32310091 OE spec MTU16V4000DS2250 3H NEA 50Hz 1 15

DIESEL GENERATOR SET
MTU 16V4000 DS2250
380V – 11 kV/50 Hz/Mission Critical Power/NEA (ORDE) Optimized
MTU 16V4000G23/Water Charge Air Cooling
Optional equipment and finishing shown. Standard may vary.
Product Highlights
// Benefits
// Performance
- Low fuel consumtion
- Optimized system integration ability
- High reliability
- High availability of power
- Long maintenance intervals
Assurance Certification (PAC)
- Engine-generator set tested to ISO 8528-5 for transient
response
- 85% load factor
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
// MTU
// Complete
Onsite Energy is a single-source supplier
// Support
- Global product support offered
// Standards
- Engine-generator set is designed and manufactured in
facilities certified to standards ISO 2008:9001 and
ISO 2004:14001
- Generator set complies to ISO 8528
- Generator meets NEMA MG1, BS5000, ISO, DIN EN and
IEC standards
- NFPA 110
// Power
Rating
- System ratings: 2050 kVA - 2150 kVA
- Accepts rated load in one step per NFPA 110
- Generator set complies to G3 according to ISO 8528-5
- Generator set exceeds load steps according to ISO 8528-5
range of accessories available
- Control panel
- Circuit breaker/power distribution
- Fuel system
- Fuel connections with shut-off valve mounted to base frame
- Starting/charging system
- Exhaust system
- Mechanical and electrical driven radiators
- Medium voltage alternators
// Emissions
- NEA (ORDE) optimized
// Certifications
- CE certification option
2
/ // / MTU 16V4000 DS2250 / 3H / 50 Hz / 380V - 11kV
Application data➀
// Manufacturer
Model
Type
Arrangement
Displacement: l
Bore: mm Stroke: mm Compression ratio
Rated speed: rpm
Engine governor
Max power: kWm Air cleaner
// // Engine
MTU
16V4000G23
4-cycle
16V
76.3
170
210
16.4
1500
ADEC
1798
Dry
Fuel System
Maximum fuel lift: m Total fuel flow: l/min
// 5
20
Total oil system capacity: l
Engine jacket water capacity: l
Intercooler coolant capacity: l
300
175
50
// Combustion Air Requirements
Combustion air volume: m3/s
Max. air intake restriction: mbar
2.4
50
// Cooling/Radiator System
Coolant flow rate (HT circuit): m3/h
Coolant flow rate (LT circuit): m3/h
Heat rejection to coolant: kW
Heat radiated to charge air cooling: kW
Heat radiated to ambient: kW
Fan power for mech. radiator (40°C): kWm
68.5
30
610
370
90
70
// Fuel Consumption➁
At 100% of power rating: At 75% of power rating: At 50% of power rating:
Liquid Capacity (Lubrication)
l/hr
433.3
331.4
229.6
g/kwh
200
204
212
Exhaust System
Exhaust gas temp. (after turbocharger): °C
Exhaust gas volume: m3/s
Maximum allowable back pressure: mbar
Minimum allowable back pressure: mbar
➀ All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
➁ Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
All fuel consumption values refer to rated engine power.
475
6.2
85
30
3
/ // / MTU 16V4000 DS2250 / 3H / 50 Hz / 380V - 11kV
Standard and Optional Features
// System
Ratings (kW/kVA)
Generator model
Voltage
NEA (ORDE) optimized 40°C/100m
without radiator
with mechanical radiator
with electr. driven radiator
kWel
kVA*
AMPS
kWel
kVA*
AMPS
kWel
kVA*
AMPS
Marathon 744RSL7092
380 V
1680
2100
3191
1640
2050
3115
1640
2050
3115
(Low voltage
400 V
1680
2100
3031
1640
2050
2959
1640
2050
2959
marathon standard)
415 V
1680
2100
2922
1600
2000
2782
1600
2000
2782
Marathon 1020FDL7093 380 V
1680
2100
3191
1640
2050
3115
1640
2050
3115
(Low voltage 400 V
1680
2100
3031
1640
2050
2959
1640
2050
2959
marathon oversized)
415 V
1680
2100
2922
1600
2000
2782
1600
2000
2782
Leroy Somer LSA 51.2 VL90 380 V
1720
2150
3267
1680
2100
3191
1680
2100
3191
(Low voltage
400 V
1720
2150
3103
1680
2100
3031
1680
2100
3031
Leroy Somer)
415 V
1720
2150
2991
1680
2100
2922
1680
2100
2922
Marathon 1020FDH7097 11 kV
1680
2100
110
1640
2050
108
1640
2050
108
(Medium volt. marathon)
Leroy Somer LSA 53.1 UL85 11 kV
1720
2150
113
1640
2050
108
1640
2050
108
(Medium volt. Leroy Somer)
* cos phi = 0,8
// Engine
■ 4-Cycle
■ Standard single stage air filter
■ Oil drain extension & shut-off valve
// ■ Common rail fuel injection
■ NEA (ORDE) optimized engine
■ Centrifugal oil filter
■ No load to full load regulation
■ ±0,25% voltage regulation no load to
full load
■ Brushless alternator with brushless
pilot exciter
■ 4 pole, rotating field
■ Sustained short circuit current of up
to 250% of the rated current for up
to 10 seconds (marathon generator)
 Sustained short circuit current of up
to 300% of the rated current for up to
10 seconds (Leroy Somer generator)
■ Marathon low voltage generator
 Leroy Somer generator
 Oversized generator
 Medium voltage generator
Generator
■ NEMA MG1, BS5000, ISO, DIN EN and
IEC standards
■ Self-ventilated
■ Superior voltage waveform
■ Solid state, volts-per-Hertz regulator
// ■ Closed crankcase ventilation with
improved oil seperator
■ Governor-electronic isochronous
Cooling System
■ Jacket water pump
■ Thermostat(s)
■ Water charge air cooling
 Mechanical radiator
 Electrical driven front-end cooler
 Jacket water heater
■ Represents standard features
 Represents optional features
4
/ // / MTU 16V4000 DS2250 / 3H / 50 Hz / 380V - 11kV
Standard and Optional Features, continuation
// Control Panel
■ Pre-wired control cabinet for easy
application of customized controller
(V1+)
 Island operation (V2)
 Automatic mains failure operation
with ATS (V3a)
 Automatic mains failure operation
incl. control of generator and mains
breaker (V3b)
 Island parallel operation of multiple
gensets (V4)
Automatic mains failure operation
with short (< 10s) mains parallel
overlap synchronization (V5)
Mains parallel operation of a single
genset (V6)
Mains parallel operation of multiple
gensets (V7)
//  Manual-actuated circuit breaker
 Electrical-actuated circuit breaker
 Stand-alone solution in seperate
switch box
Fuel System
■ Flexible fuel connectors mounted to
base frame
 Fuel filter with water separator
 Switchable fuel filter with
water separator
//  Different expansion modules
 Remote annunciator
 Daytank control
 Generator winding temperature
monitoring
 Generator bearing temperature
monitoring
 Differential protection with
multi-finction protection relay
 Modbus RTU-TCP gateway
Circuit Breaker/Power Distribution
 3-pole circuit breaker
 4-pole circuit breaker
//  Basler controller
 Deif controller
■Complete system metering
■ Digital metering
■ Engine parameters
■ Generator Protection Functions
■ Engine protection
■ SAE J1939 engine ECU
communications
■ Parametrization software
■ Multilingual capability
■ Multiple programmable contact inputs
■ Multiple contact outputs
■ Event recording
■ IP 54 front panel rating with
integrated gasket
 Seperate fuel cooler
 Fuel cooler integrated into cooling
equipment
Starting/Charging System
■ 24V starter
 Starter batteries
 Battery rack & cables
 Battery charger
■ Represents standard features
 Represents optional features
5
/ // / MTU 16V4000 DS2250 / 3H / 50 Hz / 380V - 11kV
Standard and Optional Features, continuation
// Mounting System
■ Welded base frame
// ■ Resilient engine and generator
mounting
Exhaust System
 Exhaust bellows with connection
flange
 Exhaust silencer with 10 dB(A) sound
attenuation
 Exhaust silencer with 30 dB(A) sound
attenuation
 Exhaust silencer with 40 dB(A) sound
attenuation
 Y-connection-pipe
■ Represents standard features
 Represents optional features
■ Modular base frame design
MASSE = 12.893,434 Kg*
6
/ // / MTU 16V4000 DS2250 / 3H / 50 Hz / 380V - 11kV
SCHWERPUNKT in Bezug auf den Koordinatenrahmen AS_KO_STD der Baugruppe 16V_1020:
X
28,856 mm
Y
87,205mm
Z
227,239mm
L=
B=
H=
5650.5413 (ohne Kühler)
1810.0000
2330.0000 (mit Standard Luftfiltern)
Weights and dimensions
MASSE = 16.358,056 Kg*
Drawing above for illustration purposes only, based an standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design.
__________________________________________________
See website for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
5090 x 1836 x 2330 mm
Weight (dry/less tank)
12893 kg
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.
Sound data
// Consult your local MTU Onsite Energy distributor for sound data.
Emissions data
// Consult your local MTU Onsite Energy distributor for emissions data.
Rating Definitions and conditions
Mission Critical Power ratings apply to installations served by a reliable utility source. The rating is applicable to varying loads
for the duration of a power outage. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with
ISO 8528-1, ISO-3046-1, BS 5514 and AS 2789. Average Load Factor: ≤ 85%. Operating hours/year: max. 1000.
// Deration factor:
Altitude: Consult your local MTU Onsite Energy Power Generation distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power Generation distributor for temperature derations.
Rated power is available up to 40°C and 100m above sea level.
Materials and specifications subject to change without notice.
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Subject to change. | 32310091 | Edition 01/15 | ENC 2015-11.
//