UL Report for MSP 3RV1041 Type E Combo.pdf

File E156943
Project 97ME21192
January 20, 1998
REPORT
on
INDUSTRIAL CONTROL EQUIPMENT - COMBINATION MOTOR CONTROLLERS
Siemens Energy and Automation Inc.
Canton, GA
Copyright © 1998 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to reproduce
this Report provided it is reproduced in its entirety.
File E156943
Vol. 1
Sec. 13
and Report
Page 1
Issued:
Revised:
1998-01-20
2003-06-05
DESCRIPTION
PRODUCT COVERED:
USL, CNL - Open Type Self-Protected Combination Motor Controller, Cat.
No. 3RV1041 or 3RV1042, followed by up to 3 digits, followed by F, H, J, K, L
or M, followed by A or B, followed by 1 or 3, followed by 0, 1, 2, 3, or 8,
may be followed by additional numbers and letters. 3RT1946-4GA07 Line
Terminal Adapter.
GENERAL:
These device are open type manual combination motor controller. They are
intended to provide motor disconnection means, motor branch-circuit shortcircuit and ground fault protection, motor control, and motor overload
*protection. These devices are suitable for use as Service Equipment.
*These devices may also be used with Siemens Listed type 3RT contactors and
3RW solid state controllers. When used, the contactors and solid state
controllers have the same horsepower rating as the 3RV1021 devices with which
they may be used.
Type 3RV1042 devices are identical to the Types 3RV1041.
is for marketing purposes only.
The name change
These devices are provided with line terminal adapters cat. no. 3RT1946*46A07. The adapters may be factory or field-installed. (See “Marking”
section).
ENGINEERING CONSIDERATIONS (NOT FOR UL REPRESENTATIVE USE):
CNL - Indicates investigated to Canadian National Standard(s) C22.2
No. 14-M91.
Note:
CNL = Canadian National Standards - Listed
USL = United States Standards - Listed
RATINGS:
Maximum HP ratings
Voltage 50/60 Hz
115-120
200-208
230-240
460-480
575-600
1-phase
2-poles
3-phase
3-poles
10 @
20 @
25 @
-----
--40 @
40 @
75 @
100 @
These devices are suitable for Design E motors.
@ Suitable for controlling motors with a maximum motor nameplate full
load current of 100 Amps at 400 V ac maximum, 75 amps at 600 V ac.
Max General Use -
100 A at 600 Y/347 V ac, 3 ph, 50/60 Hz
100 A at 480 Y/277 V ac, 3 ph, 50/60 Hz
100 A at 240 V ac, 3 ph, 50/60 Hz
These devices are suitable for use on circuits capable of delivering the
following maximum short-circuit currents.
File E156943
*
Vol. 1
Sec. 13
and Report
Page 2
Issued:
Revised:
1998-01-20
2003-06-05
RMS Symmetrical Amperes
Voltage
30 kA
600 Y/347 V ac
65 kA
480 Y/277 V ac
65 kA
240 V ac
The trip rating is 125% of the dial setting (thermal range)
NOMENCLATURE:
3RV1041
I
-
4F
II
A
III
1
IV
8
V
I
Basic Type, Size S3
3RV1041, 3RV1042 - 3 main contacts
II
Setting Ranges
III
Suffix
from
to (A)
4F
4H
4J
4K
4L
4M
28
36
45
57
70
80
40
50
63
75
90
100
VI
VII
P0
VII
setting range with instantaneous tripping 12 x In
setting range with instantaneous tripping 12 x In, Class 20
overload relay.
Type of Terminals
1
3
V
1B
VI
Tripping Class
A
B
IV
-
Screw terminal
Main terminal have screw terminals, all other terminals have gage
clamps
Auxiliary Switches and Tripping Units
(Assemblies with certified accessories Type 3RV19...)
0
1
2
3
none provided
1NO + 1NC, side mounted
2NO, side mounted
2NC, side mounted
8
code number for further following suffixes under VI
Auxiliary Switches and tripping units, continued
-1B Undervoltage trip, side mounted
-2B Undervoltage trip, side mounted, and 2NO aux.
before-break
-3B Remote tripping unit, side mounted.
Operating Voltage of Accessories
24 V through 600 V ac, or
Contacts, make-
12 V through 250 V dc