Brochure: SITOP UPS1600 - 24 V DC Uninterruptible Power Supply

SITOP UPS1600
Brochure 09/2013
24 V DC Uninterruptible Power Supply
High-performance, communicative and integrated in TIA
If a power failure occurs, not only does the AC power
go out but also the 24 V DC supply and thus the
complete automation system as well. Costly downtimes
and undefined system states can be the result. DC
uninterruptible power supplies prevent this scenario
by providing reliable backup of the DC voltage for hours
while also providing diagnostics and system integration.
The new SITOP UPS1600 offers even more possibilities
for system integration with comprehensive functions
and open communication via USB or Ethernet/PROFINET –
the first DC UPS with these interfaces, allowing it to fully
integrate into projects in TIA Portal.
The DC UPS modules complement 24 V DC power supplies
from SITOP for uninterrupted rated currents up to 20 A from
the UPS1100 battery modules based on maintenance-free
gel cell batteries. Via the integrated electronics, the UPS1600
automatically detects the type of battery and charges it at
the optimal, temperature-controlled charging characteristics.
The intelligent battery management system monitors
all relevant data, including battery modules connected in
parallel. The battery status and various values, such as the
­voltage, current or residual capacity, are output via the
­Ethernet/PROFINET interface. Even remote diagnostics
by means of a secure network is possible thanks to an
integrated web server. The device status of the UPS1600
along with the network connection can be easily monitored
in the SINEMA Server network management software.
The slim UPS1600 DC UPS module features dynamic overload response, which can be used to activate industrial PCs,
for example. The high charging current quickly restores the
buffering capacity following a power failure. For use in
stand-alone mode, the UPS can be activated from the
­battery, for example, to start generators.
The benefits at a glance
•Compact DC UPS modules SITOP UPS1600 24 V DC / 10 A
and 20 A with digital inputs and outputs, optionally with
USB or Ethernet/PROFINET interfaces with 2 ports
•Battery modules SITOP UPS1100 24 V DC / 1.2 Ah, 3.2 Ah
and 7 Ah with maintenance-free gel cell batteries and
­integrated electronics
•Intelligent battery management with automatic detection
of battery modules and selection of the optimal,
temperature-controlled charging characteristics.
Monitoring of operational readiness, battery connection,
­aging and charge level
•All diagnostic data and alarms available via USB and
Ethernet/PROFINET
•High dynamic overload capacity: 3 times rated current for
30 ms and 1.5 times rated current for 5 sec per ­minute
•High charging currents
•Cold start from battery modules when mains voltage is
­unavailable
•Remote monitoring with integrated web server
•SITOP UPS Manager (free software download) supports
configuration and monitoring with PC-based systems
•Full integration in TIA: Convenient engineering in the TIA
Portal, S7 function blocks for integration in user programs
and WinCC faceplates
www.usa.siemens.com/sitop
SITOP UPS1600 – the first open...
Whether open or system-integrated, the communicative DC UPS can be integrated into any automation solution. Fully
flexible data communication is performed via USB or Industrial Ethernet/Profinet. Special configuration and visualization
software makes it easy to integrate the DC UPS in both PC and PLC based systems. This means you benefit from the high
performance of the SITOP UPS1600 in any case.
Open communication
Control
Industrial PC
Control, configuring / monitoring
Industrial PC
PC
Industrial Ethernet
24 V DC
SITOP
power
supply
SITOP
UPS1600
SITOP
UPS1100
G_KT01_XX_00796
Energy Storage Link
Uninterruptible 24 V DC power supply
The advantages of SITOP UPS1600 through integration in PC-based systems
•Easy configuration and monitoring via SITOP UPS Manager, runs on all common Windows systems
•Comprehensive diagnostic capabilities using the UPS status and the connected energy storage
•Connection via USB or Ethernet
•Targeted shutdown of multiple PCs (master-slave principle)
•Closing of software applications
•Integrated OPC server (available soon)
•Remote monitoring via integrated UPS web server, a
­ ccess to device configuration information and ­operating data,
for example, mains/buffer mode, ­output power, charging current and battery status
2
SITOP UPS1600
SITOP UPS1600 in PC-based automation system:
Configuration and monitoring takes place via SITOP UPS Manager software. If a power failure occurs, the 24 V DC buffer
and the integration of the DC UPS in Industrial Ethernet enable controlled shutdown of multiple PCs in master-slave mode.
G_KT01_XX_00797
Remote monitoring via the web server:
The integrated web server provides access to all
relevant power supply data, of course, only with
­appropriate user credentials.
Configuration and monitoring with the SITOP
UPS Manager:
The free software tool supports easy configuration
of the UPS in the PC system and also visualization of
a wide variety of states of the UPS, even in the form
of trend charts.
SITOP UPS1600
3
Technical specifications
DC UPS modules
Order numbers
Input data
without interface
with USB interface
with 2 Ethernet / PROFINET interfaces
Rated input voltage Uin rated/ Range
Connection threshold for buffering
Input current Iin rated
Mains buffering
Adjustable range using rotary coding switch
Behavior on restoration of input voltage after buffering
time
On/off control circuit
(via external isolated NO contact)
Starting from battery with input voltage missing
(by means of external isolated NO contact)
Energy storage units
Connectable batteries
Output data
Output voltage in normal operation
Output voltage in buffering mode
Output +Bat/-Bat in normal operation
End-of-charge voltage
Output current – rated value
• Power boost for 30 ms
• Extra power for 5 s/min
Charging current
Efficiency for normal operation and charged battery
Protection and monitoring
Reverse polarity protection
Overload / short-circuit protection
Signaling
Normal operation/buffer mode
Charging status (over 85% charged)
Alarm (not ready for buffering)
Battery status
PROFINET interface (versions ...-2AY0)
Ethernet (versions ...-2AY0)
General data
Radio interference level (EN 55022) / noise immunity
Safety class
Degree of protection (EN 60529)
Ambient temperature during operation
with natural convection
Transport/storage temperature
Dimensions (W x H x D) in mm
Weight, approx.
Installation
Approvals
4
SITOP UPS1600
SITOP UPS1600 24 V/ 10 A
SITOP UPS1600 24 V/ 20 A
6EP4134-3AB00-0AY0
6EP4134-3AB00-1AY0
6EP4134-3AB00-2AY0
6EP4136-3AB00-0AY0
6EP4136-3AB00-1AY0
6EP4136-3AB00-2AY0
24 V DC/ 21 ... 29 V
22.5 V DC ± 3% (factory setting), adjustable:
21 V, 21.5 V, 22 V, 22.5 V, 23 V, 24 V, 25 V DC or via software.
Approx. 14 A for max. charging ­current
Approx. 25 A for max. charging ­current
(3 A)
(4 A)
0.5 min, 1 min, 2 min, 5 min, 10 min, 20 min,
max. buffering time or via software
Interruption of Uout for the automatic restart of PCs or optionally no interruption
by opening the circuit the buffer mode is terminated
by closing the circuit the buffer mode is started
– coded Siemens types SITOP UPS1100 (max. 6 over Energy Storage Link)
– non-coded Siemens types 6EP1935-6M...
– other manufacturers of lead-acid or pure lead batteries
Rated input voltage Uin less approx. 0.2 V
27 V DC (no load); 24 V DC (50% battery rated current);
22 V DC (100% battery rated current); 18.5 V DC (exhaustive discharge
protection)
I-U charging characteristic (first constant charging current, then charge retention)
Automatic temperature-specific setting with SITOP UPS1100 battery modules
0 ... 10 A
0 ... 20 A
30 A
60 A
15 A
30 A
Max. 4A
Max. 3 A
automatic adjustment with UPS1100;
automatic adjustment with UPS1100;
otherwise selectable 0.8 A,
otherwise selectable 0.3 A, 0.8 A, 3 A
1.75 A, 4 AA
> 97.3%
> 97.5%
against input voltage Uin and against batteries
Yes, restart in normal operation
LED 1 (OK/BAT) green/yellow and isolated changeover switch 1
LED 2 (BAT>85%) green and isolated changeover switch 3
LED 3 (Alarm) red and isolated changeover switch 2
LED 4 (BAT.FAULT) red and isolated changeover switch 2: Battery defective,
yellow: selected buffering time not assured, yellow flashing: Overtemperature
LED 5 (SF) green and LED 6 (RUN)
LED 7 (P1) green/yellow and LED 8 (P2) green/yellow, link and activity
Class B / Noise immunity to EN 61000-6-2
Class III (ext. circuit and power supply unit: SELV voltage to EN 60950 is required)
IP20
-25 ... +70 °C (derating from 60 °C)
-40 ... + 85 °C
50 x 125 x 125
0.4 kg without interface, 0.42 kg with USB,
0.45 kg with Ethernet/PROFINET interfaces
Snaps onto DIN rail DIN EN 50022-35x15/7.5
CE, cULus; available soon: CB, cCSAus Class I Div 2, ATEX, GL, ABS
Technical specifications
Battery modules
SITOP UPS1100 24 V/ 1.2 Ah
SITOP UPS1100 24 V/ 3.2 Ah
SITOP UPS1100 24 V/ 7Ah
For SITOP UPS1600
10 A
10 A and 20 A
10 A and 20 A
Order number
6EP4131-0GB00-0AY0
6EP4133-0GB00-0AY0
6EP4134-0GB00-0AY0
Recommended end of charge
voltage (set automatically by
­SITOP UPS1600):
26.4…27.3 V DC (> +20 °C), 27.3…29.0 V DC (< +20 °C)
Charging current
max. 0.36 A
Rated output voltage
24 V DC, 22 ... 27.0 V DC (no load)
Rated output current
Integral battery fuse
Signaling
LED green:
Battery OK
Flashing green:Error or warning,
off:
battery off, no communication
Degree of protection (EN 60529)
IP00
Ambient temperature
-10…+50 °C
Transport/storage temperature
-40…+85 °C
Service life (when capacity falls to
50% of original capacity), depen­
ding on battery temperature,
approx.
+20 °C: 4 years, +30°C: 2 years, +40 °C: 1 year, +50 °C: 0.5 years
Installation
Standard rail or wall mounting
Standard rail or wall mounting
Wall mounting
Dimensions (W x H x D) in mm
89 x 130 x 107
190 x 169 x 79,.5
186 x 186 x 110.5
Weight, approx.
1.9 kg
3.8 kg
6.1 kg
max. 0.96 A
max. 2.1 A
10 A
20 A
40 A
15 A
25 A
2 x 25 A
Certification
CE, cULus; available soon: CB, cCSAus Class I Div 2, ATEX, GL, ABS
Buffer times
at load current ...
1A
24.5 min
2.6 h
5.4 h
2A
15.,5 min
1h
2:6 h
3A
9 min
39.3 min
1.6 h
4A
6.5 min
27.1 min
1.2 h
6A
3.5 min
17.5 min
41 min
8A
2 min
12.1 min
28.6 min
10 A
1 min
9 min
21.8 min
12 A
–
7 min
17.3 min
14 A
–
5 min
15.1 min
16 A
–
4 min
12.5 min
20 A
–
1 min
9.1 min
Technical specifications apply for rated input voltage and +25°C ambient temperature (if not otherwise specified).
Determination of the buffering times is based on the discharge period of new and completely charged battery modules
until shutdown of the DC UPS.
SITOP UPS1600
5
...and system-integrated DC UPSV
Integration in TIA and TIA Portal
Control
SIMATIC S7-300/1500
(400/1200 available soon)
STEP 7
Human machine interface
Panel PC/ PC
SIMATIC HMI, WinCC
Engineering
PG/ PC, TIA Portal,
STEP 7
PC WinCC,
SCADA system
PROFINET
24 V DC
SITOP
power
supply
SITOP
UPS1600
SITOP
UPS1100
G_KT01_XX_00797
Energy Storage Link
Uninterruptible 24 V DC power supply
SITOP UPS1600 in Totally Integrated Automation:
Engineering takes place via the TIA Portal. If a power
failure occurs, the 24V DC buffer and the integration
of the DC UPS in PROFINET enables the PLCs to be
brought to a defined state independent of one another.
Function blocks for SIMATIC S7-300 and 1500 (400 and
1200 available soon) are available for this purpose. The
comprehensive diagnostic data of the power supply can
be visualized by various devices, for example, via
UPS faceplates.
Advantages of the SITOP UPS1600
through system integration
•Full integration in TIA saves time and money
in planning and operation
•Convenient engineering of SITOP DC UPS in the
TIA Portal
•Fast selection of products and network integration
in PROFINET
•Comprehensive device configuration
•Comprehensive diagnostic capabilities using the p
­ ower
supply statusg
•Easy integration in STEP 7 user programs with ­function
blocks for S7-300/1500 (400/1200 available soon),
free download
•Fast integration in the HMI with “UPS faceplates” for
SIMATIC Panels and SIMATIC WinCC (free download)
6
SITOP UPS1600
Engineering in the TIA Portal:
The integration of the DC UPS into PROFINET is simple and
reliable.
Engineering in the TIA Portal:
The UPS configuration is also extremely user-friendly,
because the configuration data of UPS1600 and UPS1100
are stored in the TIA Portal.
Faceplates for diagnostics in WinCC:
Monitoring is quickly provided with prefabricated SITOP
UPS1600 faceplates. All relevant operating data and
diagnostic data of the DC UPS and the battery can be seen
at a glance. Even alarm messages, such as missing buffer
readiness are generated without time-consuming programming.
SITOP UPS1600
7
Get more information
More information on SITOP DC UPS:
www.siemens.com/sitop-ups
Information material for download:
www.siemens.com/sitop-infomaterial
Using the SITOP Selection Tool to select the appropriate power
supply:
www.siemens.com/sitop-selection-tool
www.siemens.com/sitop/manuals
www.siemens.com/sitop/manuals
CAx data (2D, 3D, circuit diagram macro) as download:
www.siemens.com/sitop-cax
Electronic ordering via the Internet with the Industry Mall:
www.siemens.com/industrymall
Your personal contact partner is listed at:
www.siemens.com/automation/partner
Siemens Industry, Inc.
3333 Old Milton Parkway
Alpharetta, GA 30005
1-800-241-4453
[email protected]
www.usa.siemens.com/sitop
Subject to change without prior notice.
Article No.: 6ZB5341-0AQ02-0AA1
MP.R1.SC.0000.77.3.31 / Dispo 10001
BR 0913 2.0 SB 6 En
US Order No: PSBR-0AQ02-1113
All rights reserved.
Printed in USA
©2013 Siemens Industry, Inc.
Industrial Security
Siemens provides automation and drive products
with industrial security functions that support the
secure operation of plants or machines. They are an
important component in a holistic industrial security
concept. With this in mind, our products undergo
continuous development. We therefore recommend
that you keep yourself informed with respect to our
product updates. Please find further information
and newsletters on this subject at:
http://support.automation.siemens.com
To ensure the secure operation of a plant or machine
it is also necessary to take suitable preventive action
(e.g. cell protection concept) and to integrate the
automation and drive components into a state-of-theart holistic industrial security concept for the entire
plant or machine. Any third-party products that may
be in use must also be taken into account. Please find
further information at:
http://www.siemens.com/industrialsecurity
The information provided in this brochure contains merely general
descriptions or characteristics of performance which in case of actual use
do not always apply as described or which may change as a result of
further development of the products. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the terms
of contract. Availability and technical specifications are subject to
change without notice.
All product designations may be trademarks or product names
of Siemens AG or supplier companies whose use by third parties
for their own purposes could violate the rights of the owners.