Specification Sheet

C4700D Series
EURO SERIES DC/DC CONVERTER
FEATURES
•
•
•
•
•
•
•
•
•
1200 - 2500W
Industrial Grade DC/DC Converter
High Operating Temp
Hot Pluggable
Wide Input Voltage
Configurable Options
Eurocassette Mounting
Wall Mounting
Chassis Mounting
SPECIFICATIONS
INPUT
ENVIRONMENTAL
Input voltage
DC Input voltage: 10 - 800Vdc
See selection table
Units will turn off with under or over input voltage.
No-load input power
5-6W model (series dependent)
Switch on time
1-2 seconds.
Operating temperature
-20°C to +75°C
(optional -40 to 75C)
Load derating
Derate 2.5% per °C, from +55°C to 75°C
Cooling
H: Heatsink - natural convection
F: Fan - increased airflow recommended
TF: Temperature controlled Fan included
See selection table
OUTPUT
Output voltage
Voltage range; 4.5 - 400Vdc
See selection table
Environment Options
Option c: Extended temperature range to -40°C
Output current
See selection table.
Storage temperature
-40°C to +85°C
Ripple & noise
1% + 30mVpp
Humidity
Up to 95% RH, non-condensing
Line regulation
0.1% (±10%)
STANDARDS
Load regulation
0.2% typical, load step 10-90%
EMI standards
acc. to EN61000-6-4 class A, optionally class B
Load transient
6% typical, load step 10-90%
Immunity standards
acc. to EN61000-6-2
Response time
2-3ms typical ±1%
C-Tick
AS/NZS CISPR11: 2002 Group1 Class A
Temperature coefficient 0.02% per °C typical.
Safety / Construction
acc. to EN60950-1 / EN50178
Holdup time
10mS at 220VAC typical
Protection category
IP20 acc. to EN60529
NEMA or others on request
Turn on rise time
100mS typical (soft start)
Remote sensing
Standard for all series
Efficiency
80%-92% typical
Output Options
Option dd: Decoupling Diode for redundant /
parallel operation
Option cs: Active Current Sharing
Option h: Remote on/off (inhibit)
Option dr: DC OK via relay contacts
MECHANICAL
PROTECTION
Overload protection
Overvoltage protection
Protection Options
MTBF
Current limited at 105%–110% of full load.
OVP switches off module with automatic return
to operation
Option i: Inrush Current Limiting
Option sd: Reverse polarity protection for DC input
by Series Diode
Mounting
See technical illustrations
Eurocassette, pluggable module for 19" subrack
Option w: Wall Mounting
Option cha: Chassis Mounting
Dimensions
See Technical illustration
Connector
H15 acc. to DIN 41612 H15
and high current connectors for I > 50A,
or terminals / bolts / bars
Mechanical Options
Option ms: Increased Mechanical Strength
Option t: Tropical protection
19" Rack Mounting
Options
Subrack Height 3U, 5U, 6U
Wiring, Front Panels
Accessories: Fuses, MCBs, Mains on/off switch
Contact Powerbox for rack configuration
100Khrs to 140Khrs at 40°C
acc. to MIL-HDBK-217E (notice 1)
www.powerbox.com.au - 1800 251 380
www.powerbox.co.nz - 0800 104 480
Doc. No. C4700D Rev.E 02-02-16
C4700D Series
EURO SERIES DC/DC CONVERTER
SELECTION TABLE
INPUT OUTPUT INPUT OUTPUT INPUT INPUT OUTPUT INPUT
INPUT
INPUT
INPUT
INPUT
OUTPUT
OUTPUT OUTPUT
COOLING
10-16V AMPS
20-32V AMPS
40-64V 50-80V AMPS
80-160V 160-320V 320-380V 320-640V 450-800V AMPS
VDC
RANGE
C4700
100
C4720
160
C4730
C4740
180
C4750
C4770
C4780Z
C4770G
C4770K
180
F
5
4.5-5.5
C4701
80
C4721
110
C4731
C4741
140
C4751
C4771
C4781Z
C4771G
C4771K
150
F
9
8-10
C4702
68
C4722
95
C4732
C4742
120
C4752
C4772
C4782Z
C4772G
C4772K
130
F
12
11-13
C4703
58
C4723
80
C4733
C4743
100
C4753
C4773
C4783Z
C4773G
C4773K
110
F
15
14-16
C4704
46
C4724
60
C4734
C4744
75
C4754
C4774
C4784Z
C4774G
C4774K
80
F
24
23-26
C4705
40
C4725
50
C4735
C4745
65
C4755
C4775
C4785Z
C4775G
C4775K
70
F
28
26-30
C4709
22
C4729
30
C4739
C4749
38
C4759
C4779
C4789Z
C4779G
C4779K
40
F
48
45-55
C 4706 18
C4726
25
C4736
C4746
31
C4756
C4776
C4786Z
C4776G
C4776K
33
F
60
58-68
C4707
C4727
13
C4737
C4747
18
C4777G
C4777K
C4757
C4777
C4787Z
20
F
110
100-130
C4707J 6
10
C4727J 7
C4737J C4747J 10
C4757J
C4777J
C4787ZJ C4777GJ
C4777KJ 10
F
200
190-200
C4708
C4728
C4738
C4758
C4778
C4788 Z
C4778K
F
220
200-250
5
C4708J 3
7
C4728J 3.5
Note - Cooling Heatsink
C4748
10
C4778G
10
C4738J C4748J 5
C4758J C4778J C4788ZJ C4778GJ C4778KJ 5
F
400
380-400
H: Heatsink - Natural Convection / F: Fan - increased airflow recommended / TF: Temperature controlled Fan included
See selection table
OPTIONS
Model Designation:
Add the designation of options to the model number, eg. C2560-dd-dr-cs
Options for Input, Output, Environmental and Mechanical follow.
19" Rack Mounting:
Subrack Height 3U, 5U, 6U
Wiring, Front Panels
Accessories: Fuses, MCBs, Mains on/off switch
Contact Powerbox for rack configuration
INPUT OPTIONS
Option “i”
(inrush current limiting): A thermistor is connected in series with the input lines which changes its resistance from high to low when it
gets hot. It does not reduce the current surge if the input power is interrupted for a short period of time not allowing the thermistor to
cool down. Thermistors are fitted as standard to all mains input models except for 1-phase input of models > 2.5kW. Thermistors are
available up to 45A. For higher input current an electronic inrush current limitation can be offered.
Option “ie”
electronic inrush current limiting An electronic circuit limits the inrush current.
Option “sd”
(series diode): A series diode protects the module against input voltage of wrong polarity (additional power losses).
Option “ad”
(anti-parallel diode): To avoid the power losses of a series diode a diode is provided with opposite polarity in parallel to the input
blowing an internal or external fuse if the module is connected to a supply with wrong polarity.
Option “au”
(auto-ranging) For standard dual AC input models the range of 115/230Vac is to be selected by connecting the input line to different
pins on the connector. With auto-ranging the unit senses the input voltage and provides automatically the correct connection.
Option “p”
(power fail): A signal (logic or relay) is given if the input voltage (AC or DC) drops below the specified limit.
In AC input units we sense the rectified input voltage so that a power fail alarm will not be triggered if at light loads mains power
returns before the input capacitors are substantially discharged.
Option “r”
(relay): A relay instead of a logic signal is provided for failure indication.
OUTPUT OPTIONS
Option “dd”
Option “cs”
Option “csi”
Option “h1”
(decoupling diode): For redundant operation the outputs of two or more units are paralleled behind de-coupling diodes so that an
internal fault of one module does not affect the operation of the others. These diodes cause power losses.
(active current sharing): An additional control circuit provides active current sharing via an interconnecting wire between converters
that operate in parallel. Active current sharing should be used for multi-output units operating inparallel.
(current sharing interrupt): Option "csi" will effect the removal of the "cs" signal. Should there be an instance where a unit is not
supplying the load, then the effect of its "cs" signal is removed, and the load voltage is unaffected by this condition.
(inhibit): A terminal connected to the negative input line also shuts off the converter.
This can also be used in conjunction with a thermal trip which shuts the unit down.
Option “h2”
(inhibit): Operation of the unit is inhibited if a voltage signal (5V/10mA) is applied in reference to the negative line of the (main) output.
Option “rco”
(reducing current limiting at over temperature) A circuit reduces the current limiting level at higher temperature (to be specified).
Option “d”
(DC-ok, one output): A logic signal is given if the output voltage (main output in multi-output systems) is below the specified limit.
Option “m”
(DC-ok, all outputs): In multi-output systems a logic signal is provided if the voltage of any output is below the specified limit.
Option “ac”
(AC ok) A logic signal connected to relay contacts is given if the output voltage of an inverter is below the specified limit.
Option "y"
(sys-reset): This logic signal is a combination of power fail and DC-ok as specified for VME systems.
Option "r"
(relay): A relay instead of a logic signal is provided for failure indication.
www.powerbox.com.au - 1800 251 380
www.powerbox.co.nz - 0800 104 480
Doc. No. C4700D Rev.E 02-02-16
C4700D Series
EURO SERIES DC/DC CONVERTER
OPTIONS
ENVIRONMENT OPTIONS
Option "t"
Option "c"
Option "ms"
(tropical protection):The unit is given additional protection by a heavy
coat of varnish on the printed circuit board(s) and components.
(extended temperature range):The circuit is designed and tested for
operation at an ambient temperature as low as –40 °C.
(increased mechanical strength): Screws are secured by Locktite and
heavy components are fastened by ties and/or glue. Modules with the "ms" option
meet the standard EN61373 regarding shock and vibration.
MECHANICAL OPTIONS
Standard mounting
"Eurocassette" pluggable module for 19" sub-racks 8
Option "w"
(wall mounting): Module is screwed against a mounting plate for
installation in a cabinet. The load connections are typically a terminal block.
Option "cha"
Option "din"
(chassis mount) Module is designed for installation to a structure or
within cabinet. Screw type connectors are supplied with the module.
(DIN rail mount) Module is designed for DIN rail mounting to a
structure or within Cabinet. Screw type connectors are supplied with the module.
TECHNICAL ILLUSTRATIONS
www.powerbox.com.au - 1800 251 380
www.powerbox.co.nz - 0800 104 480