UL Report for MSP 3RV102 Manual and Group.pdf

File E47705
Vol. 7
and Report
Sec. 9
Page 1
Issued: 1997-08-29
Revised: 2005-06-30
DESCRIPTION
PRODUCT COVERED:
USL, CNL - Type Nos. 3RV1021, 3RV1121, 3RV1321 or 3RV1421, followed
by combination of 0, 1 or 4 and a letter A through K, followed by A or C,
followed by 1 or 3. May be followed by additional numbers and letters for
manufacturers use.
GENERAL:
These devices are open type 3-pole manual motor controllers for
starting and stopping motors which may be connected directly across the
line. They are adjusted over a small range as indicated in the setting
range table. They are provided with integral ambient compensated, non
replaceable thermal trip features and are suitable for providing overload
protection and motor disconnect. The trip current is 125 percent of the
FLA shown on dial. Line or load side of the main terminals may be used in
reverse also.
Type 3RV1321 - .... is identical to the standard series device but
thermal overload trip is out of function.
Type 3RV1121-... is identical to the standard series device but with
no motor overload function. The internal overload tripping system does not
trip the controller, however it trips the attached trip module for
indication to remote panels.
Type 3RV1421 - .... is identical to the standard series device but
instantaneous tripping is adjusted to 19 x Je.
These devices may be provided with certified accessories of Type
3RV19..including auxiliary switches, tripping units, bus bar assembly and
short circuit indicators.
RATINGS:
General Purpose Rating
600 V AC, 25 A, FLA max 25 A
Horsepower
Voltage
115 V
200 V
230/240 V
460/480 V
575/600 V
1-ph
2 hp
3 hp
3 hp
-
3-ph
5 hp
7 ½ hp
15 hp
20 hp
Pilot Duty rating for 3RV1121 trip module outputs 1 NO + 1 NC: C600,
R300 opposite polarity.
File E47705
Vol. 7
and Report
Sec. 9
Page 2
Issued: 1997-08-29
Revised: 2005-09-07
ENGINEERING CONSIDERATIONS (NOT FOR UL REPRESENTATIVE USE):
CNL - Indicates Investigated to Canadian National Standard(s) C22.2
No. 14-M95
Note: CNL = Canadian National Standards - Listed.
USL = United States Standards - Listed.
These devices are suitable for use on a circuit capable of delivering
not more than 1,000 rms symmetrical amperes up to setting range - 1B, 600 V
maximum and width - 1C and higher 5,000 rms symmetrical amperes, 600 V
maximum.
Maximum Short-circuit rating:
in Group Installations
480 V, 3 phase, 65,000 rms symmetrical
amperes
600 V, 3 phase, 30,000 rms symmetrical
Amperes for ratings 0.11 up to 12.5 A
600 V, 3 phase, 10,000 rms symmetrical
Amperes for ratings 11 up to 25 A
Enclosure size: 11-1/2 by 11-1/2 by 6 inches metal.
Branch Circuit Protective device: The appropriate BCPD need to be
determined in accordance with the National Electrical Code, Article 430-53
and the application. The following devices are permitted.
Fuses: Classes RK1, RK5, J, G, T, CC or
Circuit Breakers: Listed Siemens type, with a marked short-circuit
rating equal or larger than the available short-circuit current
rating.
These devices were tested for group installation use at the above
levels without any upstream branch circuit device.
All devices except suffix 4A, 4B, 4C, and 4D are suitable for tap
conductor protection in group applications, 600 V ac maximum.
All devices with suffix 4A, 4B, and 4C are suitable for tap conductor
protection in group applications, 480 V ac maximum.
These devices are suitable to provide over current protection for
control transformers.
These devices are suitable for motor disconnect.
GROUP INSTALLATION:
All setting ranges are suitable for use in group installation for the
following ratings:
File E47705
Vol. 7
and Report
Sec. 9
Page 2A
Issued: 1997-08-29
New: 2005-09-07
NOMENCLATURE BREAKDOWN:
3RV1021-
1A
A
1
8 -
1B
P0
I
II
III
IV
V
VI
VII
I.
*
II.
Basic Type Size S0
3RV1021 - 3 main contacts with overload and short-circuit
protection, instantaneous tripping 12 x Je
3RV1121 – 3 main contacts with short-circuit protection, overload
tripping 12 x 1e is indicated by an attached tripping
module.
3RV1321 - 3 main contacts with short-circuit protection only
3RV1421 - 3 main contacts with overload and short-circuit
protection, instantaneous tripping 19 x Je
Setting Ranges
Suffix
From
OA
0B
0C
0D
0E
0F
0G
0H
0J
0K
1A
1B
1C
1D
1E
1F
1G
1H
1J
1K
4A
4B
4C
4D
0.11
0.14
0.18
0.22
0.28
0.35
0.45
0.55
0.7
0.9
1.1
1.4
1.8
2.2
2.8
3.5
4.5
5.5
7
9
11
14
17
20
to (A)
max. Fuse or CB
0.16
0.2
0.25
0.32
0.4
0.5
0.63
0.8
1
1.25
1.6
2
2.5
3.2
4
5
6.3
8
10
12.5
16
20
22
25
6 A
6 A
6 A
6 A
6 A
6 A
6 A
6 A
6 A
6 A
6 A
6 A
10 A
10 A
15 A
20 A
25 A
30 A
40 A
50 A
60 A
80 A
100 A
100 A
File E47705
Vol. 7
and Report
Sec. 9
Page 3
Issued: 1997-08-29
Revised: 2005-06-30
III. Tripping Class
A
setting ranges with instantaneous tripping Class 10.
C
same as A but setting range fixed to maximum range value
IV.
Type of Terminals
1
Screw Terminal
3
main terminal have screw terminals auxiliary contact if provided
have cage clamp terminals
V.
Auxiliary Switches and Tripping Units
(Combinations with certified accessories Type 3RV19...)
0
without
1
1NO + 1NC, side mounted
2
2NO, side mounted
3
2NC, side mounted
4
1NO/NC Changeover, top mounted
5
1NO + 1NC, top mounted
8
code No. for further following suffixes under V.
VI.
Auxiliary Switches and Tripping Units continued
-OK Supply side from the bottom (main terminals used in reverse)
-1B Undervoltage Trip, side mounted
-2B same as -1B and 2NO aux. switch make-before-break
-3B Remote Tripping Unit, side mounted
VII.
..
*
Operating voltage for accessories
24 V through 600 V ac or 12 V through 250 V dc
File E47705
Vol. 7
and Report
Sec. 9
*Page 4
Issued: 1997-08-29
Revised: 2003-06-05
CONSTRUCTION DETAILS:
General: The product shall be constructed in accordance with the
following description and photos.
Spacings: Other than noted below, the spacings between bare live
parts of opposite polarity and between bare live parts and grounded metal
parts is not less than 3/8 in (9.5 mm) measured through air or 1/2 in (12.7
mm) measured over the surface of insulating material.
The spacings between bare live parts and metal parts of an enclosure
or the mounting surface shall be less than 1/2 in (12.7 mm) through air or
over surface.
Tolerances:
nominal.
Unless specified otherwise, the indicated dimensions are
Corrosion Protection: All parts are of corrosion resistant material
or are plated or painted as corrosion protection.
Markings: Paper adhesive labels on the device and printed to the
cover including the manufacturer’s name, type and electrical ratings.
The terminal tightening torque must be marked on the device. These
markings do not pertain to control circuits. Line and Load side of the main
terminals may be used in reverse also.
The following statement is also marked on the device:
“MAX FUSE xx A”
xx = for current rating of the fuse see list on page 2
The following statement is also marked on the device or in the
instruction manual:
“SUITABLE FOR USE ON A CIRCUIT CAPABLE OF DELIVERING NOT MORE THAN
5000 RMS SYMMETRICAL AMPERES; 600 V MAXIMUM”.
“USE 75°C COPPER WIRE ONLY”
“SUITABLE AS MOTOR DISCONNECT”
All devices except suffix 4A, 4B, 4C, and 4D are marked “Suitable for tap
conductor protection in group applications.” Suffix 4A, 4B, and 4C
are marked “Suitable for tap conductor protection in group
applications, 480 V ac maximum.”