SM AC Datasheet

SM AC – EnergyMaster™
Site Monitoring
for Business-Critical Continuity™
Monitoring
Description
Features and Benefits
The Supervision Module for AC (SM AC) provides detailed information and alarms
regarding the condition and status of the telecom site's AC supply and backup
generator. Based on this information, site visits and maintenance related to the AC and
standby generator can be optimized to save both time and money, especially for sites
located remotely.
Lower maintenance cost related to AC
units
Higher availability thanks to automated
standby alternator tests and AC alarms
The SM AC is an easy-to-install monitoring device connected to the advanced control
unit (ACU) of the DC power system, and the AC units it supervises. It is designed for
measuring AC voltages and currents, and providing calculations of powers and total
harmonic distortions. SM AC is also designed for remotely testing start-functions of
standby generator.
The information and alarms, regarding the AC units on a specific site, can be monitored
or checked by means of a simple web browser or specific management software. No
additional software is needed and login to monitor the site is password protected.
(Examples of alarms provided by means of the control unit of the power system are
specified in the datasheet and/or manual for the specific unit.)
SM AC – EnergyMaster™
SM AC – EnergyMaster™
Technical Specifications, SM AC
General
Power Supply
Power Consumption
Temperature Range
EMC
Safety
Approvals
18-60 VDC
6W
0℃ to +60℃ / 32℉ to +140℉
EN 300 386 class B, FCC part 15 class B
IEC 60950, EN 60950, UL 60950
CE, UL and designed to meet NEBS level 3
Mechanical Data
Dimensions (H×W×D)
Standard Installation Methods
Weight
150×400×43 mm / 5.9×15.7×1.7 inch
Rack and wall mounted
< 2.7 kg / 5.95 lbs
Inputs/Outputs
External Communication
Digital Inputs
12 Digital Inputs
Analog Inputs
3 Mains/Phase Voltage
3 Phase Current
1 Battery Voltage
1 Temperature
1 Network Frequency
3 Apparent Powers
3 Active Powers
3 Reactive Powers
3 Current Distortions
Energy
Digital Outputs
4 Relay Outputs
RS232 / RS485
Alarms/Events
0-600 VAC, 0-346 VAC
0-5 A external current transformer
0-36 V DC
-25℃ to +80℃ / -13℉ to +176℉
45-65 Hz
kVA calculated in software
kW calculated in software
kVA calculated in software
0-100% calculated in software, THD (Total Harmonic Distortion)
kWh calculated in software
ABBREVIATIONS
PSTN
Public Switched Telephone Network,
an ordinary telephone line
IE
Internet Explorer
ENEC
EnergyMaster™ Emerson Network
Energy Center, multi-platform, multiuser, distributed multi-language
web environment for monitoring of
Emerson Network Power DC, HPAC
and UPS equipment
PSEM
Power Supply and Environment
Monitoring system
ACU
Advanced Control Unit
PSU
Power Supply Unit (AC/DC converter/
rectifier)
24VDC / 250VAC, 5A
System Layout
ENEC
SM DU Supervision Module for additional
alarms in extension cabinets
SM AC
Supervision Module for Alternating
Current
SM BAT Supervision Module for Battery
Backup
SM IO
SM DU
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity™.
www.emersonnetworkpower.com
www.emersonnetworkpower.com/energysystems
www.DCpowerefficiency.com
Supervision Module for generic
monitoring
AC Power
Embedded Power
Precision Cooling
Connectivity
Infrastructure Management & Monitoring
Racks & Integrated Cabinets
DC Power
Outside Plant
Services
Embedded Computing
Power Switching & Controls
Surge Protection
Business-Critical Continuity, Emerson Network Power
and the Emerson Network Power logo are trademarks
and service marks of Emerson Electric Co.
©2010 Emerson Electric Co.
Emerson Network Power reserves the right to alter without notice the specification, design or conditions of supply of any product or service.
2010.7