No. 23 - Circuit breaker ratings - type GMI circuit breakers

www.usa.siemens.com/techtopics
TechTopics No. 23
Circuit breaker ratings - type GMI circuit breakers
TechTopics No. 4 discussed the changes in the ratings structure
for medium-voltage circuit breakers used in metal-clad
switchgear. This issue of TechTopics includes more detailed
versions of the ratings tables for type GMI circuit breakers, both
for the “constant MVA” and the “constant kA” ratings.
The structure of ratings for these circuit breakers is defined in
the following standards:
Finally, as voltage is decreased further, a limit is approached
at which the contacts cannot absorb further increases in
heat during interruption. The maximum design voltage was
designated as “V,” and the range (the “constant MVA” region)
over which the interrupting current capability increases as
voltage decreases is defined in terms of voltage range factor
“K.” The voltage V/K defines the associated lower limit of
voltage.
Standard
"Constant MVA"
ratings
"Constant kA"
ratings
ANSI/IEEE
C37.04
1979
1999
Rating structure for AC high-voltage circuit breakers
ANSI
C37.06
1979
1987
1997
2000
AC high-voltage circuit breakers rated on a symmetrical current basis–preferred ratings and related
required capabilities
ANSI/IEEE
C37.09
1979
1999
Test procedure for AC high-voltage circuit breakers rated on a symmetrical current basis
ANSI/IEEE
C37.010
1979
1999
Application guide for AC high-voltage circuit breakers rated on a symmetrical current basis
Title
The 1999-2000 revisions comprise the first major structural
change to the circuit breaker rating standards since the
change from the total (asymmetrical) current basis of rating
to the symmetrical current basis of rating in 1964. The 1964
rating structure reflects a “constant MVA” ratings basis over
a range of operating voltages, and reflects the air-magnetic
interruption technology then common. At the maximum
design voltage, interrupting capacity is limited by the ability of
the circuit breaker to withstand the transient recovery voltage
across the circuit breaker contacts following interruption. As
the operating voltage is reduced, the interrupting capability
increases, as the air-magnetic arc chutes can more readily
handle the reduced transient recovery voltage.
In the range of V/K to V, the interrupting current varies so the
product of voltage and interrupting current is a constant. Thus,
interrupting MVA is constant over the range from V/K to V.
The “constant MVA” rating structure does not conform to
the physics of modern interrupting techniques. For today’s
vacuum interrupters, the interrupting capability of the vacuum
interrupter does not increase significantly as the operating
voltage is decreased from rated maximum design voltage.
The 1999-2000 revisions to the standards recognized this
by changing the voltage range factor (K) to equal 1.0, which
effectively removes it from the rating structure.
Answers for infrastructure.
Because there is a huge installed base of circuit breakers
that are rated to the old standards, we expect that new
circuit breakers and switchgear will be available with the
old “constant MVA” ratings for many years. “Constant MVA”
circuit breakers must be designed, rated, and tested to the old
standards, as the new standards do not define the full rating
structure or test requirements for the “constant MVA” circuit
breakers.
Gradually, however, the new “constant kA” circuit breakers
and switchgear will become more widely used. The use of
the “constant kA” ratings simplifies the application of circuit
breakers and switchgear, and also more accurately represents
the true physics of modern vacuum interrupters.
Type GMI circuit breaker ratings (historic “constant MVA” rating basis)
These ratings are in accordance with the following standards:
A
NSI/IEEE C37.04-1999 standard rating structure for AC high-voltage circuit breakers rated on a symmetrical current basis
A
NSI C37.06-1987 AC high-voltage circuit breakers rated on a symmetrical current basis – preferred ratings and related
required capabilities
A
NSI/IEEE C37.09-1979 standard test procedure for AC high-voltage circuit breakers rated on a symmetrical current basis
A
NSI/IEEE C37.010-1999 application guide for AC high-voltage circuit breakers rated on a symmetrical current basis
Circuit breaker type
Measured parameter
General
Units
5GMI-250
5GMI-350
Nominal voltage class
kV
4.16
Nominal 3-phase MVA class 9
MVA
250
Rated
voltage
Insulation
levels
Related
required
capabilities
Closing and
latching
(momentary)
15GMI-750
15GMI-1000
4.16
7.2
13.8
13.8
13.8
350
500
500
750
1,000
kV rms
4.76
4.76
8.25
15.0
15.0
15.0
Voltage range factor (K) 3
----
1.24
1.19
1.25
1.30
1.30
1.30
Power
frequency
kV rms
19
19
36
36
36
36
Lightning
impulse (BIL)
kV crest
60
60
95
95
95
95
A rms
1,200
2,000
1,200
2,000
3,000FC4
4,000FC4
1,200
2,000
3,000FC4
4,000FC4
1,200
2,000
1,200
2,000
3,000FC4
4,000FC4
1,200
2,000
3,000FC4
4,000FC4
Short-circuit (at rated maximum
design voltage) (I) 5, 6, 10
kA rms sym
29
41
33
18
28
37
Interrupting time
Cycles
5
5
5
5
5
5
Permissible tripping delay (Y)
Sec
2
2
2
2
2
2
Rated maximum design
voltage (V) divided by K (=V/K)
KV rms
3.85
4.0
6.6
11.5
11.5
11.5
Max. sym interrupting (K x I) 7
KA rms sym
36
49
41
23
36
48
Short-time current (K x I)
(three seconds)
kA rms
36
49
41
23
36
48
Asymmetrical (1.6 x K x I) 8
kA rms
58
78 opt1
78
66
77 opt1
37
58 opt1
58
77 opt1
77
Peak (2.7 x K x I) 8
kA peak
97
132 opt1
132
111
130 opt1
62
97 opt1
97
130 opt1
130
Withstand
voltage levels
Continuous
Current
15GMI-500
Maximum design voltage (V) 2
Rated
values
Rated current
7GMI-500
4
Footnotes:
1
High closing and latching (momentary) rating available for special application.
2
Maximum voltage for which the circuit breaker is designed and the upper limit for operation.
3
K is the ratio of the rated maximum design voltage to the lower limit of the range of operating voltage in which the required symmetrical and
asymmetrical interrupting capabilities vary in inverse proportion to the operating voltage.
4
4,000FC indicates that fan cooling is included in the switchgear structure for this rating. The circuit breaker for the 3,000 A rating may be located in the
upper cell or in the lower cell of a vertical section. The circuit breaker for the 4,000 A rating must be located in the upper cell of the vertical section.
4,000 A rating is not available in outdoor equipment. Some models use fan cooling for 3,000 A.
5
To obtain the required symmetrical interrupting capability of a circuit breaker at an operating voltage between 1/K times rated maximum design voltage
and rated maximum design voltage, the following formula shall be used:
Required symmetrical interrupting capability = rated short-circuit current (I) x [(rated maximum design voltage)/(operating voltage)]
For operating voltages below 1/K times rated maximum design voltage, the required symmetrical interrupting capability of the circuit breaker shall be
equal to K times rated short-circuit current.
6
Within the limitations stated in ANSI/IEEE C37.04-1979, all values apply to polyphase and line-to-line faults. For single-phase-to-ground faults, the specific
conditions stated in clause 5.10.2.3 of ANSI/IEEE C37.04-1979 apply.
7
Current values in this row are not to be exceeded even for operating voltage below 1/K times rated maximum design voltage. For operating voltages
between rated maximum design voltage and 1/K times rated maximum design voltage, follow footnote 5 above.
8
Current values in this row are independent of operating voltage up to and including rated maximum design voltage.
9
“Nominal 3-Phase MVA Class” is included for reference only – this information is not listed in ANSI C37.06-1987.
10
Standard duty cycle is CO – 15 s – CO.
Type GMI circuit breaker ratings (new “constant kA” rating basis)
These ratings are in accordance with the following standards:
A
NSI/IEEE C37.04-1999 standard rating structure for AC high-voltage circuit breakers
A
NSI/IEEE C37.06-2009 AC high-voltage circuit breakers rated on a symmetrical current basis – preferred ratings and related
required capabilities
A
NSI/IEEE C37.09-1999 standard test procedure for AC high-voltage circuit breakers rated on a symmetrical current basis
A
NSI/IEEE C37.010-1999 application guide for AC high-voltage circuit breakers rated on a symmetrical current basis
Circuit breaker type
Rated values
Units
5GMI-31
5GMI-40
5GMI-50
7GMI-40
15GMI-20
15GMI-25
15GMI-31
15GMI-40
15GMI-50
Maximum design voltage (V) 1
kV rms
4.76
4.76
4.76
8.25
15.0
15.0
15.0
15.0
15.0
Voltage range factor (K)
----
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Power
frequency
kV rms
19
19
19
36
36
36
36
36
36
Lightning
impulse
(BIL)
kV crest
60
60
60
95
95
95
95
95
95
Continuous 3
A rms
1,200
2,000
1,200
2,000
3,000FC3
4,000FC3
1,200
2,000
3,000FC3
4,000FC3
1,200
2,000
3,000FC3
4,000FC3
1,200
2,000
1,200
2,000
1,200
2,000
1,200
2,000
3,000FC3
4,000FC3
1,200
2,000
3,000FC3
4,000FC3
Short-circuit (I) 4, 5
kA rms sym
31.5
40
50
40
20
25
31.5
40
50
ms cycles
83
5
83
5
83
5
83
5
83
5
83
5
83
5
83
5
83
5
Withstand
voltage
levels
2
Interrupting time
Permissible tripping delay (Y)
Sec
2
2
2
2
2
2
2
2
2
Max. sym interrupting (I)
kA rms sym
31.5
40
50
40
20
25
31.5
40
50
% dc component
%
47
47
47
47
47
47
47
47
47
Short-time current (I)
(three seconds)
kA rms
31.5
40
50
40
20
25
31.5
40
50
Closing and latching
(momentary)
asymmetrical (1.55 x I)
kA rms
49
62
78
62
31
39
49
62
78
Closing and latching
(momentary) peak (2.6 x I)
kA peak
82
104
130
104
52
65
82
104
130
Footnotes:
1
Maximum voltage for which the circuit breaker is designed and the upper limit for operation.
2
K is listed for informational purposes only. For circuit breakers rated on a “kA basis,” the voltage range factor is 1.0.
3
4,000FC indicates that fan cooling is included in the switchgear structure for this rating. The circuit breaker for the 3,000 A rating may be located in the
upper cell or in the lower cell of a vertical section. The circuit breaker for the 4,000 A rating must be located in the upper cell of the vertical section.
4,000 A rating is not available in outdoor equipment. Some models use fan cooling for 3,000 A.
4
All values apply to polyphase and line-to-line faults.
5
Standard duty cycle is O – 0.3 s – CO – 15 s – CO.
The information provided in this document contains merely general
descriptions or characteristics of performance which in case of actual
use do not always apply as described or which may change as a result of
further development of the products. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the terms
of contract.
All product designations may be trademarks or product names of
Siemens AG or supplier companies whose use by third parties for their
own purposes could violate the rights of the owners.
Siemens Industry, Inc.
7000 Siemens Road
Wendell, NC 27591
Subject to change without prior notice.
Order No.: IC1000-F320-A129-X-4A00
All rights reserved.
© 2012 Siemens Industry, Inc.
For more information, contact: +1 (800) 347-6659
www.usa.siemens.com/techtopics