ESP200 Class 48 Single Phase_Trip Curves.pdf

Class 48
3UB88
ESP200 size A / A1
Trip Curves
single phase
UL508
Danger
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this
device before working on this device.
Replace all covers before power
supplying this device is turned on.
Peligro
Danger
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Desenergice totalmente antes de instalar o darle
servicio.
Vuelva a colocar todas las cubiertas antes de
energizar el interruptor.
EN
Settings
ES
1) CLASS 5
1)
Tension dangereuse.
Danger de mort ou risque de blessures graves.
Couper l’alimentation de l’appareil et le verrouiller
avant d’effectuer des travaux sur l’appareil.
Enlever tous les recouvrements avant de mettre
sous tension l’appareil.
Ajustes
10
20
FR
Réglages
30
Time - Current - Characteristics
CLASS 5, 10, 20, 30
1000
2)
Trip time in seconds
500
3)
100
50
CLASS 30 - cold start
CLASS 20 - cold start
10
CLASS 10 - cold start
5
CLASS 5 - cold start
CLASS 5 - warm start
1
0.6
1
1.5
5
2
multiple of full load amp (FLA)
10
2) Ground fault Level is to protect equipment, not intended for
EN personnel protection. Ground fault trip: ground fault current > 60 %
of present motor current.
3)Trip Current is 125 % of Full Load Amps
2) El nivel de puesta a tierra sirve para proteger a los equipos, pero
no al personal. Disparo por falla a tierra: corriente de puesta a tierra
ES
> 60 % de la corriente actual del motor.
3)La corriente de disparo alcanza 125 % de de la carga eléctrica
total.
2) Le niveau de mise à la terre est prévu pour protéger le matériel
mais pas les personnes. Déclenchement sur défaut à la terre:
FR
courant de mise à la terre > 60 % du courant moteur actuel.
3) Le courant de déclenchement s’élève à 125 % de la charge
électrique totale.