Datenblatt

For more information, please visit the product page.
date
05/06/2015
page
1 of 4
SERIES: PSE-600 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
FEATURES
up to 600 W continuous power
1U x 2U form factor
I2C communication for monitoring and control
redundant (N+1) operation
blind mate connections for hot-swap
power factor correction
3.3 Vdc (0.5 A) standby voltage
DROOP current sharing or forced current sharing (optional)
single I/O connector for AC input, DC output and signals
remote on/off control, power good signal
efficiency up to 90%
o
of N
C
rt
.
T
Rheinla
nd
UV
, I
nc
•
•
•
•
•
•
•
•
•
•
•
h A
ca
meri
US
MODEL
PSE-600-48
Notes:
output
voltage
output
current
output
power
ripple
and noise
efficiency1
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
typ
(%)
48
12.5
600
480
90
1. At 230 Vac input.
PART NUMBER KEY
PSE-600 - 48 - CXX
Base Number
Output Voltage
cui.com
Reserved for Custom
Configurations
For more information, please visit the product page.
CUI Inc │ SERIES: PSE-600 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 05/06/2015 │ page 2 of 4
INPUT
parameter
conditions/description
min
voltage
typ
90
frequency
50
current
at 90 Vac, full load
inrush current
half cycle, cold start, 25°C
at 115 Vac, 60 Hz
at 230 Vac, 50 Hz
leakage current
power factor correction
0.95
0.98
min
typ
max
units
264
Vac
60
Hz
8.25
A
20
40
A
A
1.5
mArms
max
units
OUTPUT - V1 (MAIN OUTPUT)
parameter
conditions/description
total regulation
±3
transient response
25% step load, 1A/µs slew rate, recovery to 1%
within 1 ms
hold-up time
at full load
in redundant operation
%
3
12
20
%
ms
ms
OUTPUT - V2 (STANDBY OUTPUT)
parameter
conditions/description
min
output voltage
typ
max
3.3
output current
0
ripple and noise
total regulation
units
Vdc
0.5
A
33
mVp-p
±2.5
%
STATUS & CONTROL
parameter
conditions/description
I2C interface
SCL 100 kHz clock rate, SDA data line
remote sense
main output
remote enable
“active low” enables main output, last-mate/
first-break enable pin
current share
droop share; active current share option
status
AC OK, DC OK and OTP_OK (open collector, active
“low” = OK); and PS_PRESENT
LED indicator
AC OK & DC OK indicators
min
typ
max
units
min
typ
max
units
60
Vdc
%
120
%
max
units
PROTECTIONS
parameter
conditions/description
over voltage protection
V1
V2
over current protection
latching, shutdown after 2 s
over temperature protection
output shut down, auto recovery
115
SAFETY & COMPLIANCE
parameter
conditions/description
min
safety approvals
cTUVus UL60950-1, CE (LVD)
emissions
FCC 15 Sub Part J, Class A, EN55022 Class A
harmonic compliance
EN61000-3-2 Class A
surges (mains)
IEC/EN 61000-4-5
voltage dips/interruptions
IEC/EN 61000-4-11
cui.com
typ
For more information, please visit the product page.
CUI Inc │ SERIES: PSE-600 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 05/06/2015 │ page 3 of 4
SAFETY & COMPLIANCE (CONTINUED)
parameter
conditions/description
MTBF
as per Telcordia SR332, 40°C, full load
min
RoHS
2011/65/EU
typ
max
500,000
units
hours
ENVIRONMENTAL
parameter
conditions/description
min
operating temperature
storage temperature
max
units
0
typ
55
°C
-40
85
°C
max
units
MECHANICAL
parameter
conditions/description
min
dimensions
10.00 x 3.30 x 1.60 (254 x 83.8 x 40.6 mm)
cooling / airflow
integral high performance 38 mm fan, inlet at
face; exhaust at connector
input / output connector
FCI P/N 51939-420LF
mates with FCI P/N 51915-192LF
hot-swap capability
fully hot-swappable, blind mate connector
typ
inches
MECHANICAL DRAWING
units: inches [mm]
tolerance:
X.XX ±0.02 [0.50]
X.XXX ±0.010 [0.25]
INPUT/OUTPUT CONNECTOR
Pins
Function
Pins
Function
Pins
Function
Pins
Function
Pins
Function
Pins
Function
Pins
Function
P1
+48 V
A1
+V1 Sense
A2
EEPROM A0
A31
N/C
A4
AC OK
A5
Signal Return
A6
+3.3 VSB
Return
P2
-48 V
B1
-V1 Sense
B2
EEPROM A1
B31
N/C
B4
DC OK
B5
EEPROM
Clock SCL
B6
Reserved
P3
FG
C1
ISHARE
C2
EEPROM A2
C31
N/C
C4
PS_PRESENT
C5
EEPROM
Data (SDA)
C6
Reserved
P4
AC
Neutral
D1
Reserved
D2
N/C
D31
N/C
D4
OTP OK
D5
+3.3 VSB
D6
Enable
(short pin)
P5
AC Line
--
--
--
--
--
--
--
--
--
--
--
--
Note:
1. POE Isolation Barrier - No traces to be routed between these pins and any others.
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PSE-600 │ DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
date 05/06/2015 │ page 4 of 4
REVISION HISTORY
rev.
1.0
description
date
initial release
05/06/2015
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
[email protected]
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.