temperature,
and short circuit protections
• UL 1310, UL 508, and TUV safety approvals
• long life electrolytic capacitors
• efficiency up to 88%
RoHS
output
voltage
output
current
output
power
ripple
and noise1
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
(%)
VDRS-100-12
12
7.5
90
180
87
VDRS-100-15
15
6.4
96
180
87
VDRS-100-24
24
4
96
180
88
VDRS-100-48
48
2
96
250
87
MODEL
Note:
1. at full load, 230 Vac input, measured at 20MHz bandwidth with a 47 μF and 0.1 μF parallel cap on the output
PART NUMBER KEY
VDRS - 100 - XX
Base Number
Output
Voltage
cui.com
efficiency
For more information, please visit the product page.
date 08/23/2012 │ page 2 of 4
CUI Inc │ SERIES: VDRS-100 │ DESCRIPTION: AC-DC DIN RAIL
INPUT
parameter
conditions/description
min
max
units
88
124
264
370
Vac
Vdc
47
63
Hz
1.1
0.55
A
A
30
60
A
A
max
units
line regulation
±1
%
load regulation
±2
%
voltage
frequency
current
115 Vac
230 Vac
inrush current
115 Vac, cold start
230 Vac
typ
OUTPUT
parameter
conditions/description
temperature coefficient
(0 ~ 50°C)
hold-up time
at 115 Vac, cold start
at 230 Vac, cold start
adjustibility
adjustible with built-in trim pot
min
typ
±0.03
%/°C
16
32
ms
ms
±10
%
max
units
150
%
PROTECTIONS
parameter
conditions/description
min
over voltage protection
latch-off mode
115
over load protection
constant current limiting, automatically recovers
after fault condition is removed
102
short circuit protection
output shut down and auto restart
typ
%
SAFETY & COMPLIANCE
parameter
conditions/description
min
isolation voltage
input to output for 1 minute
input to case for 1 minute
isolation resistance
input to output, input to case,
output to case, 500 Vdc
safety approvals
UL 508, TUV EN 60950-1,
UL 1310 NEC class 2 compliant
EMI/EMC
EN 55022 : 2006(Class B), EN 61204-3: 2000, EN
61000-6-3: 2007, EN 61000-3-2,3 :2006,
EN 55024, EN 61204-3: 2000, EN 61000-6-1:
2007 (EN 61000-4-2,3,4,5,6,8,11)
typ
units
3,000
1,500
Vac
Vac
100
MΩ
leakage current
RoHS compliant
max
1
mA
yes
ENVIRONMENTAL
parameter
max
units
operating temperature
-20
70
°C
storage temperature
-40
85
°C
operating humidity
conditions/description
min
non-condensing
storage humidity
vibration
(10 ~ 500 Hz, 1 hour per axis, 3 hours total)
cui.com
typ
20
90
%
10
95
%
5
Grms
For more information, please visit the product page.
date 08/23/2012 │ page 3 of 4
CUI Inc │ SERIES: VDRS-100 │ DESCRIPTION: AC-DC DIN RAIL
MECHANICAL DRAWING
5.00 0.197
5.00 0.197
5.00 0.197
5.00 0.197
99.00 3.898
5.00 0.197
+V +V -V -V
DC ON
+V ADJ.
90.00 3.543
N
L
7.50 0.295
7.50 0.295
55.00 2.165
DERATING CURVE
Output power vs. Ambient temperature
Output power vs. Input Voltage
100
80
Load ( %)
Load ( %)
100
60
50
40
20
80
60
40
20
0
0
-20
0
10
20
30
90
40 50 60 70
100
110
120
Input Voltage (Vac) 60 Hz
Ambient temperature (°C)
ACTIVE DC SIGNAL - RELAY CONTACT
Contact Close
When the output voltage reaches the adjusted output voltage
Contact Open
When the output voltage drops below 90%
Contact Ratings (MAX)
30 V / 1 A resistive load
cui.com
264
For more information, please visit the product page.
CUI Inc │ SERIES: VDRS-100 │ DESCRIPTION: AC-DC DIN RAIL
date 08/23/2012 │ page 4 of 4
REVISION HISTORY
rev.
description
date
1.0
initial release
06/03/2010
1.01
new template applied
08/18/2011
1.02
V-Infinity branding removed, drawing updated
08/23/2012
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
[email protected]
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical
component is any component of a life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to
affect its safety or effectiveness.