J24229-1 Fl_L2 Final Report.pdf

ANALYTICAL REPORT
Job Number: 660-24229-1
Job Description: Raytheon
For:
ARCADIS U.S., Inc.
14055 Riveredge Drive
Suite 400
Tampa, FL 33637
Attention: Mr. Gus Suarez
_____________________________________________
Natalie Tafuni
Project Manager I
[email protected]
07/24/2008
Methods: FDEP, DOH Certification #: E84282, E81005 These test results meet all the requirements of NELAC unless
specified in the case narrative. All questions regarding this test report should be directed to the TestAmerica Project
Manager who signed this test report. The estimated uncertainty associated with these reported results is available upon
request. The results contained in this test report relate only to these samples included herein.
TestAmerica Laboratories, Inc.
TestAmerica Tampa 6712 Benjamin Road, Suite 100, Tampa, FL 33634
Tel (813) 885-7427 Fax (813) 885-7049 www.testamericainc.com
Page 1 of 14
Job Narrative
660-J24229-1
Comments
No additional comments.
Receipt
All samples were received in good condition within temperature requirements.
300.0
The batch matrix spike recovery for batch 660-65221 was outside of control limits for bromide. The data are flagged with J3 qualifiers.
Page 2 of 14
EXECUTIVE SUMMARY - Detections
Client: ARCADIS U.S., Inc.
Lab Sample ID
Analyte
660-24229-1
Client Sample ID
Result / Qualifier
0.066
Bromide
Method
1.0
mg/L
300.0
1.0
mg/L
300.0
IMW-7_072208
0.84
I
1.0
mg/L
300.0
0.34
I
1.0
mg/L
300.0
0.83
I
1.0
mg/L
300.0
DMW-M_072208
Bromide
660-24229-5
I
1.1
Bromide
660-24229-4
Units
IMW-14_072208
Bromide
660-24229-3
Reporting
Limit
IMW-17_072208
Bromide
660-24229-2
Job Number: 660-24229-1
IDPT-4_072208
TestAmerica Tampa
Page 3 of 14
METHOD SUMMARY
Client: ARCADIS U.S., Inc.
Description
Job Number: 660-24229-1
Lab Location Method
Preparation Method
Matrix: Water
Anions by Ion Chromatography
TAL TAM
MCAWW 300.0
Lab References:
TAL TAM = TestAmerica Tampa
Method References:
MCAWW = "Methods For Chemical Analysis Of Water And Wastes", EPA-600/4-79-020, March 1983 And Subsequent Revisions.
TestAmerica Tampa
Page 4 of 14
METHOD / ANALYST SUMMARY
Client: ARCADIS U.S., Inc.
Job Number: 660-24229-1
Method
Analyst
MCAWW 300.0
Petterson, Alyssa
TestAmerica Tampa
Page 5 of 14
Analyst ID
AP
SAMPLE SUMMARY
Client: ARCADIS U.S., Inc.
Job Number: 660-24229-1
Lab Sample ID
Client Sample ID
Client Matrix
660-24229-1
660-24229-2
660-24229-3
660-24229-4
660-24229-5
IMW-17_072208
IMW-14_072208
IMW-7_072208
DMW-M_072208
IDPT-4_072208
Water
Water
Water
Water
Water
TestAmerica Tampa
Page 6 of 14
Date/Time
Sampled
07/22/2008
07/22/2008
07/22/2008
07/22/2008
07/22/2008
1506
1315
1344
1405
1421
Date/Time
Received
07/23/2008
07/23/2008
07/23/2008
07/23/2008
07/23/2008
0844
0844
0844
0844
0844
SAMPLE RESULTS
TestAmerica Tampa
Page 7 of 14
Analytical Data
Client: ARCADIS U.S., Inc.
Job Number: 660-24229-1
General Chemistry
Client Sample ID:
Lab Sample ID:
Client Matrix:
IMW-17_072208
660-24229-1
Water
Analyte
Bromide
Result
0.066
Anly Batch: 660-65221
Client Sample ID:
Lab Sample ID:
Client Matrix:
Result
1.1
Anly Batch: 660-65221
PQL
1.0
Dil
1.0
Method
300.0
Date Sampled:
Date Received:
Qual
Units
mg/L
Date Analyzed
MDL
0.011
07/24/2008 0017
PQL
1.0
07/22/2008 1315
07/23/2008 0844
Dil
1.0
Method
300.0
IMW-7_072208
660-24229-3
Water
Analyte
Bromide
Result
0.84
Anly Batch: 660-65221
Client Sample ID:
Date Sampled:
Date Received:
Qual Units
I
mg/L
Date Analyzed
MDL
0.011
07/24/2008 0017
PQL
1.0
07/22/2008 1344
07/23/2008 0844
Dil
1.0
Method
300.0
DMW-M_072208
660-24229-4
Water
Analyte
Bromide
Result
0.34
Anly Batch: 660-65221
Client Sample ID:
Lab Sample ID:
Client Matrix:
MDL
0.011
07/24/2008 0017
660-24229-2
Water
Client Sample ID:
Lab Sample ID:
Client Matrix:
Qual Units
I
mg/L
Date Analyzed
07/22/2008 1506
07/23/2008 0844
IMW-14_072208
Analyte
Bromide
Lab Sample ID:
Client Matrix:
Date Sampled:
Date Received:
Date Sampled:
Date Received:
Qual Units
I
mg/L
Date Analyzed
MDL
0.011
07/24/2008 0017
PQL
1.0
07/22/2008 1405
07/23/2008 0844
Dil
1.0
Method
300.0
IDPT-4_072208
660-24229-5
Water
Analyte
Bromide
TestAmerica Tampa
Result
0.83
Anly Batch: 660-65221
Date Sampled:
Date Received:
Qual Units
I
mg/L
Date Analyzed
MDL
0.011
07/24/2008 0017
Page 8 of 14
PQL
1.0
07/22/2008 1421
07/23/2008 0844
Dil
1.0
Method
300.0
DATA REPORTING QUALIFIERS
Client: ARCADIS U.S., Inc.
Lab Section
Job Number: 660-24229-1
Qualifier
Description
J3
Estimated value; value may not be accurate. Spike recovery
or RPD outside of criteria.
U
Indicates that the compound was analyzed for but not
detected.
I
The reported value is between the laboratory method
detection limit and the laboratory practical quantitation limit.
General Chemistry
TestAmerica Tampa
Page 9 of 14
QUALITY CONTROL RESULTS
TestAmerica Tampa
Page 10 of 14
Quality Control Results
Client: ARCADIS U.S., Inc.
Job Number: 660-24229-1
Method Blank - Batch: 660-65221
Lab Sample ID:
Client Matrix:
Dilution:
Date Analyzed:
Date Prepared:
MB 660-65221/1
Water
1.0
07/24/2008 0017
N/A
Method: 300.0
Preparation: N/A
Analysis Batch: 660-65221
Prep Batch: N/A
Units: mg/L
Instrument ID: No Equipment Assigned
Lab File ID:
N/A
Initial Weight/Volume: 1.0 mL
Final Weight/Volume: 5 mL
Analyte
Result
Qual
MDL
PQL
Bromide
0.011
U
0.011
1.0
Lab Control Spike/
Lab Control Spike Duplicate Recovery Report - Batch: 660-65221
Method: 300.0
Preparation: N/A
LCS Lab Sample ID: LCS 660-65221/2
Client Matrix:
Water
Dilution:
1.0
Date Analyzed:
07/24/2008 0017
Date Prepared:
N/A
Analysis Batch: 660-65221
Prep Batch: N/A
Units: mg/L
Instrument ID: No Equipment Assigned
Lab File ID: N/A
Initial Weight/Volume:
1.0 mL
Final Weight/Volume:
5 mL
LCSD Lab Sample ID: LCSD 660-65221/3
Client Matrix:
Water
Dilution:
1.0
Date Analyzed:
07/24/2008 0017
Date Prepared:
N/A
Analysis Batch: 660-65221
Prep Batch: N/A
Units: mg/L
Instrument ID:
No Equipment Assigned
Lab File ID:
N/A
Initial Weight/Volume: 1.0 mL
Final Weight/Volume: 5 mL
Analyte
LCS
Bromide
95
% Rec.
LCSD
92
Limit
RPD
RPD Limit
90 - 110
3
30
Calculations are performed before rounding to avoid round-off errors in calculated results.
TestAmerica Tampa
Page 11 of 14
LCS Qual LCSD Qual
Quality Control Results
Client: ARCADIS U.S., Inc.
Job Number: 660-24229-1
Matrix Spike/
Matrix Spike Duplicate Recovery Report - Batch: 660-65221
Method: 300.0
Preparation: N/A
MS Lab Sample ID:
Client Matrix:
Dilution:
Date Analyzed:
Date Prepared:
680-38139-F-1 MS
Water
2.0
07/24/2008 0017
N/A
Analysis Batch: 660-65221
Prep Batch: N/A
Instrument ID: No Equipment Assigned
Lab File ID:
N/A
Initial Weight/Volume: 1.0 mL
Final Weight/Volume: 5 mL
MSD Lab Sample ID:
Client Matrix:
Dilution:
Date Analyzed:
Date Prepared:
680-38139-F-1 MSD
Water
2.0
07/24/2008 0017
N/A
Analysis Batch: 660-65221
Prep Batch: N/A
Instrument ID: No Equipment Assigned
Lab File ID:
N/A
Initial Weight/Volume: 1.0 mL
Final Weight/Volume: 5 mL
Analyte
MS
Bromide
89
% Rec.
MSD
90
Limit
RPD
RPD Limit
MS Qual MSD Qual
90 - 110
1
30
J3
Calculations are performed before rounding to avoid round-off errors in calculated results.
TestAmerica Tampa
Page 12 of 14
Page 13 of 14
Login Sample Receipt Check List
Client: ARCADIS U.S., Inc.
Job Number: 660-24229-1
Login Number: 24229
Creator: Atkins, Amy
List Number: 1
List Source: TestAmerica Tampa
Question
T / F/ NA
Radioactivity either was not measured or, if measured, is at or below
background
The cooler's custody seal, if present, is intact.
The cooler or samples do not appear to have been compromised or
tampered with.
Samples were received on ice.
Cooler Temperature is acceptable.
Cooler Temperature is recorded.
COC is present.
COC is filled out in ink and legible.
COC is filled out with all pertinent information.
There are no discrepancies between the sample IDs on the containers and
the COC.
Samples are received within Holding Time.
Sample containers have legible labels.
Containers are not broken or leaking.
Sample collection date/times are provided.
Appropriate sample containers are used.
Sample bottles are completely filled.
There is sufficient vol. for all requested analyses, incl. any requested
MS/MSDs
VOA sample vials do not have headspace or bubble is <6mm (1/4") in
diameter.
If necessary, staff have been informed of any short hold time or quick TAT
needs
Multiphasic samples are not present.
Samples do not require splitting or compositing.
N/A
Comment
N/A
True
True
True
True
True
True
True
True
True
True
True
True
True
True
True
True
True
True
True
TestAmerica Tampa
Page 14 of 14
4 Degrees.CU-04
Recd trip blank - no analysis per Gus Suarez