570 Surge Protective Device; Technical Specifications (SS-70100)

500 Series
570 Surge Protective Device
Submittal Specification
General Specifications
Maximum Continuous Operating Voltage
Short Circuit Current Rating (SCCR)
Operating Frequency Range
Suppression Technology
EMI/RFI Noise Rejection
Location Type
Nominal Discharge Current (In)
Standard Status Indication
120VAC 125%, all others 115%
200kAIC
47-63Hz
SAD/MOV Hybrid
63dB Max
Type 1 / Type 2
20kA
LED’s, Alarm, Relay Alarm Contacts, Built-in-Test
ANSI/UL 1449 Third Edition
UL 1283, cUL(Type 2 locations)
NEMA 4
10 Years Parts, 5 Years Labor
Certifications
Standard Enclosure
Warranty
Life Cycle Surge Testing (10kA, 20kV, IEEE Cat. C3)
Surge Rating
125kA Per Mode
160kA-200kA Per Mode
Per Mode
15,000
30,000
Per Phase
30,000
60,000
UL 1449 Third Edition, Type 1 VPRs
Source
Configuration
SA, YA
YC
L-N
L-G
L-L
N-G
700V
1000V
700V
1200V
1000V
1800V
700V
1000V
Model Number Configurator
Remote Monitoring Panel Option
_5 _7 _0 _ _ _ _ _A _ _ _G _1 _S
Configuration & Voltage
SA
YA
YC
DB
DF
Single Phase
3W+G
(L1,L2,N,G)
Three Phase
WYE, 4W+G
(L1,L2,L3,N,G)
Three Phase
Delta, 3W+G
(L1,L2,L3,G)
120/240VAC
120/208VAC,
127/220VAC
277/480VAC,
254/440VAC
12
16
20
37
220VAC,
230VAC, 240VAC
Surge Rating
125kA Per Mode
250kA Per Phase
160kA Per Mode
320kA Per Phase
200kA Per Mode
400kA Per Phase
375kA Per Mode
750kA Per Phase
Additional Accessories
N
R
Connection Type
Wire Compression
Lugs
Rotary Disconnect
Switch
S
Standard
X
Consult Factory for additional source
configurations, Surge Ratings, Monitoring
Options, Enclosure Ratings, Etc.
Harness Length
6 Feet
10 Feet
20 Feet
Monitoring Option
Example Model #: 570YC20ARTG1X59
Red & Green LED’s, Surge Counter, Audible
Alarm, Alarm Enable & Disable feature, 2
sets of Relay Alarm Contacts, Built-in-Test
200kA (“20”) & 375kA (“37”)
D
Dual Counter - “C” Monitoring option with
voltage Surge & SWELL Counters
Active Surge Monitor
See publication SL-70109, TS-70109
0.44”
[11.1]
For all applications requiring CUL approvals,
change the SPD model number from a UL
Type 1 (570xxxxxxxx1x) to a UL Type 2
(570xxxxxxxx2x)
Active Surge Monitor
A Web-Based Power Quality Monitor
integrated within a Surge Protection Device
Surge Connection
AxB
C
D
Wt
Rating
Type
Wire Lug 16” x 12” 17.25” 9.5” 35 lb.
(N)
(406 x 305) (438) (241) (15.9 kg)
“12”




Disconnect 16” x 16” 17.25” 10”
45 lb.
(R)
(406 x 406) (438) (254) (20.4 kg)
Wire Lug 16” x 16” 17.25” 10”
45 lb.
(N)
(406 x 406) (438) (254) (20.4 kg)
Disconnect 20” x 16” 21.25” 10”
55 lb.
(R)
(508 x 406) (540) (254) (24.9 kg)
100 Emerson Parkway
Binghamton, NY 13905
P (607) 721 8840
P (800) 288 6169
F (607) 722 8713
E [email protected]
CUL Approvals
Available Option for ALL units
T
Dimensional Information
“16”
&
“20”
Model Accessory
“X27”
“X57”
“X59”
125kA (“12”) & 160kA (“16”)
C
480VAC
constructed with the monitoring system on a
remote panel - Perfect for custom installations.
Real-Time Measurements
Event Logging with Time/Date Stamp
Embedded Web Page
Ethernet, MODBUS, RS-485
Communications
 SPD Health Status - % Protection remaining
 LCD Display
A C
C
A
D
D
B
B
*9.0”
9.0”
(229)
[229]
* Enclosure depth changes to 10.0” [254] when the
“Active Surge Monitor” option is selected.
SS-70100 Rev 2 9-15