Flow Measurement
SITRANS F C
Flow sensor SITRANS FCS400
■ Overview
The pressure drop through the sensor is a function of the properties of the fluid and the flow rate. A pressure loss and accuracy
calculator can be found on the Siemens Internet site
www.siemens.com/fc430/sizer
The preferred flow direction is indicated by an arrow on the sensor. Flow in the direction of the arrow will be measured as positive. The flow direction can be adjusted at the transmitter to compensate for reverse installation.
Installation orientation
The optimal installation orientation is vertical with the flow upwards. This ensures that suspended solids or bubbles are completely pushed through the sensor. A drain valve below the sensor will allow the pipe and sensor to drain completely.
Supports
In order to support the weight of the flowmeter and to ensure reliable measurements when external effects exist (e.g. plant vibrations), the sensor should be installed in rigidly supported
pipelines.
The flow measuring principle is based on the Coriolis Effect. The
FCS400 sensor’s measuring tubes are energized by an electromechanical driver circuit which oscillates them at their resonance frequency.
Two pick-ups are placed symmetrically upstream and downstream of the central driver. When a process fluid passes
through the sensor, the Coriolis Effect will act on the vibrating
tubes and cause deflection which can be measured as a phase
shift between pick-ups 1 and 2. The phase shift is proportional
to the mass flow rate.
The amplitude of the driver is automatically regulated to ensure
a stable output from both of the pickups.
The temperatures of the sensor tubes and frame are measured
with high precision to provide compensation for changes with
temperature in the measuring properties.
The sensor signals are analyzed for flow, density and fluid temperature in the sensor front end. The digital signal is controlled
to conform to high Safety Integrated Level (SIL) and sent digitally
to the transmitter via standard cable. The FCT030 further calculates total mass and volume, fraction, dosing control and many
other functions.
The front-end module has a process noise filter, which can be
used to improve the meter’s performance when installation and
application conditions are not ideal. Typical interferences from
process conditions such as pump pulsations, mechanical vibrations, oscillating valves can be reduced considerably.
■ Integration
The SITRANS FCS400 Massflow sensor is suitable for both indoor and outdoor installation and meets the requirements of Protection Class IP67/NEMA 4X. Optionally the sensor can be ordered with hazardous certification to Zone 1 + 20/21 (ATEX,
IECEx, EAC Ex, FM, CSA, NEPSI, INMETRO) or Class I + II + III
Div. 1 (FM).
The flowmeter is bidirectional and can be installed in any orientation. The sensor is self-draining in many positions, with vertical
mounting preferred.
It is important to ensure that the sensor tubes are always completely filled with homogeneous fluid; otherwise measuring errors may occur. Suitable fluids are clean liquids, pastes, light
slurries or gases. Condensing vapours, aerated liquids or slush
are not recommended.
The materials in contact with the process medium must be evaluated for corrosion and erosion resistances for long sensor life.
Supports or hangers should be installed symmetrically and
stress-free in close proximity to both of the process connections.
Shut-off devices
To conduct a system zero adjustment, secure shut-off devices
are required in the pipeline.
Where possible, shut-off devices should be installed both upstream and downstream of the flowmeter.
System design
• The sensor design consists of process connections, inlet and
outlet manifolds mounted in a stiff frame and two parallel tubes
equally sharing the process medium flow. The meter is protected in a pressure-rated stainless steel enclosure with two
purge ports to support a pressure guard in non-Ex applications.
• The sensing tubes are curved in the CompactCurve shape
which gives high sensitivity and low pressure loss. The
CompactCurve shape was selected to ensure that the smallest flows are measured with optimal signal to noise ratio.
• Vibration mode separation creates a controlled measuring environment only within the CompactCurve part of the tubes. As
a result the sensor has high immunity to plant vibration while
avoiding large mass balancing of the meter components.
• The 15° slope of the CompactCurve shape ensures secure
self-draining when the sensor axis is mounted vertically or up
to 10° off vertical.
• The sensor frame is designed to conduct plant vibrations directly through the sensor body to adjacent pipeline while providing isolation of the metering section from the vibration.
Careful mounting of the pipeline with regard to minimizing vibration at the meter will ensure a secure measurement environment.
■ Installation guidelines
• The mass flowmeter does not require any flow conditioning or
straight inlet pipe sections. Care should be exercised however
to ensure that any upstream valves, gates, sight glasses etc.
do not cavitate and are not set into vibration by the flow.
• It is always preferred to place the flowmeter upstream of any
control valve (what goes in, comes out) or other pipeline component which may cause flashing, cavitation or vibrations.
• The presence of gas bubbles in the fluid may result in erroneous measurements, particularly in the density measurement.
Therefore the flowmeter should not be installed at the lowest
pressure point in the liquid piping system or where vapour can
collect. Install the meter in pipeline sections with high pressure
to maintain system pressure and compress any bubbles.
Siemens FI 01 · 2016
3/151
3
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flow sensor SITRANS FCS400
3
• Drop lines downstream from the flow sensor should be
avoided to prevent the meter tube from draining during flowing
conditions. A back-pressure device or orifice is recommended to ensure that flow does not separate within the flow
sensor but the metering section remains at positive pressure
at all times while there is flow.
• The flowmeter should not come into contact with any other objects. Avoid making attachments to the housing except for the
pressure guard components (if required).
• When the connecting pipeline is larger than the sensor size,
suitable standard reducers may be installed. A selection of
oversize and undersize connections can be ordered - refer to
the sizes tables below.
• The flow sensor may be supported at the junction between
process connection and the manifold, but should not be used
to support adjacent piping. Ensure that the piping is also supported on both sides so that connection stresses are neutral.
• If strong vibrations exist in the pipeline, they should be
damped using elastic pipeline elements. The damping devices must be installed outside the supported flowmeter section. Direct connection of flexible elements to the sensor
should be avoided.
• Make sure that any dissolved gases, which are present in
many liquids, do not outgas. The back pressure at the outlet
should be at least 0.2 bar (3 psi) above the vapour pressure
of the process fluid.
• Assure that operation below the vapour pressure cannot occur
particularly for fluids with low latent heat of vaporisation.
• The sensor should not be installed in the vicinity of strong electromagnetic fields, e.g. near motors, pumps, variable frequency drives, transformers etc.
• When operating meters on a common mounting base the sensors should be mounted and spaced separate from each
other to avoid cross-talk and other vibration interferences.
• When operating meters in interconnected pipelines the pipes
should be decoupled to prevent cross talk.
Remote system cabling
The system is designed so that standard instrumentation cable
with four cores and overall screen or two screened pairs can be
used, or cable sets can be ordered with the flowmeter. The cable
can be ordered in various set lengths and terminated in the field.
The maximum design length for the sensor cable is 200 m
(656 ft), limited to 150 m (492 ft) for Ex applications with Class
IIC gases. Data transmission speed and process variable update rates may be affected by the cable characteristics. For best
results, choose a cable with the following electrical characteristics:
Property
Unit
Value
Resistance
[/km]
59
Characteristic impedance
[]
100 @ 1 MHz
Insulation resistance
[M/km]
200
Maximum voltage
[V]
300
The flowmeter system applies maximum 15 V DC in operation
and is certified intrinsically safe. The complete system is insulation tested to 1500 V in production.
Cabling solutions which can be ordered with the flowmeter are
as follows:
1. High performance plugged cable using M12 plugs into prepared sockets
2. Cable glands for either metric or NPT threaded terminal housings.
3. Plain cable in set lengths to be passed through flexible and
rigid conduit (not supplied) for metric or NPT threaded terminal housings
Cable for items 1, 2 and 3 are available either gray for standard
applications or light blue for Ex applications to identify the circuit
as intrinsically safe.
Insulation and heating
For applications where pipeline insulation is required for personnel protection or process temperature maintenance, the
SITRANS FCS400 flow sensor may also be insulated. The form
and material of insulation is not prescribed and entirely depends
on the practices at the application location or plant.
Insulation must not be crowded around the sensor pedestal but
shaped at a 45° cone to allow the pedestal to radiate excess
heat and maintain a suitable working temperature within the
front-end housing.
Where trace heating is employed, an electric heating jacket can
be ordered as an accessory. It is shaped to the sensor body and
controlled from a weatherproof setpoint device.
The jacket can heat the sensor enclosure up to 200 °C (392 °F).
However further insulation is also recommended for personnel
protection or low loss temperature maintenance.
Calibration
To ensure accurate measurement all flowmeters must be initially
calibrated. The calibration of each SITRANS FCS400 coriolis
sensor is conducted at SIEMENS flow facilities accredited according to ISO/IEC 17025 by DANAK. A calibration certificate for
every sensor is stored on the SensorFlash SD card. The accreditation body DANAK has signed the ILAC MRA agreement (International Laboratory Accreditation Corporation - Mutual Recognition Arrangement). Therefore the accreditation ensures
international traceability and recognition of the test results in 39
countries worldwide, including the US (NIST traceability).
3/152
Siemens FI 01 · 2016
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flow sensor SITRANS FCS400
■ Technical specifications
Flow sensor FCS400
Parameter
Unit
Value
Process pressure range
[barg (psi)]
316L: 0 ... 100 (0 ... 1450)
Hastelloy C22: 0 ... 160 (0 ... 2321)
Process temperature range
[°C (°F)]
-50 ... +200 (-58 ... +392)
Ambient temperature range
[°C (°F)]
-40 ... +60 (-40 ... +140)
Transport temperature range
[°C (°F)]
-40 ... +70 (-40 ... +158)
Density range
[kg/m3 (lb/ft3)]
1 ... 5000 (0.062 ... 312.2)
Process media
Fluid group
1 (suitable for dangerous fluids)
Form
Light slurry, liquid and non-condensing gas
3
No. of process values
• Primary process values
• Mass flow
• Density
• Process medium temperature
• Derieved process values
• Volume flow
• Corrected volume flow (with reference density)
• Fraction A:B
• Fraction % A:B
Performance specifications
Sensor
Parameter
Unit
DN 15
DN 25
DN 50
DN 80
Max. zero point error
[kg/h (lb/min)]
0.2 (0.007)
2.0 (0.072)
7.5 (0.276)
18 (0.66)
Qmin
[kg/h (lb/min)]
20 (0.735)
200 (7.35)
750 (27.6)
900 (33.1)
Qnom
[kg/h (lb/min)]
3 700 (136.0)
11 500 (422.6)
52 000 (1 911)
136 000 (4 997)
Qmax
[kg/h (lb/min)]
6 400 (235.2)
17 700 (650.4)
70 700 (2598)
181 000 (6651)
Linearity error mass flow
[%]
± 0.1
± 0.1
± 0.1
± 0.1
Repeatability mass flow
[%]
± 0.05
± 0.05
± 0.05
± 0.05
Density accuracy standard
calibration
[kg/m3 (lb/ft3)]
± 5 (± 0.31)
± 5 (± 0.31)
± 5 (± 0.31)
± 5 (± 0.31)
Density accuracy extended
calibration
[kg/m3 (lb/ft3)]
± 0.5 (± 0.031)
± 0.5 (± 0.031)
± 0.5 (± 0.031)
± 0.5 (± 0.031)
Temperature error
[°C (°F)]
± 0.5 (± 0.9)
± 0.5 (± 0.9)
± 0.5 (± 0.9)
± 0.5 (± 0.9)
Pressure/temperature curves
Process pressure (bar)
Metric flange ratings, EN 1092-1
120
100
ANSI Flange Ratings per ASME B16.5
Process pressure (bar)
With two major exceptions, the pressure rating of the flow sensors is independent of the process medium temperature. Design
rules for flange connections in both the EN1092-1 and ASME
B16.5 standards dictate pressure derating with increasing temperature. The charts below show the effect of process medium
temperature on the pressure ratings for the flanges within the
FCS400 product program.
120
100
80 Class 600
60
40 Class
Graphic
300
follows end of the week
20
Class 150
0
-50
PN 100
0
80
60 PN 63
40
50
100
150
200
Process temperature (°C)
ASME B16.5 flanged sensors
Graphic
PN 40
follows end of the week
20
PN 16
0
-50
0
50
100
150
200
Process temperature (°C)
EN1092-1 flanged sensors
Siemens FI 01 · 2016
3/153
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flow sensor SITRANS FCS400
Sensor variants
SITRANS FCS400 sensors are available in three main variants:
Standard, hygienic and NAMUR. A wide range of process connections is available for the FCS400 sensors. The available combinations of type, sensor size and connection size are shown in
the tables below.
12-VCO-4 Quick connect
JIS B2200:2004/10K
JIS B2200:2004/20K
JIS B2200:2004/40K
●
SMS 1145 Hygineic screwed
DIN 11864-2A Aseptic flanged
●
ISO 2853 Hygienic screwed
DIN 11864-1A Aseptic secrewed
●
ISO 2852 Hygienic clamped
DIN 32676 Hygienic Tri-clamp
DIN 11851 Hygienic screwed
ASME B1.20.1 NPT pipe thread
ISO 228-1 G pipe thread
ANSI B16.5-2009, class 600
ANSI B16.5-2009, class 300
ANSI B16.5-2009, class 150
EN 1092-1 D Nut, PN 100
EN 1092-1 D Nut, PN 63
EN 1092-1 D Nut, PN 40
EN 1092-1 B1, PN 100
EN 1092-1 B1, PN 63
EN 1092-1 B1, PN 16
Connection
Sensor
3
EN 1092-1 B1, PN 40
Standard sensors
O
O
O
O
O
O
O
Standard: 7ME461.-...
DN 15 (½") DN 6 (¼")
DN 10
●
●
O
●
DN 25 (1")
●
O
●
O
O
O
●
DN 20 (¾")
●
●
●
●
●
●
●
●
O
●
●
●
●
O
●
●
O
●
●
O
O
O
DN 15 (½")
DN 25 (1")
O
●
O
O
O
O
●
●
●
●
●
●
●
O
O
●
DN 40 (1½")
O
●
O
●
O
O
O
DN 50 (2")
●
●
O
●
O
O
O
DN 65 (2½")
O
●
O
O
DN 80 (3")
●
●
O
●
O
O
O
DN 100 (4")
●
O
O
O
DN 40 (1½")
●
●
DN 32 (1¼")
DN 50 (2")
O
8")
DN 15 (½")
DN 25 (1")
O
(3/
O
●
O
O
O
●
●
●
●
O
●
●
●
●
●
●
DN 25 (1")
●
●
O
O
O
●
●
●
●
●
O
O
O
O
●
●
●
●
●
O
O
O
O
O
●
●
●
DN 65 (2½")
DN 80 (3")
DN 50 (2")
• Combinations shown ● are Mainstream products with delivery
time of up to 15 days depending on the combination and production stock levels.
• Combinations shown O are Sidestream products with delivery
from 45 to 90 days. Not all components are held in production
stock for Sidestream products.
3/154
Siemens FI 01 · 2016
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flow sensor SITRANS FCS400
ISO 2853 0.8 μm screwed
ISO 2852 0.8 μm clamped
DIN 11864-2 0.8 μm flanged
Connection
DIN 11864-1 0.8 μm screwed
The aseptic flanges offered for FCS400 conform with the standard DIN 11864-2A BF-A. The flange fitted to the sensor is therefore the back flange and the seal is an O-ring.
DIN 32676 0.8 μm Tri-clamp
The hygienic sensors all have maximum internal surface roughness < 0.8 µm and are EHEDG and 3A approved. Hygienic sensors are offered with process connection conforming to various
international quick-connect clamps or threaded connectors.
Pressure ratings are according to the relevant standard and the
sensor size. Maximum pressure in the hygienic program is
PN 40.
DIN 11851 0.8 μm screwed
Aseptic flanged process connections
Sensor
Hygienic sensor variants
Hygienic: 7ME462.-...
DN 15 (½")
DN 6 (¼")
O
DN 15 (½")
●
●
●
Ring OD
d11
Bolt Circle Bolt
d5
holes
Flange
diameter
d10
10
13 x 1.5
10
22.4
37
4 x 9
54
15
19 x 1.5
16
28.4
42
4 x 9
59
20
23 x 1.5
20
32.4
47
4 x 9
64
25
29 x 1.5
26
38.4
53
4 x 9
70
32
35 x 1.5
32
47.7
59
4 x 9
76
40
41 x 1.5
38
53.7
65
4 x 9
82
50
53 x 1.5
50
65.7
77
4 x 9
94
65
70 x 2.0
66
81.7
95
8 x 9
107
80
85 x 2.0
81
97.7
112
8 x 11
113
●
O
●
●
●
●
O
O
DN 15 (½")
DN 25 (1")
●
DN 32 (1¼")
O
●
●
●
●
DN 40 (1½")
DN 50 (2")
Bore
d1
●
DN 20 (¾")
DN 25 (1")
Size DN Pipe
DIN 11864-2A BF-A flange dimensions
DN 10 (3/8")
DN 25 (1")
The flange dimensions in the FCS400 program are as follows:
DN 25 (1")
DN 40 (1½")
O
DN 50 (2")
●
O
●
O
O
●
●
●
●
●
●
●
●
●
●
DN 65 (2½")
DN 80 (3")
DN 50 (2")
DN 65 (2½")
●
DN 80 (3")
●
DN 100 (4")
• Combinations shown ● are Mainstream products with delivery
time of up to 15 days depending on the combination and production stock levels.
• Combinations shown O are Sidestream products with delivery
from 45 to 90 days. Not all components are held in production
stock for Sidestream products.
Siemens FI 01 · 2016
3/155
3
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flow sensor SITRANS FCS400
NAMUR sensor variants
●
●
●
ISO 2853 Hygienic screwed
●
ISO 2852 Hygienic clamped
●
DIN 11864-2A Aseptic flanged
O
DIN 11864-1A Aseptic secrewed
ASME B1.20.1 NPT pipe thread
O
DIN 32676 Hygienic Tri-clamp
ISO 228-1 G pipe thread
ANSI B16.5-2009, class 600
ANSI B16.5-2009, class 300
ANSI B16.5-2009, class 150
EN 1092-1 D Nut, PN 100
EN 1092-1 D Nut, PN 63
EN 1092-1 D Nut, PN 40
EN 1092-1 B1, PN 100
EN 1092-1 B1, PN 63
EN 1092-1 B1, PN 40
EN 1092-1 B1, PN 16
Connection
Sensor
3
DIN 11851 Hygienic screwed
The NAMUR variants have build-in lengths according to NAMUR
recommendation NE 132. The recommendations of NE 132 are
stated for sensors with flanges the same size as the sensor nominal size, and for flanges to EN1092-1 PN 40 with B1 flange facing. For couplings of other standards such as ASME B16.5
Class 150, the overall length incorporates the difference in
length between standard EN and ASME flanges. NAMUR variants are offered with flange and pipe thread connections according to EN, ISO oand ASME standards, as shown in the table
below.
●
●
●
●
O
O
NAMUR: 7ME471.-...
DN 15 (½") DN 6 (¼")
DN 10 (3/8")
DN 15 (½")
O
O
●
O
●
O
O
O
DN 20 (¾")
DN 25 (1")
DN 25 (1")
O
●
O
●
●
O
●
●
O
●
●
●
O
DN 15 (½")
DN 25 (1")
O
●
O
O
O
●
O
●
●
●
DN 32 (1¼")
DN 80 (3")
●
●
●
●
DN 40 (1½")
O
●
O
●
O
O
O
DN 50 (2")
O
●
O
●
O
O
O
DN 65 (2½")
O
O
O
O
O
●
O
O
O
●
O
●
●
O
●
●
●
O
●
●
DN 25 (1")
O
●
O
O
●
●
●
●
●
●
●
●
●
●
O
●
●
●
DN 50 (2")
DN 65 (2½")
O
●
O
O
DN 80 (3")
O
●
O
●
DN 100 (4")
O
O
O
O
• Combinations shown ● are Mainstream products with delivery
time of up to 15 days depending on the combination and production stock levels.
• Combinations shown O are Sidestream products with delivery
from 45 to 90 days. Not all components are held in production
stock for Sidestream products.
3/156
●
O
O
DN 40 (1½")
DN 50 (2")
●
Siemens FI 01 · 2016
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flow sensor SITRANS FCS400
■ Dimensional drawings
'
&
3
%
$
Sensor
A
B
C
Weight
[DN]
[inch]
[mm]
[inch]
[mm]
[inch]
[mm]
[inch]
[kg]
[lb]
15
½
90
3.54
280
11.0
90
3.54
4.6
10.1
25
1
123
4.84
315
12.4
90
3.54
7.9
17.4
50
2
187
7.36
390
15.4
90
3.54
25.7
56.7
80
3
294
11.6
504
19.8
90
3.54
66.5
147
SITRANS FCS400, dimensions in mm (inch), weights in kg (lb), for a EN 1092 PN 40 flanged version.
The build-in length D depends on the flange.
Siemens FI 01 · 2016
3/157
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flow sensor SITRANS FCS400
Overall length
The overall length (build-in length (D)) of each sensor depends on the connection standard and the pressure rating. The tables below
summarize the dimensions available at the time of publishing. Please contact Siemens for further information about our desired process connection specification.
Standard: 7ME461.-...
3
Sensor
DN 15 (½")
Connection
DN 6
(¼")
DN 25 (1")
265
265
360
EN 1092-1 B1, PN 40
265
265
360
EN 1092-1 B1, PN 63
265
EN 1092-1 B1, PN 100
270
ANSI B16.5, class 150
270
270
360
ANSI B16.5, class 300
270
270
ANSI B16.5, class 600
270
285
265
ANSI B1.20.1 NPT pipe thread
265
DIN 11851 Hygienic screwed
DN 80 (3")
DN 10 DN 15 DN 20 DN 25 DN 25 DN 32 DN 40 DN 40 DN 50 DN 65 DN 80 DN 100
(3/8") (½")
(¾")
(1")
(1")
(1¼") (1½") (1½") (2")
(2½") (3")
(4")
EN 1092-1 B1, PN 16
ISO 228-1 GH pipe thread
DN 50 (2")
275
265
610
915
840
840
610
610
915
840
840
360
610
610
915
915
915
360
610
610
915
915
915
365
620
915
875
360
380
620
915
875
360
380
620
915
875
840
840
365
270
265
610
620
365
265
193
360
DIN 32676-C Hygienic clamp
265
265
360
DIN 11864-1 Aseptic screwed
265
265
360
DIN 11864-2 Aseptic flange
265
265
ISO 2852 Hygienic clamp
620
360
265
610
360
360
265
ISO 2853 Hygienic screwed
365
274
360
360
610
610
875
610
875
620
610
875
610
610
840
610
860
274
SITRANS FCS400, overall length (D), dimensions in mm
Sensor
DN 15 (½")
Connection
DN 6
(¼")
DN 25 (1")
10.43
10.43
14.17
EN 1092-1 B1, PN 40
10.43
10.43
14.17
EN 1092-1 B1, PN 63
10.43
EN 1092-1 B1, PN 100
10.63
ANSI B16.5, class 150
10.63
10.63
14.17
ANSI B16.5, class 300
10.63
10.63
ANSI B16.5, class 600
10.63
11.22
10.43
ANSI B1.20.1 NPT pipe thread
10.43
DIN 11851 Hygienic screwed
10.83
10.43
24.02
36.02
33.07
33.07
24.02
24.02
36.02
33.07
33.07
14.17
24.02
24.02
36.02
36.02
36.02
14.17
24.02
24.02
36.02
36.02
36.02
14.37
24.41
36.02
34.45
14.17
14.96
24.41
36.02
34.45
14.17
14.96
24.41
36.02
34.45
33.07
33.07
7.60
14.17
10.43
10.43
14.17
DIN 11864-1 Aseptic screwed
10.43
10.43
14.17
DIN 11864-2 Aseptic flange
10.43
10.43
SITRANS FCS400, overall length (D), dimensions in inch
3/158
Siemens FI 01 · 2016
14.17
10.43
10.43
24.41
14.37
10.43
ISO 2852 Hygienic clamp
14.37
14.37
10.63
10.43
24.02
DIN 32676-C Hygienic clamp
ISO 2853 Hygienic screwed
DN 80 (3")
DN 10 DN 15 DN 20 DN 25 DN 25 DN 32 DN 40 DN 40 DN 50 DN 65 DN 80 DN 100
(3/8") (½")
(¾")
(1")
(1")
(1¼") (1½") (1½") (2")
(2½") (3")
(4")
EN 1092-1 B1, PN 16
ISO 228-1 GH pipe thread
DN 50 (2")
24.41
14.17
24.02
14.17
10.78
14.17
14.17
10.78
24.02
24.02
34.45
24.02
34.45
24.41
24.02
34.45
24.02
24.02
33.07
24.02
33.86
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flow sensor SITRANS FCS400
Hygienic 0.8 m: 7ME462.-...
Sensor
DN 15 (½")
Connection
DN 10
(3/8")
DN 15
(½")
DIN 11851 Hygienic screwed
265
265
DN 25 (1")
DN 20
(¾")
DN 25
(1")
265
DN 25
(1")
DN 32
(1¼")
360
360
360
DN 40
(1½")
DN 50 (2")
DN 80 (3")
DN 40
(1½")
DN 50
(2")
DN 65
(2½")
DN 80
(3")
610
610
840
840
DIN 32676-C Hygienic clamp
265
DIN 11864-1 Aseptic screwed
265
360
DIN 11864-2 Aseptic flange
265
360
620
610
ISO 2852 Hygienic clamp
265
360
ISO 2853 Hygienic screwed
265
360
360
610
875
610
875
610
875
610
840
610
860
SITRANS FCS400, overall length, dimensions in mm
Sensor
DN 15 (½")
Connection
DN 10
(3/8")
DN 15
(½")
DIN 11851 Hygienic screwed
10.43
10.43
DN 25 (1")
DN 20
(¾")
DN 25
(1")
DN 25
(1")
DN 32
(1¼")
7.60
14.17
14.17
DIN 32676-C Hygienic clamp
10.43
DIN 11864-1 Aseptic screwed
10.43
14.17
DIN 11864-2 Aseptic flange
10.43
14.17
10.43
14.17
ISO 2852 Hygienic clamp
10.43
14.17
ISO 2853 Hygienic screwed
10.43
14.17
DN 40
(1½")
DN 50 (2")
DN 80 (3")
DN 40
(1½")
DN 50
(2")
DN 65
(2½")
DN 80
(3")
24.20
24.20
33.07
33.07
14.17
24.20
34.45
24.20
34.45
24.41
24.20
34.45
24.20
24.20
33.07
24.20
33.86
SITRANS FCS400, overall length, dimensions in inch
Siemens FI 01 · 2016
3/159
3
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flow sensor SITRANS FCS400
NAMUR: 7ME471.-...
Sensor
DN 15 (½")
Connection
DN 6
(¼")
DN 25 (1")
DN 80 (3")
EN 1092-1 B1, PN 16
510
510
600
715
715
915
915
915
EN 1092-1 B1, PN 40
510
510
600
715
715
915
915
915
EN 1092-1 B1, PN 63
510
600
715
715
915
915
915
600
715
715
915
915
915
EN 1092-1 B1, PN 100
3
DN 50 (2")
DN 10 DN 15 DN 20 DN 25 DN 25 DN 32 DN 40 DN 40 DN 50 DN 65 DN 80 DN 100
(3/8") (½")
(¾")
(1")
(1")
(1¼") (1½") (1½") (2")
(2½") (3")
(4")
EN 1092-1 D, PN 16
510
600
715
715
915
EN 1092-1 D, PN 40
510
915
600
715
715
EN 1092-1 D, PN 63
600
715
715
ANSI B16.5, class 150
600
915
ANSI B16.5, class 300
600
915
600
915
ANSI B16.5, class 600
ISO 228-1 GH pipe thread
510
ANSI B1.20.1 NPT pipe thread
510
DIN 11851 Hygienic screwed
915
510
510
510
DIN 32676-C Hygienic clamp
510
DIN 11864-1 Aseptic screwed
510
600
510
600
600
715
600
715
915
915
715
600
715
DIN 11864-2 Aseptic flange
ISO 2852 Hygienic clamp
510
600
ISO 2853 Hygienic screwed
510
600
715
715
915
715
SITRANS FCS400, overall length, dimensions in mm
Sensor
DN 15 (½")
Connection
DN 6
(¼")
DN 25 (1")
DN 50 (2")
DN 80 (3")
DN 10 DN 15 DN 20 DN 25 DN 25 DN 32 DN 40 DN 40 DN 50 DN 65 DN 80 DN 100
(3/8") (½")
(¾")
(1")
(1")
(1¼") (1½") (1½") (2")
(2½") (3")
(4")
EN 1091-1 B1, PN 16
20.08
20.08
23.62
28.15
28.15
36.02
36.02
36.02
EN 1091-1 B1, PN 40
20.08
20.08
23.62
28.15
28.15
36.02
36.02
36.02
EN 1091-1 B1, PN 63
20.08
23.62
28.15
28.15
36.02
36.02
36.02
23.62
28.15
28.15
36.02
36.02
36.02
EN 1091-1 B1, PN 100
EN 1092-1 D, PN 16
20.08
23.62
28.15
28.15
36.02
EN 1092-1 D, PN 40
20.08
23.62
28.15
28.15
36.02
EN 1092-1 D, PN 63
23.62
28.15
28.15
ANSI B16.5, class 150
23.62
36.02
ANSI B16.5, class 300
23.62
36.02
ANSI B16.5, class 600
23.62
36.02
ISO 228-1 GH pipe thread
20.08
ANSI B1.20.1 NPT pipe thread
20.08
DIN 11851 Hygienic screwed
36.02
20.08
20.08
20.08
DIN 32676-C Hygienic clamp
20.08
DIN 11864-1 Aseptic screwed
20.08
23.62
20.08
23.62
23.62
28.15
23.62
28.15
36.02
36.02
28.15
23.62
28.15
DIN 11864-2 Aseptic flange
ISO 2852 Hygienic clamp
20.08
23.62
ISO 2853 Hygienic screwed
20.08
23.62
SITRANS FCS400, overall length, dimensions in inch
3/160
Siemens FI 01 · 2016
28.15
28.15
28.15
36.02
© Siemens AG 2016
Flow Measurement
SITRANS F C
Flowmeter - Accessories/Spare parts
Spare parts - transmitter FCT030
Article No.
Description
Article No.
Display and keypad assembly with firewire connection
to the transmitter module1)
A5E03548971
Mounting bracket - FCT030;
in painted aluminum for
pipe or wall mounting of
transmitter FCT030 remote
version. Including lock ring,
pressure pads and seal cap
A5E03906091
Sensor interface (Compact).
Front end flow calculator and
process detection. SIL 3
approved1)
A5E03549142
M12 option for sensor housing in stainless steel. Prewired and potted to replace
M12 socket in DSL housing
A5E03906095
A5E03549098
M12 option - remote - in
painted aluminum. Prewired and potted replacement M12 connection for
FCT030 transmitter remote
version
A5E03906104
Sensor interface (Remote);
barrier unit for high speed
digital communication and
Ex ib power supply to
remote front end
DSL module
Remote terminal house M20
A5E03906112
Display lid in painted aluminum with Ex glass plate and
o-ring seal
A5E03549344
Remote terminal house NPT - in painted aluminum
for sensor cable termination
at FCT030 transmitter
remote version. Pre-wired
and potted
A5E03906130
Transmitter cassette (active)
with SIL approved
4 ... 20 mA output and
HART 7.21)
A5E03549357
Transmitter cassette (passive) with SIL approved
4 ... 20 mA output and
HART 7.21)
A5E03549383
Bag of loose spare parts;
including cable strain relief
components, mounting tool,
seals and gasket, assorted
screws and washers, hex
cap nut, blind plugs, and
o-rings
A5E03549396
Power supply
240 V AC, 47 ... 63 Hz
24 ... 90 V DC
A5E03549413
Blind lid in painted aluminum with o-ring seal
A5E03549429
Description
3
Spare parts - sensor FCS400
I/O assembly
Advise Order code
F00 to F97 from Selection
and Ordering data2)
A5E03939114
SensorFlash
(micro SD card)
A5E03915258
Description
Article No.
Blind lid in painted aluminum with o-ring seal
A5E03549295
Frontend cassette
Spare part frontend
cassette for remote version
of FC430 and cassette for
FC4101)
A5E03549191
Sensor housing metric
A5E03549313
Sensor housing NPT in
painted aluminum
A5E03906080
Bag of loose parts for sensor; including cable strain
relief components, washer,
seals, o-rings, and assorted
screws
A5E03549324
1)
The system firmware bundle must be stated in the "Remark" field when
ordering, to ensure compatibility of the system. The FW revision is found
on the product label for FC430 and FC410.
Further for FC430 the firmware bundle can be found in the local display in
the menu items 3.1.10. e.g. "2.02.01-02"
2)
The I/O configuration must be stated in the "Remark" field. The I/O configuration is found in the F option of the ordering code. e.g. code “F40” for
ordering Ch2 Active Current/Freq/Pulse, Ch3 Active Current/Freq/Pulse,
Ch4 Active Input
Siemens FI 01 · 2016
3/181