DS III - 7MF4433, 7MF4434, 7MF4435, 7MF4533 for differential pressure and flow catalog specifications

© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for differential pressure and flow
■ Technical specifications
SITRANS P, DS III for differential pressure and flow
HART
PROFIBUS PA and FOUNDATION Fieldbus
Input
Measured variable
Spans (infinitely adjustable) or
nominal measuring range and
max. permissible operating pressure
Differential pressure and flow
Span (min. ... max.)
Maximum
operating
pressure
Nominal measuring range
Maximum
operating
pressure
1 ... 20 mbar (0.4 ... 8 inH2O)
32 bar
(464 psi)
20 mbar (8 inH2O)
32 bar
(464 psi)
1 ... 60 mbar (0.4 ... 24 inH2O)
160 bar
(2320 psi)
60 mbar (24 inH2O)
160 bar
(2320 psi)
2.5 ... 250 mbar (1 ... 100 inH2O)
250 mbar (100 inH2O)
6 ... 600 mbar (2.4 ... 240 inH2O)
600 mbar (240 inH2O)
16 ... 1600 mbar (6.4 ... 642 inH2O)
1600 mbar (642 inH2O)
50 ... 5000 mbar (20 ... 2000 inH2O)
5 bar (2000 inH2O)
0.3 ... 30 bar (4.35 ... 435 psi)
2.5 ... 250 mbar (1 ... 100 inH2O)
6 ... 600 mbar (2.4 ... 240 inH2O)
30 bar (435 psi)
420 bar
(6091 psi)
250 mbar (100 inH2O)
600 mbar (240 inH2O)
16 ... 1600 mbar (6.4 ... 642 inH2O)
1600 mbar (642 inH2O)
50 ... 5000 mbar (20 ... 2000 inH2O)
5 bar (2000 inH2O)
0.3 ... 30 bar (4.35 ... 435 psi)
30 bar (435 psi)
420 bar
(6091 psi)
Lower measuring limit
• Measuring cell with silicone oil filling
-100 % of max. span or 30 mbar a (0.44 psia) (-33 % with 30 bar (435 psi) measuring cell)
Upper measuring limit
100 % of max. span (for oxygen version and inert filling liquid; max. 120 bar (1740 psi))
Output
Output signal
4 ... 20 mA
Digital PROFIBUS PA and
FOUNDATION Fieldbus signal
• Lower limit (infinitely adjustable)
3.55 mA, factory preset to 3.84 mA
-
• Upper limit (infinitely adjustable)
23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA
Load
• Without HART
RB  (UH - 10.5 V)/0.023 A in ,
UH: Power supply in V
-
• With HART
RB = 230 ... 500  (SIMATIC PDM) or
RB = 230 ... 1100  (HART Communicator)
-
Physical bus
-
IEC 61158-2
Protection against polarity reversal
Protected against short-circuit and polarity reversal. Each connection against the other with max.
supply voltage.
Set to 2 s (0 ... 100 s)
Electrical damping (step width 0.1 s)
Acc. to IEC 60770-1
Measuring accuracy
Reference conditions
(All error data refer always refer to the set
span)
Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm,
silicone oil filling, room temperature 25 °C (77 °F)
Span ratio r = max. span/set span
Nominal measuring range ratio r = nominal
measuring range/set measuring range
Error in measurement at limit setting incl.
hysteresis and reproducibility
• Linear characteristic
- r  10
 (0.0029  r + 0.071) %
 (0.0029  r + 0.071) %
- 10 < r  30
 (0.0045  r + 0.071) %
 (0.0045  r + 0.071) %
- 30 < r  100
 (0.005  r + 0.05) %
 (0.005  r + 0.05) %
- r  10
 0.1 %
 0.1 %
- 10 < r  30
 0.2 %
 0.2 %
- r  10
 0.2 %
 0.2 %
- 10 < r  30
 0.4 %
 0.4 %
• Square-rooted characteristic (flow > 50 %)
• Square-rooted characteristic
(flow > 25 ... 50 %)
Siemens FI 01 · 2015 US Edition
1/137
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for differential pressure and flow
SITRANS P, DS III for differential pressure and flow
HART
PROFIBUS PA and FOUNDATION Fieldbus
Long-term stability
(temperature change ± 30 °C (± 54 °F))
• 250, 600, 1600 and 5000 mbar (0.29, 0.87,  (0.125  r) per 5 years
2.32 and 7.25 psi)-measuring cell
 (0.125  r) per 5 years
• 20 mbar (8 inH2O)-measuring cell
 (0.2  r) per year
 (0.2  r) per year
• 60 mbar (24 inH2O)-measuring cell
 (0.25  r) % per 5 years
 (0.25  r) % per 5 years
• 30 bar (435 psi)-measuring cell
 (0.25  r) % per 5 years
 (0.25  r) % per 5 years
• at -10 ... +60 °C (14 ... 140 °F)
 (0.08  r + 0.1) %1)
 (0.08  r + 0.1) %1)
• at -40 ... -10 °C and 60 ... 85 °C
(-40 ... +14 °F and 140 ... 185 °F)
 (0.1  r + 0.15) %/10 K
 (0.1  r + 0.15) %/10 K
 (0.15  r) % per 70 bar (1015 psi)
 (0.15  r) % per 70 bar (1015 psi)
 (0.15  r) % per 32 bar (464 psi)
 (0.15  r) % per 32 bar (464 psi)
 0.14 % per 70 bar (1015 psi)
 0.14 % per 70 bar (1015 psi)
 0.2 % per 32 bar (464 psi)
 0.2 % per 32 bar (464 psi)
-
3  10-5 of nominal measuring range
Influence of ambient temperature
(Twice the value with 20 mbar (8 inH2O)measuring cell
Influence of static pressure
• on the zero point (PKN)
- 20 mbar (0.29 psi)-measuring cell
• on the span (PKS)
- 20 mbar (0.29 psi)-measuring cell
Measured Value Resolution
Rated conditions
Degree of protection (to EN 60529)
IP66 (optional IP66/IP68), NEMA 4X
Temperature of medium
• Measuring cell with silicone oil filling
-40 ... +100 °C (-40 ... +212 °F) -20 ... +100 °C (-4 ... +212 °F) with 30 bar measuring cell
• Measuring cell with inert filling liquid
-20 ... +100 °C (-4 ... +212 °F)
• In conjunction with dust explosion protection
-20 ... +60 °C (-4 ... +140 °F)
Ambient conditions
• Ambient temperature
- Transmitter
(with 4-wire connection, observe temperature values of supplementary 4-wire electronics)
-40 ... +85 °C (-40 ... +185 °F)
- Display readable
-30 ... +85 °C (-22 ... +185 °F)
• Storage temperature
-50 ... +85 °C (-58 ... +185 °F)
• Climatic class
- Condensation
Relative humidity 0 ... 100 %
Condensation permissible, suitable for use in the tropics
• Electromagnetic Compatibility
- Emitted interference and interference
immunity
Acc. to IEC 61326 and NAMUR NE 21
Design
Weight (without options)
Enclosure material
Die-cast aluminum:  4.5 kg ( 9.9 lb)
Stainless steel precision casting:  7.1 kg ( 15.6 lb)
Low-copper die-cast aluminum, GD-AlSi12 or stainless steel precision casting, mat. no. 1.4408
Wetted parts materials
• Seal diaphragm
Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819, Monel, mat. no. 2.4360, tantalum or gold
Measuring cell filling
Silicone oil or inert filling liquid
(maximum value with oxygen measurement pressure 100 bar (1450 psi) at 60 °C (140 °F))
Process connection
Female thread ¼-18 NPT and flange connection with mounting thread M10 to DIN 19213 or
7/ -20 UNF to IEC 61518
16
Material of mounting bracket
• Steel
Sheet-steel, Mat. No. 1.0330, chrome-plated
• Stainless steel
1/138
Siemens FI 01 · 2015 US Edition
Sheet stainless steel, mat. no. 1.4301 (SS 304)
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for differential pressure and flow
SITRANS P, DS III for differential pressure and flow
HART
PROFIBUS PA and FOUNDATION Fieldbus
Supplied through bus
Power supply UH
Terminal voltage on transmitter
10.5 ... 45 V DC
10.5 ... 30 V DC in intrinsically-safe mode
-
Separate 24 V power supply necessary
-
No
• Not Ex
-
9 ... 32 V
• With intrinsically-safe operation
-
9 ... 24 V
Bus voltage
Current consumption
• Basic current (max.)
-
12.5 mA
• Start-up current  basic current
-
Yes
• Max. current in event of fault
-
15.5 mA
Fault disconnection electronics (FDE) available
-
Yes
Certificates and approvals
Classification according to PED 97/23/EC
PN 32/160 (MAWP 464/2320 psi)
PN 420 (MAWP 6092 psi)
For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3,
paragraph 3 (sound engineering practice)
For gases of fluid group 1 and liquids of fluid group 1; complies with basic safety requirements of
Article 3, paragraph 1 (appendix 1); assigned to category III, conformity evaluation module H by the
TÜV Nord.
Explosion protection
• Intrinsic safety "i"
PTB 13 ATEX 2007 X
- Marking
Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb
- Permissible ambient temperature
- Connection
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +70 °C (-40 ... +158 °F) temperature class T5;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
To certified intrinsically-safe circuits with peak val- FISCO supply unit:
ues:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300  Linear barrier:
Uo = 24 V, Io = 250 mA, Po = 1.2 W
L i = 7 H, Ci = 1.1 nF
- Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF
• Explosion-proof "d"
PTB 99 ATEX 1160
- Marking
Ex II 1/2 G Ex d IIC T4/T6 Gb
-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6
- Permissible ambient temperature
- Connection
To circuits with values: UH = 10.5 ... 45 V DC
- Marking
Ex II 1 D IP65 T 120 °C
Ex II 1/2 D IP65 T 120 °C
- Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
- Max. surface temperature
- Connection
120 °C (248 °F)
To certified intrinsically-safe circuits with peak values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW, Ri = 300 
- Marking
- Connection
FISCO supply unit:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W
Linear barrier:
Uo = 24 V, Io = 250 mA, Po = 1 W
L i = 7 H, Ci = 1.1 nF
- Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF
• Dust explosion protection for zone 21/22
To circuits with values: UH = 9 ... 32 V DC
PTB 01 ATEX 2055
• Dust explosion protection for zone 20
PTB 01 ATEX 2055
Ex II 2 D IP65 T 120 °C
To circuits with values: UH = 10.5 ... 45 V DC;
Pmax = 1.2 W
To circuits with values: UH = 9 ... 32 V DC;
Pmax = 1 W
Siemens FI 01 · 2015 US Edition
1/139
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for differential pressure and flow
SITRANS P, DS III for differential pressure and flow
HART
• Type of protection "n" (zone 2)
Ex II 2/3 G Ex nA IIC T4/T5/T6 Gc
Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc
- Marking
- Connection (Ex nA)
Um = 45 V
Um = 32 V
- Connection (Ex ic)
To circuits with values:
Ui = 45 V
FISCO supply unit ic:
Uo = 17.5 V, Io = 570 mA
Linear barrier:
Uo = 32 V, Io = 132 mA, Po = 1 W
- Effective internal inductance/capacitance L i = 0.4 mH, Ci = 6 nF
• Explosion protection acc. to FM
- Identification (XP/DIP) or (IS); (NI)
• Explosion protection to CSA
- Identification (XP/DIP) or (IS)
1)
PROFIBUS PA and FOUNDATION Fieldbus
PTB 13 ATEX 2007 X
L i = 7 H, Ci = 1.1 nF
Certificate of Compliance 3008490
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6;
CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III
Certificate of Compliance 1153651
CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD
T4...T6; CL II, DIV 2, GP FG; CL III
Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.064 . r + 0.08) % / 28 °C (50 °F).
1/140
Siemens FI 01 · 2015 US Edition
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for differential pressure and flow
HART communication
HART
230 ... 1100 
Protocol
HART Version 5.x
Software for PC
SIMATIC PDM
PROFIBUS PA communication
Simultaneous communication with
master class 2 (max.)
4
The address can be set using
Configuration tool or local operation (standard setting
address 126)
Cyclic data usage
• Output byte
5 (one measured value) or
10 (two measured values)
• Input byte
0, 1, or 2 (register operating
mode and reset function for
metering)
Internal preprocessing
FOUNDATION Fieldbus
communication
Function blocks
3 function blocks analog input,
1 function block PID
• Analog input
- Adaptation to customerspecific process variables
Yes, linearly rising or falling
characteristic
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Output/input (can be locked
within the device with a bridge)
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
- Square-rooted characteristic
for flow measurement
Yes
Device profile
PROFIBUS PA Profile for Process Control Devices Version
3.0, class B
• PID
Standard FOUNDATION Fieldbus function block
• Physical block
1 resource block
Function blocks
2
Transducer blocks
- Adaptation to customer-specific process variables
Yes, linearly rising or falling
characteristic
1 transducer block Pressure with
calibration, 1 transducer block
LCD
• Pressure transducer block
- Electrical damping, adjustable
0 ... 100 s
- Simulation function
Input /Output
- Failure mode
parameterizable (last good
value, substitute value, incorrect
value)
- Limit monitoring
Yes, one upper and lower warning limit and one alarm limit
respectively
• Register (totalizer)
Can be reset, preset, optional
direction of counting, simulation
function of register output
• Analog input
- Failure mode
parameterizable (summation
with last good value, continuous
summation, summation with
incorrect value)
- Limit monitoring
One upper and lower warning
limit and one alarm limit respectively
• Physical block
1
Transducer blocks
2
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Simulation function: Measured
pressure value, sensor temperature and electronics temperature
Constant value or over parameterizable ramp function
• Pressure transducer block
- Can be calibrated by applying
two pressures
Yes
- Monitoring of sensor limits
Yes
- Specification of a container
characteristic with
Max. 30 nodes
- Square-rooted characteristic
for flow measurement
Yes
- Gradual volume suppression
and implementation point of
square-root extraction
Parameterizable
- Simulation function for measured pressure value and sensor temperature
Constant value or over parameterizable ramp function
Siemens FI 01 · 2015 US Edition
1/141
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for differential pressure and flow
Selection and Ordering data
Article No.
Selection and Ordering data
Article No.
SITRANS P DS III with HART pressure transmitters for differential pressure and flow,
PN 32/160 (MAWP 464/2320 psi)
7MF 4 4 3 3 -
SITRANS P DS III with HART pressure transmitters for differential pressure and flow,
PN 32/160 (MAWP 464/2320 psi)
7MF 4 4 3 3 -
77777 - 7777
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling Measuring cell cleaning
Silicone oil
normal
Inert liquid1)
grease-free to
cleanliness level 2
Electrical connection/cable entry
• Screwed gland Pg 13.513)
• Screwed gland M20 x 1.5
• Screwed gland ½-14 NPT
• Han 7D plug (plastic housing) incl. mating
connector13)14)
• M12 connectors (stainless steel)15)16)
1
3
Measuring span (min. ... max.)
PN 32 (MAWP 464 psi)
1 ... 20 mbar2)
(0.4015 ... 8.03 inH2O)
B
PN 160 (MAWP 2320 psi)
1 ... 60 mbar
(0.4015 ... 24.09 inH2O)
2.5 ... 250 mbar
(1.004 ... 100.4 inH2O)
6 ... 600 mbar
(2.409 ... 240.9 inH2O)
16 ... 1600 mbar
(6.424 ... 642.4 inH2O)
50 ... 5000 mbar
(20.08 ... 2008 inH2O)
0.3 ... 30 bar
(4.35 ... 435 psi)
C
D
E
F
G
H
Process connection
Female thread ¼-18 NPT with flange connection
• Sealing screw opposite process connection
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M10 to DIN 19213
(only for replacement requirement)
• Vent on side of process flange 2)
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M10 to DIN 19213
(only for replacement requirement)
Die-cast aluminum
Stainless steel precision
casting8)
Version
• Standard versions
• International version, English label inscriptions, documentation in 5 languages on CD
(no Order code selectable)
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"9)
- "Intrinsic safety and flameproof enclosure"
(Ex ia + Ex d)"10)
- "Ex nA/ic (Zone 2)"11)
- "Intrinsic safety, explosion-proof enclosure
and dust explosion protection (Ex ia+ Ex d +
Zone 1D/2D)"10)12)
• FM + CSA intrinsic safe (is)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX)12)
• With FM + CSA, Type of protection:
- "Intrinsic Safe und Explosion Proof (is + xp)"9)
1/142
Siemens FI 01 · 2015 US Edition
F
0
1
6
7
Power supply units see Chap. 7 "Supplementary Components".
Included in delivery of the device:
• Brief instructions (Leporello)
• CD-ROM with detailed documentation
• Sealing plug(s) or sealing screw(s) for the process flanges(s)
A
B
C
E
H
L
Y
2
0
6
4
Non-wetted parts materials
process flange screws Electronics housing
Stainless steel
Stainless steel
A
B
C
D
Display
• Without display
• Without visible display
(display concealed, setting: mA)
• With visible display (setting: mA)
• with customer-specific display
(setting as specified, Order code "Y21" or "Y22"
required)
Wetted parts materials
(stainless steel process flanges)
Seal diaphragm
Parts of measuring cell
Stainless steel
Stainless steel
Hastelloy
Stainless steel
Hastelloy
Hastelloy
Tantalum3)
Tantalum
Monel3)
Monel
Gold3)
Gold
Version for diaphragm seal4) 5) 6) 7)
77777 - 7777
1)
For oxygen application, add Order code E10.
2)
Not suitable for connection of remote seal. Position of the top vent valve in
the process flange (see dimensional drawing).
3)
Not in conjunction with max. span 20 and 60 mbar (8.03 und 24.09 inH2O))
4)
When the manufacture’s certificate (calibration certificate) has to be
ordered for transmitters with diaphragm seals according to IEC 60770-2, it
is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified
here.
5)
If the acceptance test certificate 3.1.is ordered for the transmitter with
mounted diaphragm seals this certificate must also be ordered with the
respective remote seals.
6)
The diaphragm seal is to be specified with a separate order number and
must be included wiht the tranmitter order number, for example
7MF443.-..Y..-.... und 7MF4900-1...-.B
7)
The standard measuring cell filling for configurations with remote seals (Y)
is silicone oil.
8)
Not in conjunction with Electrical connection "Screwed gland Pg 13.5" and
"Han7D plug".
9)
Without cable gland, with blanking plug
10) With
enclosed cable gland Ex ia and blanking plug
11) Configurations
2
3
in connection with IP65.
13) Only
in connection with Ex approval A, B or E.
14) Permissible
1
2
A
B
D
P
E
R
F
S
NC
with HAN and M12 connectors are only available in Ex ic.
12) Only
only for crimp-contact of conductor cross-section 1 mm2
15) Only
in connection with Ex approval A, B, E or F.
16) M12
delivered without cable socket.
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for differential pressure and flow
Selection and Ordering data
Article No.
Selection and Ordering data
Pressure transmitters for differential pressure
and flow PN 32/160 (MAWP 464/2320 psi)
SITRANS P DS III with PROFIBUS PA (PA)
SITRANS P DS III with FOUNDATION Fieldbus (FF)
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Inert liquid1)
Measuring cell
cleaning
normal
grease-free to
cleanliness level 2
Pressure transmitters for differential pressure
and flow PN 32/160 (MAWP 464/2320 psi)
7MF 4 4 3 4 -
SITRANS P DS III with PROFIBUS PA (PA)
7MF 4 4 3 5 -
SITRANS P DS III with FOUNDATION Fieldbus (FF)
77777 - 7777
1
3
B
PN 160 (MAWP 2320 psi)
60 mbar
(24.09 inH2O)
250 mbar
(100.4 inH2O)
600 mbar
(240.9 inH2O)
1600 mbar
(642.4 inH2O)
5 bar
(2008 inH2O)
30 bar
(435 psi)
C
D
E
F
G
H
- Mounting thread M10 to DIN 19213
(only for replacement requirement)
7MF 4 4 3 5 77777 - 7777
Display
• Without display
• Without visible display
(display concealed, setting: bar)
• With visible display (setting: bar)
• With customer-specific display
(setting as specified, Order code "Y21" required)
B
C
F
0
1
6
7
Included in delivery of the device:
• Brief instructions (Leporello)
• CD-ROM with detailed documentation
• Sealing plug(s) or sealing screw(s) for the process flanges(s)
Wetted parts materials
(stainless steel process flanges)
Seal diaphragm
Parts of measuring cell
Process connection
Female thread ¼-18 NPT with flange connection
• Sealing screw opposite process connection
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M10 to DIN 19213
(only for replacement requirement)
• Venting on side of process flanges2)
- Mounting thread 7/16-20 UNF to IEC 61518
7MF 4 4 3 4 -
Electrical connection/cable entry
• Screwed gland M20 x 1.5
• Screwed gland ½-14 NPT
• M12 connectors (stainless steel)12) 13)
Nominal measuring range
PN 32 (MAWP 464 psi)
20 mbar 2)
(8.03 inH2O)
Stainless steel
Stainless steel
Hastelloy
Stainless steel
Hastelloy
Hastelloy
Tantalum 3)
Tantalum
Monel3)
Monel
Gold 3)
Gold
Version as diaphragm seal 4) 5) 6) 7)
Article No.
A
B
C
E
H
L
Y
2
0
6
4
1)
For oxygen application, add Order code E10.
2)
Not suitable for connection of remote seal. Position of the top vent valve in
the process flange (see dimensional drawing).
3)
Not in conjunction with max. span 20 and 60 mbar (8.03 und 24.09 inH2O))
4)
When the manufacture’s certificate (calibration certificate) has to be
ordered for transmitters with diaphragm seals according to IEC 60770-2, it
is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified
here.
5)
If the acceptance test certificate 3.1.is ordered for the transmitter with
mounted diaphragm seals this certificate must also be ordered with the
respective remote seals.
6)
The diaphragm seal is to be specified with a separate order number and
must be included wiht the tranmitter order number, for example
7MF443.-..Y..-.... und 7MF4900-1...-.B
7)
The standard measuring cell filling for configurations with remote seals (Y)
is silicone oil.
8)
Without cable gland, with blanking plug.
9)
With enclosed cable gland Ex ia and blanking plug.
10)
Configurations with HAN and M12 connectors are only available in Ex ic.
11)
Only in connection with IP65.
12)
Only in connection with Ex approval A, B, E or F.
13)
M12 delivered without cable socket
Non-wetted parts materials
process flange screws Electronics housing
Stainless steel
Stainless steel
Die-cast aluminum
Stainless steel precision
casting
Version
• Standard versions
• International version, English label inscriptions,
documentation in 5 languages on CD
(no Order code selectable)
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"8)
- "Intrinsic safety and flameproof enclosure"
(Ex ia + Ex d)"9)
- "Ex nA/ic (Zone 2)" 10)
- "Intrinsic safety, explosion-proof enclosure and
dust explosion protection (Ex ia + Ex d +
Zone 1D/2D)"9) 11)(not for DS III FF)
• FM + CSA intrinsic safe (is)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX)11)
• With FM + CSA, Type of protection:
- "Intrinsic Safe und Explosion Proof (is + xp)"8)
2
3
1
2
A
B
D
P
E
R
F
S
NC
Siemens FI 01 · 2015 US Edition
1/143
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for differential pressure and flow
Selection and Ordering data
Order code
Further designs
Add "-Z" to Article No. and specify Order
code.
Pressure transmitter with mounting
bracket (1x fixing angle, 2 x nut, 2 x Uwasher or 1 x bracket, 2 x nut, 2 x Uwasher) made of:
• Steel
• Stainless steel
O-rings for process flanges
(instead of FPM (Viton))
• PTFE (Teflon)
• FEP (with silicone core, approved for food)
• FFPM (Kalrez, compound 4079),
for measured medium temperatures
-15 ... 100 °C (5 ... 212 °F)
• NBR (Buna N)
Selection and Ordering data
HART PA
A01
A02




FF


A20
A21
A22









A23



A30
A31
A32
A33




Sealing screws (2 units)
¼-18 NPT, with valve in mat. of process
flanges
A40



Cable sockets for M12 connectors
(metal (CuZn))
A50



B11
B12
B13
B14
B16















English rating plate
Pressure units in inH2O and/or psi
B21



Quality inspection certificate (Five-step
factory calibration) to IEC 60770-21)
C11



Inspection certificate2) to EN 10204-3.1
C12



Factory certificate to EN 10204-2.2
C14



Functional safety (SIL2)
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL
conformity declaration
C20

Functional safety (PROFIsafe)
Certificate and PROFIsafe protocol
C213)
Functional safety (SIL2/3)
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL
conformity declaration
C23
Device passport Russia
(For price request please contact the technical support
www.siemens.com/automation/supportrequest)
C99
plug
• Han 7D (metal)
• Han 8D (instead of Han 7D)
• Angled
• Han 8D (metal)
Rating plate inscription
(instead of German)
• English
• French
• Spanish
• Italian
• Cyrillic (russian)
1/144
Siemens FI 01 · 2015 US Edition





Order code
Further designs
Add "-Z" to Article No. and specify Order
code.
HART PA
FF
Setting of upper limit of
output signal to 22.0 mA
D05

Manufacturer's declaration acc. to NACE
(MR 0103-2012 and MR 0175-2009)
(only together with seal diaphragm made of
Hastelloy and stainless steel)
D07



Degree of protection IP66/IP68
(only for M20 x 1.5 and ½-14 NPT)
D12



Process flange screws made of Monel
(max. nominal pressure PN20)
D34



Supplied with oval flange set
(2 items), PTFE packings and screws in
thread of process flanges
D37



Capri cable gland 4F CrNi and clamping
device (848699 + 810634) included
D59



Use in or on zone 1D/2D
(only together with type of protection
"Intrinsic safety" (transmitter
7MF4...-.....-.B.. Ex ia)“and IP65)
E01



Overfilling safety device for flammable
and non-flammable liquids
(max. PN 32 (MAWP 464 psi), basic device
with type of protection "Intrinsic safety
(Ex ia)", to WHG and VbF, not together with
measuring cell filling "inert liquid")
E08

Oxygen application
(In the case of oxygen measurement and
inert liquid max. 100 bar (1450 psi) at 60°C
(140 °F))
E10



Export approval Korea
E11



CRN approval Canada
(Canadian Registration Number)
E22



Dual seal
E24



Explosion-proof "Intrinsic safety" (Ex ia)
to INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.B..)
E254)



"Flameproof" explosion protection
according to INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.D..)
E264)



Explosion-proof "Intrinsic safety" (Ex ia
+ Ex d) to INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.P..)
E284)


Ex Approval IEC Ex (Ex ia)
(only for transmitter 7MF4...-.....-.B..)
E454)



Ex Approval IEC Ex (Ex d)
(only for transmitter 7MF4...-.....-.D..)
E464)



Explosion-proof "Intrinsic safety" to
NEPSI (China)
(only for transmitter 7MF4...-.....-.B..)
E554)



Explosion protection "Explosion-proof"
to NEPSI (China)
(only for transmitter 7MF4...-.....-.D..)
E564)



Explosion-proof "Zone 2" to NEPSI
(China)
(only for transmitter 7MF4...-.....-.E..)
E574)



Ex protection „Ex ia“, „Ex d“ and „Zone
2“ to NEPSI (China)
(only for transmitter 7MF4...-.....-.R..)
E584)



"Intrinsic safety" and "Explosion-proof"
explosion protection acc. to Kosha (Korea)
(only for transmitter
7MF4...-.....-.[B, D]..-Z + E11)
E704)



© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for differential pressure and flow
Selection and Ordering data
Order code
Further designs
Add "-Z" to Article No. and specify Order
code.
Selection and Ordering data
HART PA
FF
Additional data
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
Measuring range to be set
Specify in plain text:
• in the case of linear characteristic curve
(max. 5 characters):
Y01: ... up to ... mbar, bar, kPa, MPa, psi
• in the case of square rooted characteristic
(max. 5 characters):
Y02: ... up to ... mbar, bar, kPa, MPa, psi
Two coats of lacquer on casing and
cover (PU on epoxy)
G10



Interchanging of process connection
side
H01



Vent on side for gas measurements
H02



Stainless steel process flanges for vertical differential pressure lines
(not together with K01, K02 and K04)5)
H03



Transient protector 6 kV (lightning protection)
J01



Chambered graphite gasket for process
flange
J02



Chambered PTFE graphite gasket
J03



EPDM O-rings for process flange with
approval (WRC/WRAS)
J05



Vent valve or blanking plug of process
flange welded-in (orientation: on right
when viewing the display)6)
J08



Vent valve or blanking plug of process
flange welded-in (orientation: on left
when viewing the display)6)
J09



K01
K02
K04









Process flange
• Hastelloy
• Monel
• Stainless steel with PVDF insert
max. PN 10 (MAWP 145 psi),
max. temperature of medium 90 °C
(194 °F)
For ½-14 NPT inner process connection
on the side in the middle of the process
flange, vent valve not possible
Factory mounting of valve manifolds, see accessories.
Supplementary electronics for 4-wire connection, see accessories.
 = available
1)
2)
When the manufacture’s certificate (calibration certificate) has to be ordered
for transmitters with diaphragm seals according to IEC 60770-2, it is recommended only to order this certificate exclusively with the diaphragm seals. The
measuring accuracy of the total combination is certified here.
If the acceptance test certificate 3.1.is ordered for the transmitter with
mounted diaphragm seals this certificate must also be ordered with the
respective remote seals.
Order code
HART PA
FF
1)
Y01

Y02

Stainless steel tag plate and entry in
device variable (measuring point
description)
Max. 16 characters, specify in plain text:
Y15: ...........................................
Y15



Measuring point text (entry in device
variable)
Max. 27 char., specify in plain text: Y16:
.......
Y16



Entry of HART address (TAG)
Max. 8 char., specify in plain text: Y17: .......
Y17

Setting of pressure indicator in
pressure units
Specify in plain text (standard setting: bar):
Y21: mbar, bar, kPa, MPa, psi, ...
Note: The following pressure units can be
selected:
bar, mbar, mm H2O*), inH2O*), ftH2O*),
mmHG, inHG, psi, Pa, kPa, MPa, g/cm2,
kg/cm2, Torr, ATM or %
*) ref. temperature 20 °C
Y21



Setting of pressure indicator in nonpressure units2)
Specify in plain text:
Y22: ..... up to ..... l/min, m3/h, m, USgpm, ...
(specification of measuring range in pressure units "Y01" or "Y02" is essential, unit
with max. 5 characters)
Y223)
+
Y01 or
Y02

Preset bus address
possible between 1 and 126
Specify in plain text: Y25: .....................
Y25


Damping adjustment in seconds
(0 ... 100 s)
Y30



Factory mounting of valve manifolds, see accessories.
Only Y01, Y15, Y16, Y17, Y21, Y22, Y25 und D05 can be factory preset
3)
Profisafe transmitters can only be operated with the S7 F Systems V6.1 configuration software in combination with S7-400H
 = available
4)
Option does not include ATEX approval, but instead includes only the countryspecific approval.
1)
5)
Not suitable for connection of remote seal.
6)
Blanking plug is standard configuration. Order option A40 if a vent valve is
required instead of a blanking plug.
Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are
calculated in the same way as for HART devices.
2)
Preset values can only be changed over SIMATIC PDM.
3)
Not in conjunction with over-filling safety device for flammable and nonflammable liquids (Order code "E08")
Siemens FI 01 · 2015 US Edition
1/145
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for differential pressure and flow
Selection and Ordering data
Article No.
Selection and Ordering data
Article No.
SITRANS P DS III with HART pressure transmitters for differential pressure and flow,
PN 420 (MAWP 6092 psi)
7MF 4 5 3 3 -
SITRANS P DS III with HART pressure transmitters for differential pressure and flow,
PN 420 (MAWP 6092 psi)
7MF 4 5 3 3 -
77777 - 7777
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Measuring cell filling
Silicone oil
Measuring cell
cleaning
normal
Measuring span (min. ... max.)
2.5 ... 250 mbar
(1.004 ... 100.4 inH2O)
6 ... 600 mbar
(2.409 ... 240.9 inH2O)
16 ... 1600 mbar
(6.424 ... 642.4 inH2O)
50 ... 5000 mbar
(20.08 ... 2008 inH2O)
0.3 ... 30 bar
(4.35 ... 435 psi)
Display
• Without display
• Without visible display
(display concealed, setting: mA)
• With visible display (setting: mA)
• with customer-specific display
(setting as specified, Order code "Y21" or "Y22"
required)
1
D
E
F
G
H
Process connection
Female thread ¼-18 NPT with flange connection
• Sealing screw opposite process connection
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M12 to DIN 19213
(only for replacement requirement)
• Venting on side of process flanges, location of
vent valve at top of process flanges (see dimensional drawing)
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M12 to DIN 19213
(only for replacement requirement)
Die-cast aluminum
Stainless steel precision
casting6)
Version
• Standard versions
• International version, English label inscriptions,
documentation in 5 languages on CD
(no Order code selectable)
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"7)
- "Intrinsic safety and flameproof enclosure"
(Ex ia + Ex d)"8)
- "Ex nA/ic (Zone 2)"9)
- "Intrinsic safety, explosion-proof enclosure and
dust explosion protection (Ex ia+ Ex d +
Zone 1D/2D)"8)10)
• FM + CSA intrinsic safe (is)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX)10)
• With FM + CSA, Type of protection:
- "Intrinsic safety and explosion-proof
(is + xp)" 7), max PN 360
Electrical connection/cable entry
• Screwed gland Pg 13.511)
• Screwed gland M20x1.5
• Screwed gland ½-14 NPT
• Han 7D plug (plastic housing) incl. mating
connector11)12)
• M12 connectors (stainless steel)13) 14)
1/146
Siemens FI 01 · 2015 US Edition
6
7
Scope of delivery: Pressure transmitter as ordered (Instruction Manual is
extra ordering item)
A
B
L
Y
3
1
7
5
1)
Not in conjunction with max. span 600 mbar (240.9 inH2O)
2)
When the manufacture’s certificate (calibration certificate) has to be
ordered for transmitters with diaphragm seals according to IEC 60770-2, it
is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified
here.
3)
If the acceptance test certificate 3.1.is ordered for the transmitter with
mounted diaphragm seals this certificate must also be ordered with the
respective remote seals.
4)
The diaphragm seal is to be specified with a separate order number and
must be included wiht the tranmitter order number, for example
7MF453.-..Y..-.... und 7MF4900-1....-.B
5)
The standard measuring cell filling for configurations with remote seals (Y)
is silicone oil.
6)
Not in conjunction with Electrical connection "Screwed gland Pg 13.5" and
"Han7D plug".
7)
Without cable gland, with blanking plug
8)
With enclosed cable gland Ex ia and blanking plug
9)
Configurations with HAN and M12 connectors are only available in Ex ic.
10) Only
in connection with IP65.
11) Only
in connection with Ex approval A, B or E.
12) Permissible
Non-wetted parts materials
process flange screws Electronics housing
Stainless steel
Stainless steel
0
1
Power supply units see Chap. 7 "Supplementary Components".
Wetted parts materials
(stainless steel process flanges)
Seal diaphragm
Parts of measuring cell
Stainless steel
Stainless steel
Hastelloy
Stainless steel
Gold1)
Gold
Ausführung als Membrandruckmittler 2) 3) 4) 5)
77777 - 7777
2
3
1
2
A
B
D
P
E
R
F
S
NC
A
B
C
D
F
only for crimp-contact of conductor cross-section 1 mm2
13) Only
in connection with Ex approval A, B, E or F.
14) M12
delivered without cable socket.
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for differential pressure and flow
Selection and Ordering data
Article No.
Selection and Ordering data
Pressure transmitters for differential pressure
and flow, PN 420 (MAWP 6092 psi)
Article No.
Pressure transmitters for differential pressure
and flow, PN 420 (MAWP 6092 psi)
SITRANS P DS III with PROFIBUS PA (PA)
7MF 4 5 3 4 -
SITRANS P DS III with PROFIBUS PA (PA)
7MF 4 5 3 4 -
SITRANS P DS III with FOUNDATION Fieldbus (FF)
7MF 4 5 3 5 -
SITRANS P DS III with FOUNDATION Fieldbus (FF)
7MF 4 5 3 5 -
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Nominal measuring range
250 mbar
(100.4 inH2O)
600 mbar
(240.9 inH2O)
1600 mbar
(642.4 inH2O)
5 bar
(2008 inH2O)
30 bar
(435 psi)
1 7777 - 7777
D
E
F
G
H
Process connection
Female thread ¼-18 NPT with flange connection
• Sealing screw opposite process connection
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M12 to DIN 19213
(only for replacement requirement)
• Venting on side of process flanges, location of
vent valve at top of process flanges (see dimensional drawing).
- Mounting thread 7/16-20 UNF to IEC 61518
- Mounting thread M12 to DIN 19213
(only for replacement requirement)
A
B
L
Y
3
1
7
5
Non-wetted parts materials
Process flange screws Electronics housing
Stainless steel
Stainless steel
Die-cast aluminum
Stainless steel precision
casting
Version
• Standard versions
• International version, English label inscriptions,
documentation in 5 languages on CD
(no Order code selectable)
Explosion protection
• None
• With ATEX, Type of protection:
- "Intrinsic safety (Ex ia)"
- "Explosion-proof (Ex d)"6)
- "Intrinsic safety and flameproof enclosure"
(Ex ia + Ex d)"7)
- "Ex nA/ic (Zone 2)" 8)
- "Intrinsic safety, explosion-proof enclosure and
dust explosion protection (Ex ia + Ex d +
Zone 1D/2D)"7) 9) (not for DS III FF)
• FM + CSA intrinsic safe (is)
• FM + CSA (is + ep) + Ex ia + Ex d (ATEX)9)
• With FM + CSA, Type of protection:
- "Intrinsic safety and explosion-proof
(is + xp)"6), max PN 360
Electrical connection/cable entry
• Screwed gland M20 x 1.5
• Screwed gland ½-14 NPT
• M12 connectors (stainless steel) 10) 11)
0
1
6
7
Included in delivery of the device:
• Brief instructions (Leporello)
• CD-ROM with detailed documentation
• Sealing plug(s) or sealing screw(s) for the process flanges(s)
Wetted parts materials
(stainless steel process flanges)
Seal diaphragm
Parts of measuring cell
Stainless steel
Stainless steel
Hastelloy
Stainless steel
Gold 1)
Gold
Ausführung als Membrandruckmittler 2) 3) 4) 5)
1 7777 - 7777
Display
• Without (display hidden)
• Without visible display
(display concealed, setting: bar)
• With visible display (setting: bar)
• With customer-specific display (setting as
specified, Order code "Y21" required)
2
3
1)
Not in conjunction with max. span 600 mbar (240.9 inH2O)
2)
When the manufacture’s certificate (calibration certificate) has to be
ordered for transmitters with diaphragm seals according to IEC 60770-2, it
is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified
here.
3)
If the acceptance test certificate 3.1.is ordered for the transmitter with
mounted diaphragm seals this certificate must also be ordered with the
respective remote seals.
4)
The diaphragm seal is to be specified with a separate order number and
must be included wiht the tranmitter order number, for example
7MF453.-..Y..-.... und 7MF4900-1....-.B
5)
The standard measuring cell filling for configurations with remote seals (Y)
is silicone oil.
6)
Without cable gland, with blanking plug.
7)
With enclosed cable gland Ex ia and blanking plug.
8)
Configurations with HAN and M12 connectors are only available in Ex ic.
9)
Only in connection with IP65.
10)
Only in connection with Ex approval A, B, E or F.
11)
M12 delivered without cable socket
1
2
A
B
D
P
E
R
F
S
NC
B
C
F
Siemens FI 01 · 2015 US Edition
1/147
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
1
SITRANS P DS III for differential pressure and flow
Selection and Ordering data
Order code
Further designs
Add "-Z" to Article No. and specify Order code.
Pressure transmitter with mounting
bracket (1x fixing angle, 2 x nut, 2 x Uwasher or 1 x bracket, 2 x nut, 2 x Uwasher) made of:
• Steel
• Stainless steel
O-rings for process flanges
(instead of FPM (Viton))
• PTFE (Teflon)
• FEP (with silicone core, approved for food)
• FFPM (Kalrez, compound 4079),
for measured medium temperatures
-15 ... 100 °C (5 ... 212 °F)
• NBR (Buna N)
Selection and Ordering data
HART PA
A01
A02




FF


A20
A21
A22









A23



A30
A31
A32
A33




Sealing screws (2 units)
A40
¼-18 NPT, with valve in mat. of process flanges



Cable sockets for M12 connection
(metal (CuZn))



Plug
• Han 7D (metal)
• Han 8D (instead of Han 7D)
• Angled
• Han 8D (metal)
Rating plate inscription (instead of German)
• English
• French
• Spanish
• Italian
• Cyrillic (russian)
A50
B11
B12
B13
B14
B16















English rating plate
Pressure units in inH2O and/or psi
B21



Quality inspection certificate (Five-step
factory calibration) to IEC 60770-2
C11



Inspection certificate
Acc. to EN 10204-3.1
C12



Factory certificate
Acc. to EN 10204-2.2
C14



Functional safety (SIL2)
C20
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL conformity declaration
Functional safety (PROFIsafe)
Certificate and PROFIsafe protocol

C211)

Functional safety (SIL2/3)
C23
Devices suitable for use according to
IEC 61508 and IEC 61511. Includes SIL conformity declaration

Device passport Russia (For price request
please contact the technical support
www.siemens.com/automation/supportrequest)
C99

Setting of upper limit of output signal to
22.0 mA
D05

Manufacturer's declaration acc. to NACE
(MR 0103-2012 and MR 0175-2009)
(only together with seal diaphragm made of
Hastelloy and stainless steel)
D07



Degree of protection IP66/IP68
(only for M20 x 1.5 and ½-14 NPT)
D12



Nom. press. rating PN 500 (MAWP 7250 psi) D56
(Only for measuring cell 600 mbar ... 30 bar
(240 inH2O ... 435 psi), SIL- und Ex-options
not possible))2)

Capri cable gland 4F CrNi and clamping
device (848699 + 810634) included



1/148
Siemens FI 01 · 2015 US Edition


HART PA
FF
Use in or on zone 1D/2D
(only together with type of protection
"Intrinsic safety" (transmitter
7MF4...-.....-.B.. Ex ia)“and IP65)
E01



Export approval Korea
E11



Dual seal
E24



Explosion-proof "Intrinsic safety" (Ex ia) to E253)
INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.B..)



"Flameproof" explosion protection accord- E263)
ing to INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.D..)



Explosion-proof "Intrinsic safety" (Ex ia +
Ex d) to INMETRO (Brazil)
(only for transmitter 7MF4...-.....-.P..)
E283)


Ex Approval IEC Ex (Ex ia)
(only for transmitter 7MF4...-.....-.B..)
E453)



Ex Approval IEC Ex (Ex d)
(only for transmitter 7MF4...-.....-.D..)
E463)



Explosion-proof "Intrinsic safety"
to NEPSI (China)
(only for transmitter 7MF4...-.....-.B..)
E553)



Ex prot. "Explosion-proof" to NEPSI (China) E563)
(only for transmitter 7MF4...-.....-.D..)



Explosion-proof "Zone 2" to NEPSI (China) E573)
(only for transmitter 7MF4...-.....-.E..)



Ex protection „Ex ia“, „Ex d“ and „Zone 2“ E583)
to NEPSI (China)
(only for transmitter 7MF4...-.....-.R..)



"Intrinsic safety" and "Explosion-proof"
explosion protection acc. to Kosha (Korea)
(only for transmitter
7MF4...-.....-.[B, D]..-Z + E11)
E703)



Two coats of lacquer on casing and cover
(PU on epoxy)
G10



Interchanging of process connection side
H01



Stainless steel process flanges for vertical H03
differential pressure lines



Transient protector 6 kV (lightning protec- J01
tion)



Chambered graphite gasket for process
flange
J02



EPDM O-rings for process flange with
approval (WRC/WRAS)
J05



Vent valve or blanking plug of process
flange welded-in (orientation: on right
when viewing the display)4)
J08



Vent valve or blanking plug of process
J09
flange welded-in (orientation: on left when
4)
viewing the display)



1)
D59
Order code
Further designs
Add "-Z" to Article No. and specify Order code.
Profisafe transmitters can only be operated with the S7 F Systems V6.1 configuration software in combination with S7-400H
Tested according to IEC 61010. Only for measuring materials of the group
of fluids 2 in accordance with PED permissible. Not for use with dangerous
media suitable.
3)
Option does not include ATEX approval, but instead includes only the country-specific approval.
4) Blanking plug is standard configuration. Order option A40 if a vent valve is
required instead of a blanking plug.
2)
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for differential pressure and flow
Selection and Ordering data
Order code
Additional data
HART PA
FF
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
Measuring range to be set
Specify in plain text:
• in the case of linear characteristic curve
(max. 5 characters):
Y01: ... up to ... mbar, bar, kPa, MPa, psi
• in the case of square rooted characteristic
(max. 5 characters):
Y02: ... up to ... mbar, bar, kPa, MPa, psi
1)
Y01

Y02

Y15



Measuring point text (entry in device vari- Y16
able)
Max. 27 char., specify in plain text: Y16: .......



Entry of HART address (TAG)
Y17
Max. 8 char., specify in plain text: Y17: .........

Setting of pressure indication in pressure Y21
units
Specify in plain text (standard setting: bar):
Y21: mbar, bar, kPa, MPa, psi, ...
Note:
The following pressure units can be selected:
bar, mbar, mm H2O*), inH2O*), ftH2O*),
mmHG, inHG, psi, Pa, kPa, MPa, g/cm2,
kg/cm2, Torr, ATM or %
*) ref. temperature 20 °C



Setting of pressure indication in
Y22 +
non-pressure units2)
Y01 or
Y02
Specify in plain text:
3
Y22: ..... up to ..... l/min, m /h, m, USgpm, ...
(specification of measuring range in pressure
units "Y01" or "Y02" is essential, unit with
max. 5 characters)





Stainless steel tag plate and entry in
device variable (measuring point description)
Max. 16 characters, specify in plain text:
Y15: ...........................................
Preset bus address
possible between 1 and 126
Specify in plain text: Y25: .....................
Y25
Damping adjustment in seconds
(0 ... 100 s)
Y30

Factory mounting of valve manifolds, see accessories.
Only Y01, Y15, Y16, Y17, Y21, Y22, Y25 and D05 can be factory preset.
 = available
1)
2)
Measuring accuracies for PROFIBUS PA transmitters with Option Y01 are
calculated in the same way as for HART devices.
Preset values can only be changed over SIMATIC PDM.
Siemens FI 01 · 2015 US Edition
1/149
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
SITRANS P DS III for differential pressure and flow
■ Dimensional drawings
143 (5.6)
1
5
2
29
(1.14) 4)
84 (3.31)
6
3
7
8
166 (6.54)
53 (2.1)
24
(0.94)
69 (2.7)
50 (1.97)
128 (5.04)
15
(0.6)
Ø80 (3.15)
12
10
11
52 (2.05)
3
17 (0.67)
4
72 (2.83)
68 (2.7)
105 (4.1)
Electronic side, digital display
(longer overall length for cover with window)1)
2
Terminal side1)
3
Electrical connection:
Screwed gland Pg 13,5 (adapter)(Adapter)2) 3),
Screwed gland M20 x 1,5 or Screwed gland ½-14 NPT or
Han 7D/ Han 8D2) 3) plug
120 (4.7)
6
Blanking plug
7
Screw cover - safety bracket (only for type of protection
"Explosion-proof enclosure", not shown in the drawing)
8
Lateral venting for liquid measurement (Standard)
9
Lateral venting for gas measurement (suffix H02)
10 Mounting bracket (option)
Harting adapter
11 Sealing screw with valve (option)
5
Protective cover over keys
12 Process connection: ¼-18 NPT (IEC 61518)
1)
Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing
Not with type of protection "Explosion-proof enclosure"
Not with type of protection "FM + CSA" [IS + XP]"
For Pg 13,5 with adapter approx. 45 mm (1.77 inch)
92 mm (3.62 inch) for minimum distance to permit rotation with indicator
4
2)
3)
4)
5)
SITRANS P DS III pressure transmitters for differential pressure and flow, dimensions in mm (inch)
1/150
Siemens FI 01 · 2015 US Edition
96 (3.8)
Space for rotation
of housing
9
approx. 96 (3.78)
1
262 (10.3)
min. 90 (3.54) 5)
134 (5.28)
1
© Siemens AG 2015
Pressure Measurement
Transmitters for general requirements
143 (5.6)
53 (2.1)
17 (0.67)
29 (1.14) 8)
5
84 (3.31)
Ø80 (3.15)
50 (1.97)
1
approx. 96 (3.78)
6
3
4
3
7
2
min. 90 (3.54) 4)
approx. 85 (3.35) 6)
Space for rotation
of housing
8
8
128 (5.04)
approx. 217 (8.54) 7)
15
(0.6)
24
(0.94)
SITRANS P DS III for differential pressure and flow
9
60 (2.36) 5)
approx. 87 (3.43)
65 (2.56)
Electronic side, digital display
(longer overall length for cover with window)1)
5
Protective cover over keys
6
Blanking plug
2
Terminal side1)
7
3
Electrical connection:
Screwed gland Pg 13,5 (adapter)(Adapter)2) 3),
Screwed gland M20 x 1,5 or Screwed gland ½-14 NPT or
Han 7D/ Han 8D2) 3) plug
Screw cover - safety bracket (only for type of protection
"Explosion-proof enclosure", not shown in the drawing)
8
Sealing screw with valve (option)
9
Process connection: ¼-18 NPT (IEC 61518)
1
4
Harting adapter
1)
Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing
Not with type of protection "Explosion-proof enclosure"
Not with type of protection "FM + CSA" [IS + XP]"
92 mm (3.6 inch) for minimum distance to permit rotation with indicator
74 mm (2.9 inch) for PN ≥ 420 (MAWP ≥ 6092 psi)
91 mm (3.6 inch) for PN ≥ 420 (MAWP ≥ 6092 psi)
219 mm (8.62 inch) for PN ≥ 420 (MAWP ≥ 6092 psi)
For Pg 13,5 with adapter approx. 45 mm (1.77 inch)
2)
3)
4)
5)
6)
7)
8)
SITRANS P DS III pressure transmitters for differential pressure and flow, with process covers for vertical differential pressure lines, optional "H03" ,
dimensional drawing, dimensions in mm (inch)
SITRANS P DS III pressure transmitters for differential pressure and flow,
with process covers for vertical differential pressure lines
Siemens FI 01 · 2015 US Edition
1/151
1