Omron H7CX-A11UD Multifunction preset counter Datasheet

Multifunction Preset Counter
H7CX
Counters
• Highly visible display with backlit negative transmissive LCD.
• Programmable PV color to visually alert when output status
changes (screw terminal block models).
• Intuitive setting enabled using ergonomic up/down digit keys (4digit models) and DIP switch.
• Configurable as 1-stage counter, 2-stage counter, total and preset counter, batch counter, dual counter, or tachometer. (Configurability varies with model.)
• PNP/NPN switchable input.
• Finger-safe terminals (screw terminal block models).
• Meets a variety of mounting requirements:
Screw terminal block models, and pin-style terminal models.
• NEMA4/IP66 compliance.
• Six-language instruction manual.
Contents
Model Number Structure.............................................................. C-88
Ordering Information.................................................................... C-88
Specifications............................................................................... C-89
Connections................................................................................. C-93
Nomenclature .............................................................................. C-98
Dimensions .................................................................................. C-99
Precautions.................................................................................. C-103
Operating Procedures.................................................................. C-106
Setting Procedure Guide ....................................................... C-106
Operating Procedures (Counter Function) ............................ C-107
Operating Procedures (Tachometer Function) ...................... C-118
Operation in Configuration Selection Mode........................... C-124
Additional Information .................................................................. C-125
Multifunction Preset Counter
H7CX
C-87
Model Number Structure
■ Model Number Legend
H7CX-A@@@@@@
1 2 3 4 5 6
4. Output type
None: Contact output or contact and transistor in combination
S:
Transistor output
5. Supply voltage/external power supply
None: 100 to 240 VAC at 50/60 Hz with 12 VDC power supply
D:
12 to 24 VDC without external power supply
D1: 12 to 24 VDC or 24 VAC at 50/60 Hz with 12 VDC power
supply
6. Case color
None: Black
G:
Light gray (Munsell 5Y7/1): Produced upon request.
1. External connection
None: Screw terminals
11: 11-pin socket
2. No. of digits
None: 6 digits
4:
4 digits
3. Stage setting
None: 1-stage setting
U:
Factory-set to 1-stage setting
W:
Factory-set to 2-stage setting
Ordering Information
■ List of Models
Supported configurations
Sensor
power
supply
12 VDC
None
Output type
• 1-stage counter
• 1-stage counter with total counter
Supply voltage
• 1-stage counter
• 2-stage counter
• 1-stage counter with total
counter
• 1-stage counter with batch
counter
• Dual counter (addition/subtraction)
• Tachometer
11-pin socket
Screw terminal
1-stage
Contact output
1-stage
(See note.)
2-stage
6 digits
4 digits
6 digits
4 digits
6 digits
6 digits
4 digits
H7CX-A11@
H7CX-A114@
H7CX-A@
H7CX-A4@
H7CX-AU@
H7CX-AW@
H7CX-A4W@
100 to 240 VAC
H7CX-A11
H7CX-A114
H7CX-A
H7CX-A4
---
H7CX-AW
H7CX-A4W
12 to 24 VDC/
24 VAC
H7CX-A11D1
H7CX-A114D1
---
---
---
H7CX-AWD1
---
Contact and
transistor output
100 to 240 VAC
---
---
---
---
H7CX-AU
---
---
12 to 24 VDC/
24 VAC
---
---
---
---
H7CX-AUD1
---
---
Transistor output
100 to 240 VAC
H7CX-A11S
H7CX-A114S
H7CX-AS
H7CX-A4S
---
H7CX-AWS
---
12 to 24 VDC/
24 VAC
H7CX-A11SD1
---
---
---
H7CX-AUSD1
H7CX-AWSD1
---
12 to 24 VDC
---
---
H7CX-AD
H7CX-A4D
---
---
---
---
---
H7CX-ASD
H7CX-A4SD
---
H7CX-AWSD
H7CX-A4WSD
Contact output
Transistor output
Note: Can be used as a 2-stage counter. In this case, each output can be flexibly allocated to either stage 1 or 2.
■ Accessories (Order Separately)
Name
Flush Mounting Adapter (See note 1.)
Waterproof Packing (See note 1.)
Models
Y92F-30
Y92S-29
Track Mounting/Front Connecting
Socket
11-pin
11-pin, finger-safe type
P2CF-11-E
Back Connecting Socket
11-pin
P3GA-11
11-pin, finger-safe type
Hard Cover
Mounting Track
P2CF-11
P3GA-11 with Y92A-48G (See note 2.)
Y92A-48
Soft Cover
Y92A-48F1
50 cm (l) × 7.3 mm (t)
PFP-50N
1 m (l) × 7.3 mm (t)
PFP-100N
1 m (l) × 16 mm (t)
PFP-100N2
End Plate
PFP-M
Spacer
PFP-S
Note: 1. Supplied with screw-terminal models (i.e., excluding H7CX-A11@/-A114@ models).
2. Y92A-48G is a finger-safe terminal cover attached to the P3GA-11 Socket.
C-88
• 1-stage counter
• 2-stage counter
• 1-stage counter
with total counter
• 1-stage counter
with batch counter
• Dual counter (addition only)
Multifunction Preset Counter H7CX
Specifications
■ Ratings
H7CX-A4@
H7CX-A@
Preset counter
Supported
configurations
1-stage counter, 1-stage counter with total counter (selectable)
Rated supply voltage
(See note 1.)
100 to 240 VAC (50/60 Hz), 12 to 24 VDC
H7CX-A114@
H7CX-A11@
Counters
Item
Classification
100 to 240 VAC (50/60 Hz)
24 VAC (50/60 Hz)/12 to 24 VDC
Operating voltage range 85% to 110% of rated supply voltage (90% to 110% at 12 VDC)
Power consumption
Approx. 9.2 VA at 264 VAC
Approx. 7.2 VA at 26.4 VAC
Approx. 3.7 W at 12 VDC
Mounting method
Flush mounting
Flush mounting, surface mounting, or DIN track mounting
External connections
Screw terminals
11-pin socket
Terminal screw
tightening torque
0.5 N·m max.
---
Display
7-segment, negative transmissive LCD;
PV
11.5-mm-high characters, red or 9-mm-high characters, red or
green (programmable)
green (programmable)
SV
6-mm-high characters, green
6 digits (−99,999 to 999,999)
SV range: −99,999 to 999,999
(See note 2.) or 0 to 999,999
11.5-mm-high characters, red
9-mm-high characters, red
4 digits (−999 to 9,999)
SV range: 0 to 9,999
6 digits (−99,999 to 999,999)
SV range: −99,999 to 999,999
(See note 2.) or 0 to 999,999
Digits
4 digits (−999 to 9,999)
SV range: 0 to 9,999
Max. counting speed
30 Hz or 5 kHz (selectable, ON/OFF ratio 1:1), common setting for CP1 and CP2
Input modes
Increment, decrement, command, individual, and quadrature
Input signals
CP1, CP2, reset, and total reset
Input method
No-voltage input/voltage input (switchable)
No-voltage input
ON impedance: 1 kΩ max. (Leakage current: 5 to 20 mA at 0 Ω)
ON residual voltage: 3 V max.
OFF impedance: 100 kΩ min.
Voltage input
High (logic) level: 4.5 to 30 VDC
Low (logic) level: 0 to 2 VDC (Input resistance: approx. 4.7 kΩ)
Reset input
Minimum reset input signal width: 1 or 20 ms (selectable), common setting for all inputs
Reset system
External, manual, and automatic reset (internal according to C, R, P, and Q mode operation)
Output modes
N, F, C, R, K-1, P, Q, A
One-shot output time
0.01 to 99.99 s
Output type
Contact type: SPDT
Transistor type: 1 transistor
Control output
Contact output:
3 A at 250 VAC/30 VDC, resistive load (cosφ=1)
Minimum applied load: 10 mA at 5 VDC (failure level: P, reference value)
Transistor output:
NPN open collector, 100 mA at 30 VDC
Residual voltage: 1.5 VDC max. (approx. 1 V)
Leakage current: 0.1 mA max.
N, F, C, R, K-1, P, Q, A,
K-2, D, L
N, F, C, R, K-1, P, Q, A
N, F, C, R, K-1, P, Q, A,
K-2, D, L
NEMA B300 Pilot Duty, 1/4 HP 3-A resistive load at 120 VAC, 1/3 HP 3-A resistive load at 240 VAC
External power supply
12 VDC (±10%), 100 mA (except for H7CX-A@D models)
Refer to Precautions for details.
Key protection
Yes
Prescaling function
Yes (0.001 to 9.999)
Decimal point
adjustment
Yes (rightmost 3 digits)
Sensor waiting time
250 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.)
Memory backup
EEPROM (overwrites: 100,000 times min.) that can store data for 10 years min.
Ambient temperature
Operating:
Storage:
Ambient humidity
25% to 85%
Case color
Black (N1.5), light gray (Munsell 5Y7/1, produced upon request)
Attachments
Waterproof packing, flush mounting adapter
Yes (0.001 to 99.999)
Yes (0.001 to 9.999)
Yes (0.001 to 99.999)
−10 to 55°C (−10 to 50°C if counters are mounted side by side) (with no icing or condensation)
−25 to 65°C (with no icing or condensation)
None
Note: 1. Permissible ripple: 20% (p-p) max.
2. Only when the following modes are selected.
Input mode: command, individual, or quadrature; output mode: K-2, D, or L
Multifunction Preset Counter
H7CX
C-89
■ Ratings (contd.)
Item
H7CX-A4W@
H7CX-AW@
H7CX-AU@
Classification
Preset counter
Supported configurations
1-stage counter, 2-stage counter, 1-stage 1-stage counter, 2-stage counter, 1-stage counter with total counter, 1-stage counter with batch
counter with total counter, 1-stage counter counter, dual counter (addition/subtraction), tachometer (selectable)
with batch counter, dual counter (addition
only) (selectable)
Rated supply voltage (See note 1.)
100 to 240 VAC (50/60 Hz),
12 to 24 VDC
Operating voltage range
85% to 110% of rated supply voltage (90% to 110% at 12 VDC)
Power consumption
Approx. 9.2 VA at 264 VAC
Approx. 7.2 VA at 26.4 VAC
Approx. 3.7 W at 12 VDC
Mounting method
Flush mounting
External connections
Screw terminals
Terminal screw tightening torque
0.5 N·m max.
Display
7-segment, negative transmissive LCD
PV
11.5-mm-high characters, red or green
(programmable)
SV
6-mm-high characters, green
Preset counter/tachometer
100 to 240 VAC (50/60 Hz),
24 VAC (50/60 Hz)/12 to 24 VDC,
12 to 24 VDC
9-mm-high characters, red or green (programmable)
Digits
4 digits (−999 to 9,999)
SV range: 0 to 9,999
Input signals
CP1, CP2, reset 1, and reset 2
Input method
No-voltage input/voltage input (switchable)
No-voltage input
ON impedance: 1 kΩ max. (Leakage current: 5 to 20 mA at 0 Ω)
ON residual voltage: 3 V max.
OFF impedance: 100 kΩ min.
Voltage input
High (logic) level: 4.5 to 30 VDC
Low (logic) level: 0 to 2 VDC (Input resistance: approx. 4.7 kΩ)
Counter
Tachometer
100 to 240 VAC (50/60 Hz),
24 VAC (50/60 Hz)/12 to 24 VDC
6 digits (−99,999 to 999,999 or 0 to 999,999 when using as Tachometer)
SV range: −99,999 to 999,999 (See note 2.) or 0 to 999,999
Max. counting speed
30 Hz or 5 kHz (selectable, ON/OFF ratio 1:1), common setting for CP1 and CP2
Input mode
Increment, decrement, command, individual, and quadrature
Reset input
Minimum reset input signal width: 1 or 20 ms (selectable), common setting for all inputs
Reset system
External, manual, and automatic reset (internal according to C, R, P, and Q mode operation)
Output modes
N, F, C, R, K-1, P, Q, A
One-shot output time
0.01 to 99.99 s
Pulse measurement
method
---
Max. counting speed
---
30 Hz or 10 kHz (selectable)
Measuring ranges
---
30 Hz: 0.01 to 30.00 Hz
10 kHz: 0.01 Hz to 10 kHz
N, F, C, R, K-1, P, Q, A, K-2, D, L, H
Periodic measurement (Sampling period: 200 ms)
Measuring accuracy
---
±0.1% FS ±1 digit max. (at 23 ±5°C)
Output modes
---
HI-LO, AREA, HI-HI, LO-LO
Auto-zero time
---
0.1 to 99.9 s
Startup time
---
0.0 to 99.9 s
Average processing
---
OFF/2/4/8 times
Output type
H7CX-A4W/-AW/-AWD1: SPDT (OUT2) and SPST-NO (OUT1)
H7CX-A4WSD/-AWS/-AWSD/-AWSD1: 2 transistors
Control output
Contact output:
3 A at 250 VAC/30 VDC, resistive load (cosφ=1)
Minimum applied load: 10 mA at 5 VDC (failure level: P, reference value)
Transistor output:
NPN open collector, 100 mA at 30 VDC
Residual voltage: 1.5 VDC max. (approx. 1 V)
Leakage current: 0.1 mA max.
H7CX-AU/-AUD1: SPDT and 1 transistor
H7CX-AUSD1: 2 transistors
(Output allocation possible)
NEMA B300 Pilot Duty, 1/4 HP 3-A resistive load at 120 VAC, 1/3 HP 3-A resistive load at 240 VAC
External power supply
12 VDC (±10%) 100 mA (except for H7CX-A@D models)
Refer to Precautions for details.
Key protection
Yes
Prescaling function
Yes (0.001 to 9.999)
Decimal point adjustment
Yes (rightmost 3 digits)
Sensor waiting time
250 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.)
Memory backup
EEPROM (overwrites: 100,000 times min.) that can store data for 10 years min.
Ambient temperature
Operating:
Storage:
Ambient humidity
25% to 85%
Case color
Black (N1.5), light gray (Munsell 5Y7/1, produced upon request)
Attachments
Waterproof packing, flush mounting adapt- Waterproof packing, flush mounting adapter, labels for counter/tachometer DIP switch settings
er
Yes (0.001 to 99.999)
−10 to 55°C (−10 to 50°C if counters are mounted side by side) (with no icing or condensation)
−25 to 65°C (with no icing or condensation)
Note: 1. Permissible ripple: 20% (p-p) max.
2. Only when the following modes are selected.
- Input mode: command, individual, or quadrature; output mode: K-2, D, L, or H
- Dual count calculating mode: SUB; output mode: K-2, D, L, or H in dual counter operation
C-90
Multifunction Preset Counter H7CX
■ Characteristics
H7CX
100 MΩ min. (at 500 VDC) between current-carrying terminal and exposed non-current-carrying metal parts, and between non-continuous contacts
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts
2,000 VAC (for 100 to 240 VAC), 50/60 Hz for 1 min between power supply and input circuit (1,000 VAC for 24 VAC/
12 to 24 VDC)
1,000 VAC (for H7CX-@SD/-@SD1), 50/60 Hz for 1 min between control output, power supply, and input circuit
(2,000 VAC for models other than H7CX-@SD/-@SD1)
1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Impulse withstand
voltage
3 kV (between power terminals) for 100 to 240 VAC, 1 kV for 24 VAC/12 to 24 VDC and 12 to 24 VDC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC,
1.5 kV for 24 VAC/12 to 24 VDC and 12 to 24 VDC
Noise immunity
±1.5 kV (between power terminals) for 100 to 240 VAC and 24 VAC/12 to 24 VDC, ±480 V for 12 to 24 VDC
±600 V (between input terminals)
Square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity
Destruction: 15 kV
Malfunction: 8 kV
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm single amplitude, four cycles each in three directions (8 minutes per cycle)
Malfunction: 10 to 55 Hz with 0.35-mm single amplitude, four cycles each in three directions (8 minutes per cycle)
Shock resistance
Destruction: 294 m/s2 each in three directions
Malfunction: 98 m/s2 each in three directions
Life expectancy
Mechanical: 10,000,000 operations min.
Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load)
See Life-test Curve on page 92.
Approved safety
standards
(See note 1.)
UL508/Listing, CSA C22.2 No. 14, conforms to EN61010-1 (Pollution degree 2/overvoltage category II)
Conforms to VDE0106/P100 (finger protection).
EMC
(EMI)
Emission Enclosure:
Emission AC mains:
(EMS)
Immunity ESD:
Degree of protection
Panel surface: IP66 and NEMA Type 4 (indoors) (See note 2.)
Weight
Approx. 140 g
EN61326
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61326
EN61000-4-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:
EN61000-4-3:
10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);
10 V/m (Pulse-modulated, 900 MHz ±5 MHz) (level 3)
Immunity Conducted Disturbance: EN61000-4-6:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
EN61000-4-4:
2 kV power-line (level 3);
1 kV I/O signal-line (level 4)
Immunity Surge:
EN61000-4-5:
1 kV line to lines (power and output lines) (level 2);
2 kV line to ground (power and output lines) (level 3)
Immunity Voltage Dip/Interruption EN61000-4-11: 0.5 cycle, 100% (rated voltage)
Note: 1. To meet UL listing requirements with the H7CX-A11@ models, an OMRON P2CF-11-@ or P3GA-11 Socket must be mounted on the
H7CX. Otherwise, H7CX-A11@ models are considered to meet UL508 recognition requirements.
2. A waterproof packing is necessary to ensure IP66 waterproofing between the H7CX and installation panel.
Multifunction Preset Counter
H7CX
C-91
Counters
item
Insulation resistance
■ Life-test Curve (Reference Values)
Resistive Load
Inductive Load
1,000
No. of operations (×103)
No. of operations (×103)
1,000
700
500
300
30 VDC (cosφ=1)
250 VAC (cosφ=1)
700
500
300
30 VDC (L/R=7 ms)
100
100
70
70
250 VAC cosφ=0.4
50
50
0
1
2
3
0
4
1
2
Load current (A)
3
4
Load current (A)
Reference: A current of 0.15 A max. can be switched at 125 VDC (cosφ=1) and current of 0.1 A max. can be switched if L/R=7 ms. In both cases,
a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P).
■ Inrush Current (Reference Values)
Model
H7CX-A11/-AW
Voltage
Applied voltage Inrush current (peak value)
0.7 ms
H7CX-A11D1/-AWD1 24 VAC/12 to 24 VDC 26.4 VAC
10.4 A
1.2 ms
H7CX-AD
6.0 A
1.2 ms
12 to 24 VDC
264 VAC
Time
5.8 A
C-92
100 to 240 VAC
26.4 VDC
Multifunction Preset Counter H7CX
Connections
■ Block Diagram
(Basic
insulation)
Output circuit
(Basic
insulation)
Power supply
circuit
Counters
(See note.)
Display circuit
Internal control
circuit
Input circuit
Key switch
circuit
Note: All models except for H7CX-@D (models with 12 to 24-VDC power supplies) have basic insulation.
■ I/O Functions
Using as a Counter
Inputs
Outputs
CP1, CP2
• In general (except for dual counter mode)
Reads counting signals
Increment, decrement, command, individual, and quadrature inputs accepted.
• When used as a dual counter
Reads CP1 count signals with CP1 input and CP2 count signals with CP2 input.
Increment signals can be input.
Reset or Reset 1
• In general (except for dual counter mode)
Resets present value and outputs (OUT2 when using the batch counter). (See note 1.)
Counting cannot be performed during reset/reset 1 input.
The reset indicator is lit during reset input.
• When used as a dual counter
Resets the CP1 present value (to 0).
Counting for CP1 input cannot be performed during reset 1 input.
The reset indicator is lit during reset 1 input.
Total Reset or
Reset 2
(See note 2.)
• When used as a 1-stage/2-stage counter
Does not operate (Not used).
• When used as a total and preset counter
Resets the total count value.
Holds the total count value at 0 during total reset input.
• When used as a batch counter
Resets the batch count value and batch output (OUT1).
Holds the batch count value at 0 during reset 2 input.
• When used as a dual counter
Resets the CP2 present value.
Counting for CP2 input cannot be performed during reset 2 input.
OUT1, OUT2
Outputs take place according to designated output mode when corresponding preset is reached.
Note: 1. In increment mode or increment/decrement mode, the present value returns to 0; in decrement mode, the present value returns to the
set value with 1-stage models, and returns to set value 2 with 2-stage models.
2. The reset indicator will not be lit when the total reset or reset 2 input is ON.
Using as a Tachometer
Inputs
Outputs
CP1, CP2
Reads counting signals. (CP2 input is not used.)
Reset 1, Reset 2
Holds the measurement value and outputs. (Reset 2 input is not used.)
The reset indicator is lit during hold.
OUT1, OUT2
Outputs signals according to the specified output mode when a set value is reached.
Multifunction Preset Counter
H7CX
C-93
■ Terminal Arrangement
Confirm that the power supply meets specifications before use.
CP1
6
Total reset
10
CP2
CP1
Total reset
CP2
Reset
0V
Reset
H7CX-AD/-A4D
1-stage Contact Output
H7CX-A/-A4
1-stage Contact Output
7
8
9
10
0V
6
(−)
7
8
9
Sensor, etc.
Unused
(+) 12 VDC
11
Unused
12
Unused
13
11
5
1
Unused
Unused
12
13
External power
supply
1
2
3
4
2
3
4
5
OUT
OUT
(−)
(+)
Note: Terminals 1 and 6 are connected internally.
Total reset
6
CP1
10
CP2
0V
Reset
CP1
H7CX-ASD/-A4SD
1-stage Transistor Output
Total reset
CP2
Reset
H7CX-AS/-A4S
1-stage Transistor Output
7
8
9
10
0V
6
(−)
7
8
9
Sensor, etc.
Unused
(+) 12 VDC
11
Unused
12
Unused
13
11
5
1
Unused
Unused
12
13
External power
supply
1
2
3
4
2
3
4
OUT
5
OUT
(+)
(−)
Note: Terminals 1 and 6 are connected internally.
H7CX-A11/-A114/-A11D1/-A114D1
1-stage Contact Output
H7CX-A11S/-A114S/-A11SD1
1-stage Transistor Output
Reset
Reset
CP1
CP1
Internal circuit
CP2
0V
(−)
(+)
4
8
9
10
1 11
4
0V
(−)
(+)
8
3
2
Sensor, etc.
12 VDC
1 11
9
10
12 VDC
External power supply
External power supply
OUT
OUT
(−)
(+)
Note: Do not connect unused terminals as relay terminals.
C-94
Internal circuit
5 6 7
Total reset
3
2
Sensor, etc.
CP2
5 6 7
Total reset
Multifunction Preset Counter H7CX
(−)
(+)
10
6
(−)
8
9
10
Sensor, etc.
Sensor, etc.
(+)
(+) 12 VDC
External power
supply
7
0V
11
12
13
Counters
(−)
Reset 2
9
CP1
8
CP2
CP1
Reset 2
7
0V
6
Reset 1
CP2
H7CX-AWS/-AWSD1
2-stage Transistor Output
Reset 1
H7CX-AW/-A4W/-AWD1
2-stage Contact Output
12 VDC
11
OUT1
12
13
OUT1
External power
supply
1
2
3
4
1
5
2
3
5
(−)
(+)
9
10
Reset 2
8
CP1
CP1
Reset 2
7
CP2
CP2
H7CX-AUSD1
1 or 2-stage Transistor Output
Reset 1
H7CX-AWSD/-A4WSD
2-stage Transistor Output
(+)
Reset 1
(−)
4
OUT2
OUT2
7
8
9
10
0V
0V
6
6
(−)
Sensor, etc.
Unused
(+)
11
12
13
12 VDC
11
OUT1
12
13
OUT1 or 2
External power
supply
1
2
3
4
5
1
2
3
(−)
4
5
OUT 1 or 2
OUT2
(+)
Note: 1. Terminals 1 and 6 are connected internally.
2. Do not connect unused terminals as relay terminals.
(−)
(+)
Note: Each output can be flexibly allocated to
either stage 1 or 2 in function selection
mode.
Reset 1
CP2
CP1
Reset 2
H7CX-AU/-AUD1
1-stage Contact, 1-stage Transistor Output
7
8
9
10
0V
6
(−)
Sensor, etc.
(+)
12 VDC
External power
supply
11
1
12
2
3
13
4
OUT1 or 2
5
OUT 1 or 2
(−)
(+)
Note: Each output can be flexibly allocated to either
stage 1 or 2 by setting in function selection mode.
Multifunction Preset Counter
H7CX
C-95
■ Input Circuits
CP1, CP2, Reset/Reset 1, and Total Reset/Reset 2 Input
+14 V
1 kΩ
Internal
circuit
IN
Note: The circuit shown above is for no-voltage input (NPN input).
■ Input Connections
The inputs of the H7CX are no-voltage (short-circuit or open) inputs or voltage inputs.
No-voltage Inputs (NPN Inputs)
Open Collector
Voltage Output
H7CX-A@
H7CX-A11@
6
7
8
9
10
3
7
5
6
4
H7CX-A@
H7CX-A11@
6
7
8
9
10
3
7
5
6
4
Operates when the transistor turns ON.
Operates when the transistor turns ON.
No-voltage Input Signal Levels
No-contact input
Short-circuit level
Transistor ON
Residual voltage: 3 V max.
Impedance when ON: 1 KΩ max.
(The leakage current is 5 to 20 mA when the
impedance is 0 Ω.)
Open level
Transistor OFF
Impedance when OFF: 100 KΩ min.
Contact input
Use contact which can adequately switch
5 mA at 10 V.
Maximum applicable voltage: 30 VDC max.
Total reset/reset 2 input
DC Two-wire Sensor
CP1 input
CP2 input
Input
Reset/reset 1 input
0V
H7CX-A@
H7CX-A11@
6
7
8
9
10
3
7
5
6
4
Operates when the transistor turns ON.
Applicable Two-wire Sensor
Leakage current:1.5 mA max.
Switching capacity:5 mA min.
Residual voltage:3 VDC max.
Operating voltage:10 VDC
C-96
Multifunction Preset Counter H7CX
H7CX-A@
H7CX-A11@
Total reset/reset 2 input
CP1 input
CP2 input
Reset/reset 1 input
0V
Input
CP1 input
CP2 input
Reset/reset 1 input
0V
Input
CP1 input
CP2 input
Input
Reset/reset 1 input
0V
Total reset/reset 2 input
Sensor
Total reset/reset 2 input
PLC or
sensor
Contact Input
6
7
8
9
10
3
7
5
6
4
Operates when the contact turns ON.
Voltage Inputs (PNP Inputs)
No-contact Input
(NPN Transistor)
6
7
8
9
10
3
7
5
6
4
H7CX-A@
H7CX-A11@
6
7
8
9
10
3
7
5
6
4
Operates when the transistor turns ON.
Operates when the transistor turns OFF.
H7CX-A@
H7CX-A11@
6
7
8
9
10
3
7
5
6
4
Counters
Total reset/reset 2 input
CP1 input
CP2 input
Reset/reset 1 input
0V
Input
CP1 input
CP2 input
Reset/reset 1 input
0V
Input
CP1 input
CP2 input
Input
Reset/reset 1 input
0V
Total reset/reset 2 input
Sensor
Total reset/reset 2 input
Sensor
H7CX-A@
H7CX-A11@
Contact Input
No-contact Input
(PNP Transistor)
Operates when the contact turns ON.
Voltage Input Signal Levels
High level (Input ON):
Low level (Input OFF):
Maximum applicable voltage:
Input resistance:
4.5 to 30 VDC
0 to 2 VDC
30 VDC max.
Approx. 4.7 kΩ
Multifunction Preset Counter
H7CX
C-97
Nomenclature
Indicators
A Reset Indicator (Orange)
Lit when the reset input (1) or reset key
is ON.
B Key Protection Indicator (Orange)
C Control Output Indicator (Orange)
OUT:
One stage
OUT1, OUT2: Two stages
D Total Count Indicator
Lit when the total count value is
displayed.
E Batch Indicator
Lit when the batch count value is
displayed.
F Set Value 1, 2 Stage Indicator
G Present Value (Main Display)
Character height: 11.5 mm (6-digit: 9mm)
H Set Value (Sub-display)
Character height: 6 mm
Operation Keys
1
2
7
3
4
5
6
9
11
10
12
8
Front view of 4-digit model
I Mode Key
Used to switch mode and setting items.
J Reset Key
The operation of the reset function
depends on the configuration selected
as shown in the table below.
K Up Keys: 1 to 4
(6-digit models: 1 to 6)
L Down Keys: 1 to 4
Switches
M Key Protect Switch
1
(Factory setting) OFF
2
7
3
4
5
6
8
ON
N DIP Switch
9
11
10
Front view of 6-digit model
13
14
Reset Operation by Reset Key
Configuration
1-stage/2-stage
counter
Reset operation
Resets the present value and outputs.
Total and preset • Resets the present value and outputs.
counter
• When the total count value is displayed, resets
the present value, the total count value, and
outputs.
C-98
Multifunction Preset Counter H7CX
Batch counter
• Resets the present value and OUT2.
• When the batch count value is displayed,
resets the present value, the batch count
value, and outputs.
Dual counter
Resets the CP1 present value, CP2 present value, dual count value, and outputs.
Tachometer
Maintains the measured value and outputs (hold
function).
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■ Counter (without Flush Mounting Adapter)
Screw-terminal Models with External Power Supplies (Flush Mounting)
• H7CX-AW
• H7CX-AWS
• H7CX-A4W
• H7CX-AWD1
• H7CX-AWSD1
• H7CX-AU
• H7CX-AUD1
• H7CX-AUSD1
Counters
• H7CX-A
• H7CX-AS
• H7CX-A4
• H7CX-A4S
48×48
6
100
44.8×44.8
Note: M3.5 terminal screw (effective length: 6 mm)
Screw-terminal Models without External Power Supplies (Flush Mounting)
• H7CX-AD
• H7CX-ASD
• H7CX-A4D
• H7CX-A4SD
• H7CX-AWSD
• H7CX-AWSD
48×48
6
64
44.8×44.8
Note: M3.5 terminal screw (effective length: 6 mm)
11-pin Socket Models (Flush Mounting/Surface Mounting)
• H7CX-A11
• H7CX-A11S
• H7CX-A11D1
• H7CX-A11SD1
• H7CX-A114
• H7CX-A114S
• H7CX-A114D1
48×48
6
72.5
14.4
44.8×44.8
Multifunction Preset Counter
H7CX
C-99
■ Dimensions with Flush Mounting Adapter
Screw-terminal Models with External Power Supplies
Panel Cutouts
(Provided with Adapter and Waterproof Packing)
• H7CX-AW
• H7CX-AWS
• H7CX-A4W
• H7CX-AWD1
• H7CX-AWSD1
• H7CX-A
• H7CX-AS
• H7CX-A4
• H7CX-A4S
• H7CX-AU
• H7CX-AUD1
• H7CX-AUSD1
Panel cutouts are as
shown below.
(according to DIN43700).
Y92S-29 (provided)
Waterproof Packing
Panel
60 min.
Y92F-30 (provided)
Flush Mounting Adapter
45+0.6
−0
45+0.6
−0
60 min. 15 min.
(51)
58
48
7.5
98.5
Screw-terminal Models without External Power Supplies
(Provided with Adapter and Waterproof Packing)
• H7CX-AD
• H7CX-ASD
• H7CX-A4D
• H7CX-A4SD
• H7CX-AWSD
• H7CX-A4WSD
Y92S-29 (provided)
Waterproof Packing
58
Panel
Y92F-30 (provided)
Flush Mounting Adapter
Note: 1. The mounting panel thickness
should be 1 to 5 mm.
2. To allow easier operability, it is
recommended that Adapters are
mounted so that the gap between
sides with hooks is at least 15 mm
(i.e., so that the panel cutout interval
is at least 60 mm).
3. It is possible to mount counters
side by side, but only in the
direction without the hooks.
If they are mounted side-by-side,
water-resistant specifications
cannot be ensured.
(51)
n side by side mounting
A
48
7.5
A = (48n − 2.5)+10
62.5
11-pin Socket Models
With Y92A-48F1 attached.
A = {48n−2.5 + (n−1) x 4}+10
(Adapter and Waterproof Packing Ordered Separately)
• H7CX-A11
• H7CX-A11S
• H7CX-A11D1
• H7CX-A11SD1
• H7CX-A114
• H7CX-A114S
• H7CX-A114D1
With Y92A-48 attached.
A = (51n−5.5)+10
Y92S-29 (order separately)
Waterproof Packing
58
Panel Y92F-30 (order separately)
Flush Mounting Adapter
P3GA-11
(order separately)
Back Connecting
Socket
(51)
48
7.5
98.7
■ Dimensions with Front Connecting Socket
H7CX
-A11@
109.7
112
P2CF-11
Note: These dimensions vary with the kind of DIN track (reference value).
C-100
Multifunction Preset Counter H7CX
■ Accessories (Order Separately)
Note: All units are in millimeters unless otherwise indicated.
7.8
M3.5 x 7.5 sems
3
4.5
70 max.
Terminal Arrangement/
Internal Connections
(Top View)
35.4
Two, 4.5-dia.
holes
Counters
Track Mounting/Front Connecting Socket
P2CF-11
Eleven,
Surface Mounting Holes
Two, 4.5 dia. or two, M4
4
50 max.
31.2 max.
40±0.2
Note: Track mounting is also possible.
P2CF-11-E (Finger Safe Terminal Type)
Conforming to VDE0106/P100
Eleven,
M3.5 x 7.5 sems
4.5
5
7.8
3
1.2
70 max.
35.4
Two, 4.5-dia.
holes
4
40±0.2
50 max.
30
31.2 max.
Back Connecting Socket
P3GA-11
Terminal Arrangement/
Internal Connections
(Bottom View)
27 dia.
45
25.6
45
4.5
6.2
16.3
Note: Finger protection can be ensured by using in combination with the Y92A-48G Terminal Cover.
Finger Safe Terminal Cover
Conforming to VDE0106/P100
Y92A-48G
(Attachment for P3GA-11
Socket)
Twelve, 6.4-dia. holes
34
47.7 x 47.7
16.5
48 x 48
24.6 27.6
47.4
Multifunction Preset Counter
H7CX
C-101
Hard Cover
Y92A-48
Note: 1. Depending on the operating environment, the condition of
the Soft Cover may deteriorate, and it may shrink or become
harder. Therefore, it is recommended that the Soft Cover is
replaced regularly.
2. The H7CX’s panel surface is water-resistive (conforming to
IP66) and so even if drops of water penetrate the gaps between the keys, there will be no adverse effect on internal
circuits. If, however, there is a possibility of oil being present
on the operator’s hands, use the Soft Cover. The Soft Cover
ensures protection equivalent to IP54F against oil. Do not,
however, use the H7CX in locations where it would come in
direct contact with oil.
Soft Cover
Y92A-48F1
Flush Mounting Adapter
(provided with screw-terminal models)
Waterproof Packing
(provided with screw-terminal models)
Y92F-30
Y92S-29
Mounting Track
PFP-100N, PFP-50N
PFP-100N2
16
7.3±0.15
4.5
4.5
15 25
25
10
35±0.3
27±0.15
35±0.3
25 *
25
1,000 (500) 10
(see note)
15
1
25
25 15
25
25
10
1,000
27
24
1
10
Note: The values shown in parentheses are for the PFP-50N.
End Plate
PFP-M
Spacer
PFP-S
10
6.2
16
12
5
1.8
1
50
1.8
11.5
C-102
10 M4 x 8
pan head
screw
35.5 35.3
34.8
44.3
1.3
4.8
Multifunction Preset Counter H7CX
16.5
29.2
1.5
Precautions
■ Transistor Output
The service life of the output relays depends on the switching
capacity and switching conditions. Consider the actual application
conditions and use the product within the rated load and electrical
service life. Using the product beyond its service life may result in
contact deposition or burning.
The transistor output of the H7CX is isolated from the internal circuitry by a photocoupler, so the transistor output can be used as both
NPN and PNP output.
NPN output
Do not disassemble, repair, or modify the product. Doing so may
result in electric shock, fire, or malfunction.
Do not allow metal objects or conductive wires to enter the product.
Doing so may result in electric shock, fire, or malfunction.
Load
Load
+
+
Power for load
Power for load
The diode connected to the collector of the output transistor is used
to absorb inverted voltage that is generated when an inductive load is
connected to the H7CX.
■ External Power Supply
The capacity of the external power supply is 100 mA at 12 V. When
using a 24 VAC/12 to 24 VDC power supply, reduce the load with the
power supply voltage, as shown in the following diagram (DC power
supplies only).
(DC v ltage
PNP output
Counters
!Caution
Do not use the product in locations subject to flammable or explosive gases. Doing so may result in explosion.
Counter
ppl only)
Inductive load
Load current (mA)
+
Power for load
100
■ Changing the Set Values
When changing the set value during operation, because the H7CX
uses a constant read-in system, output will turn ON if the set value is
equal to the present value.
■ Operation with a Set Value and
Present Value of 0
20
If the set value and present value are both 0, output will turn ON.
Output will turn OFF during reset.
15
10.8
Power
pply vol age
C)
■ Power Supplies
Observe the following points when setting a prescale value.
When turning the power ON and OFF, input signal reception is possible, unstable, or impossible as shown in the diagram below.
Power
supply
Input
Impossible
0 to 1 s
Possible
Unstable
• Set the set value to a value less than {Maximum countable value −
Prescale value}.
Example: If the prescale value is 1.25 and the counting range is
0.000 to 999.999, set the set value to a value less than
998.749 (= 999.999 − 1.25).
ON
OFF
200 ms 0 to 90 ms 5 ms
■ Using the Prescaling Function
Impossible
Unstable
Turn the power ON and OFF using a relay with a rated capacity of 10
A minimum to prevent contact deterioration due to inrush current
caused by turning the power ON and OFF.
Apply the power supply voltage through a relay or switch in such a
way that the voltage reaches a fixed value immediately, otherwise
they may not be reset or a counter error may result.
Be sure that the capacity of the power supply is large enough, otherwise the counter may not start due to inrush current (reference value:
approx. 10 A, 1.2 ms at 26.4 VAC) that may flow for an instant when
the counter is turned ON.
Make sure that the fluctuation of the supply voltage is within the permissible range.
Make sure that the voltage applied is within the specified range, otherwise the internal elements of the counter may be damaged.
• If the set value is set to a value greater than this, output will not turn
ON.
Note: Output will turn ON, however, if a present value overflow occurs
(FFFFFF or FFFF).
• Setting the prescale value incorrectly may result in incorrect counting operation. Be sure to set the prescale value correctly.
■ DIP Switch Setting
Ensure that the power is turned OFF before changing DIP switch settings. Changing DIP switch settings with the power turned ON may
result in electric shock due to contact with terminals subject to high
voltages.
■ Power Failure Backup
All data is stored in the EEPROM when there is power failure. The
EEPROM can be overwritten more than 100,000 times. EEPROM is
overwritten when the power is turned OFF or when settings are
changed.
Multifunction Preset Counter
H7CX
C-103
■ Self-diagnostic Function
The following displays will appear if an error occurs.
Main display
Sub-display
Error
Output status
Correction method
Set value after
reset
No change
-----(----)
(See notes 1 and
2.)
Present value underflow
(See note 3.)
No change
Either press the reset key or turn ON
reset input.
No change
No change
ffffff
(ffff)
(See notes 1 and
2.)
Present value overflow
(See note 4.)
No change
Either press the reset key or turn ON
reset input. (See note 5.)
No change
CPU
OFF
Either press the reset key or reset the No change
power supply.
Not lit
e1
e2
Not lit
Memory error (RAM)
OFF
Reset the power supply.
e2
sum
Memory error (EEP)
(See note 6.)
OFF
Reset to the factory settings using the 0
reset key.
Note: 1.
2.
3.
4.
No change
The display for 4-digit models is given in parentheses.
Display flashes (1-second cycles).
Occurs when the present value or the total count value goes below −99,999 (−999 with 4-digit models).
Occurs when the present value (or measurement value) reaches 999,999 (9,999 with 4-digit models) under the following conditions:
• The output mode is K-2, D, L, or H.
• The H7CX is set for dual counter or tachometer operation.
5. Except when the H7CX is set for tachometer operation.
6. Includes the case where the EEPROM has reached its overwrite lifetime.
■ Response Delay Time When
Resetting (Transistor Output)
The following table shows the delay from when the reset signal is
input until the output is turned OFF.
(Reference values)
Minimum reset signal width
Output delay time
1 ms
0.8 to 1.2 ms
20 ms
15 to 25 ms
Actual measurements in N and K-2 modes.
(Reference values)
Control output type Maximum counting
speed
Output delay time
30 Hz
16.5 to 24.0 ms
5 kHz
3.7 to 5.6 ms
30 Hz
12.0 to 20.0 ms
5 kHz
0.2 to 0.55 ms
Note: The above times may vary slightly depending on the mode or
operating conditions.
■ Maximum Counting Speed for
Batch Counter
The maximum counting speed for batch counter operation is 5 kHz.
The batch counter counts the number of times the count reaches the
set value.
C-104
Pay attention to terminal polarity to ensure correct wiring.
Tighten the two mounting screws on the Adaptor. Tighten them alternately, a little at a time, so as to keep them at an equal tightness.
The following table shows the delay from when the present value
passes the set value until the output is produced.
Transistor output
Wiring input lines in the same conduit as power lines or other highvoltage lines may result in malfunction due to noise. Wire the input
lines separately, away from lines carrying high-voltages. In addition,
make the input wiring as short as possible and use shield lines or
metal wiring conduits.
■ Mounting
■ Output Delay Time
Contact output
■ Wiring
Multifunction Preset Counter H7CX
The H7CX’s panel surface is water-resistive (conforming to NEMA 4
and IP66). In order to prevent the internal circuit from water penetration through the space between the timer and operating panel, attach
a waterproof packing between the timer and installation panel and
secure the waterproof packing with the Y92F-30 Flush-mounting
Adapter.
0.5 to 1 mm
It is recommended that the space between
the screw head and the adapter should be
0.5 to 1 mm.
■ Operating Environment
X2/b
T
T/a
X1/a
X1
Counters
• Use the product within the ratings specified for submerging in water
and exposure to oil.
• Do not use the product in locations subject to vibrations or shocks.
Using the product in such locations over a long period may result in
damage due to stress.
• Do not use the product in locations subject to dust, corrosive
gases, or direct sunlight.
• Separate the input signal devices, input signal cables, and the
product from the source of noise or high-tension cables producing
noise.
• Separate the product from the source of static electricity when
using the product in an environment where a large amount of static
electricity is produced (e.g., forming compounds, powders, or fluid
materials being transported by pipe).
• Organic solvents (such as paint thinner), as well as very acidic or
basic solutions might damage the outer casing of the H7CX.
• Use the product within the ratings specified for temperature and
humidity.
• Do not use the product in locations where condensation may occur
due to high humidity or where temperature changes are severe.
• Store at the specified temperature. If the H7CX has been stored at
a temperature of less than -10°C, allow the H7CX to stand at room
temperature for at least 3 hours before use.
• Leaving the H7CX with outputs ON at a high temperature for a long
time may hasten the degradation of internal parts (such as electrolytic capacitors). Therefore, use the product in combination with
relays and avoid leaving the product as long as more than 1 month
with the output turned ON.
X1/a
X2
X
Auxiliary relay
(e.g., MY Relay)
• The load current must be within the rated current.
■ Insulation
• Specifications call for basic insulation between the power supply
and input terminals, between the power supply and output terminals, and between the input and output terminals. (The H7CX-A@D
is not insulated between the power supply and input terminals.)
• Input and output terminals are connected to devices without
exposed charged parts.
• Input and output terminals are connected to devices with basic
insulation that is suitable for the maximum operating voltage.
Multifunction Preset Counter
H7CX
C-105
Operating Procedures
■ Setting Procedure Guide
Setting for Counter Operation
(1-stage/2-stage Counter, Total and Preset Counter, Batch Counter, Dual Counter)
When Using Basic Settings Only
The settings can be performed easily with the DIP switch.
➡ For details on the setting methods, refer to page 21.
Basic Settings
•
•
•
•
•
•
Counting speed (30 Hz, 5 kHz)
Input mode (UP, DOWN)
Output mode (N, F, C, K-1)
One-shot output time (0.5 s, 0.05 s)(See note 2.)
Reset input signal width (20 ms, 1 ms)
NPN/PNP input mode (NPN, PNP)
When Using Settings Other than the Above
All the functions can be set with the operation keys.
➡ For details on the setting methods, refer to page 22.
Other Settings
1
2
3
4
5
6
7
8
ON
OFF
When Using Advanced Functions
Settings for advanced functions other than the basic
settings above can be performed with the operation keys.
➡ For details on the setting methods, refer to page 22.
Advanced Functions
• Input mode (UP/DOWN A, UP/DOWN B, UP/DOWN C)
• Output mode (R, P, Q, A, K-2, D, L, H)
• One-shot output time (except for 0.5 s and 0.05 s) (See note 2.)
•
•
•
•
•
•
•
Dual count calculating mode
Output 1 time (for 2-stage counter)
Decimal point position
Prescale value
Display color
Output allocation
Key protect level
Note: 1. At the time of delivery, the H7CX is set to the 1-stage counter (2-stage counter for H7CX-AW@/-A4W@ models) configuration.
2. Set to output 2 time when using as a 2-stage counter or batch counter.
Setting for Tachometer Operation
When Using Basic Settings Only
The settings can be performed easily with the DIP switch.
➡ For details on the setting methods, refer to page 33.
Basic Settings
•
•
•
•
Counting speed (30 Hz, 10 kHz)
Output mode (HI-LO, AREA, HI-HI, LO-LO)
Average processing (OFF, 2, 4, 8 times)
NPN/PNP input mode (NPN, PNP)
1
2
3
4
5
6
7
8
ON
OFF
When Using Advanced Functions
Settings for advanced functions other than the basic
settings above can be performed with the operation keys.
➡ For details on the setting methods, refer to page 34.
Advanced Functions
•
•
•
•
•
•
•
Decimal point position
Prescale value
Auto-zero time
Startup time
Display color
Output allocation
Key protect level
Note: At the time of delivery, the H7CX is set to the 2-stage counter (1-stage counter for H7CX-AU@ models) configuration.
C-106
Multifunction Preset Counter H7CX
■ Operating Procedures (Counter Function)
Settings for Basic Operations
Settings for basic functions can be performed with just the DIP switch.
1
2
3
4
5
6
7
Counters
Be sure to set pin 1 to ON.
8
ON
OFF
Note: All of the pins are factory-set to OFF.
Item
1
DIP switch settings enable/disable
2
3
4
OFF
ON
Disabled
Enabled
Counting speed
30 Hz
5 kHz
Input mode
UP (increment) DOWN (decrement)
Output mode
Refer to the table on the right.
Pin 4
5
6
Pin 5
OFF
One-shot output time
(See note.)
0.5 s
0.05 s
7
Reset input signal width
20 ms
1 ms
8
NPN/PNP input mode
NPN
PNP
Output mode
OFF
N
ON
OFF
F
OFF
ON
C
ON
ON
K-1
Note: Set to one-shot output 2 time when using as a 2-stage counter
or batch counter.
Easy Confirmation of Switch Settings Using Indicators
The ON/OFF status of the DIP switch pins can be
confirmed using the front display. For details, refer to page 124.
Note: 1. Be sure to set pin 1 of the DIP switch to ON. If it is set to OFF, the DIP switch settings will not be enabled.
2. Changes to DIP switch settings are enabled when the power is turned ON.
3. When setting input modes, output modes, or output times that cannot be set with the DIP switch, all of the settings have to be made using
the operation keys. For details on the setting methods, refer to page 108. When making settings using the operation keys, be sure to set
pin 1 of the DIP switch to OFF.
Switching to Total and Preset Counter, Batch Counter, and Dual Counter Operation (See note.)
The H7CX is factory-set to the 1-stage
counter (2-stage counter for H7CX-AW@/A4W@ models) configuration. To change to
a different configuration, use the procedure
shown on the right. For details, refer to
page 39.
Power ON
Configuration selection mode
Note: This includes changing to the 2stage counter (or 1-stage counter)
configuration.
MODE
+
Run mode
1
Hold down for
1 s min. (See note.)
Note: The MODE key must be pressed before the
Select the configuration using the
(1-stage
counter)
(2-stage (Total and
counter) preset counter)
and
keys (
(Batch
counter)
1
key.
key with 6-digit models).
(Dual
counter)
(Tachometer)
Note: The configurations that can be selected vary with the model.
Advanced-Function Settings
After making DIP switch settings for basic operations, advanced functions (see note) can be added using the operation keys.
For details, refer to page 22.
Note: Advanced functions consist of the dual count calculating mode, output 1 time (for 2-stage counter), decimal point position,prescale value, display
color, output allocation, and key protect level.
Multifunction Preset Counter
H7CX (Counter Function)
C-107
Settings for All Functions
Note: At the time of delivery, the H7CX is set to the 1-stage counter (2-stage counter for H7CX-AW@/-A4W@ models) configuration. When using
as a 2-stage (or 1-stage) counter, total and preset counter, batch counter, or dual counter, switch to the configuration using the procedure
given on page 124.
Settings that cannot be performed with the DIP switch are performed with the operation keys.
Power ON
For details on operations in run mode, refer to page 25.
3 s min.
See note 2.
3 s min.
The characters displayed in reverse video are the default settings.
When performing settings with operation keys only, set pin1 of the DIP switch to OFF (factory setting).
If pin 1 of the DIP switch is set to ON, the setting items indicated by
will not be displayed.
Set each setting item using the
r
See note 1.
r keys. (
r
Run mode
Note: 1. If the mode is switched to the function setting mode during operation, operation will continue.
2. Changes made to settings in function setting mode are enabled for the first time when the
mode is changed to run mode. Also, when settings are changed, the counter is reset
(present value initialized and output turned OFF) on returning to run mode.
key only for 6-digit models)
Note 3:
See note 3.
When using as a dual counter:
Dual count
calculating mode
Input mode
See note 4.
See note 4.
(UP)
(DOWN) (UP/DOWN A) (UP/DOWN B) (UP/DOWN C)
See note.
Note 4: Displayed for output modes other than K-2, D, L, and H only.
(Addition) (Subtraction)
Output mode
See note 5. See note 5.See note 5.See note 5.
(N)
See note 6.
Function setting mode
One-shot
output
time
(F)
(C)
(R)
(K-1)
(P)
(Q)
(A)
(K-2)
Note: 5. Display only when the input mode is UP/DOWN A, B,
or C with 6-digit models (with H7CX-AU@/-AW@
models only for H).
(0.01s) (0.50s)
(D)
(L)
When using as a 2-stage counter:
Oneshot
(0.01s) (0.50s) (99.99s)
output
2 time Note: Displayed only when the
output mode is C, R, K-1,
P, Q, A, or K-2.
(99.99s)
Oneshot
(Outputs held) (0.01s) (99.99s)
output
If the output time is 0.00, hold is
1 time
Counting
speed
(5kHz)
When using as a
batch counter:
Reset input
signal
width
(20ms)
Decimal
point
position
Oneshot
output
2 time
(1ms)
Prescale
value
displayed.
Note 1: Displayed for output modes
other than D, L, and H.
Note 2: HOLD cannot be set when the
output mode is K-2.
(0.01s) (0.50s) (99.99s)
Note: Displayed only when the output
mode is C, R, K-1, P, Q, A, or K-2.
See note 7.
No decimal
point
One digit after
decimal point
Two digits after
decimal point
Three digits after
decimal point
See note 7.
(0.001)
∼
(1.000)
∼
(99.999)
Note 7: The displays for 4-digit models are shown inside
parentheses.
[9.999]
NPN/PNP
input mode
(NPN
input)
(PNP
input)
(Red)
(Green)
Display color
(Red-green) (Green-red)
Note: Displayed for terminal-block models (except H7CX-A11@) only.
Output
allocation
Note: Displayed for H7CX-AU@ models only.
Key protect
level
(KP-1)
C-108
(H)
Note 6:
Note: Displayed only when the output mode is C, R, K-1, P,
Q, A, or K-2.
(30Hz)
Note: Displayed for output modes
other than K-2, D, L, and H
only.
(KP-2)
Multifunction Preset Counter H7CX
(KP-3)
(KP-4)
(KP-5)
(Counter Function)
Explanation of Functions
Input Mode (cntm) (Setting possible using DIP switch.)
Prescale Value (pscl)
Set increment mode (UP), decrement mode (DOWN), or one of the
increment/decrement modes (UP/DOWN A, UP/DOWN B, or UP/
DOWN C) as the input mode. Input modes other than UP or DOWN
modes cannot be set using the DIP switch and so use the operation
keys if other modes are required. (For details on the operation of the
input modes, refer to Input Modes and Present Value on page 112.)
Pulses input to the counter are converted according to the specified
prescale value. (Setting range: 0.001 to 99.999 for 6-digit models
and 0.001 to 9.999 for 4-digit models.)
1. Set the decimal point position to 2 decimal places.
Dual Count Calculating Mode (calm)
2. Set the prescale value to 0.02 (0.5÷25).
When using as a dual counter, select either ADD (addition) or SUB
(subtraction) as the calculation method for the dual count value. SUB
mode can be used only when K-2, D, L, or H is selected as the output
mode with 6-digit models.
ADD:
Dual count value = CP1 PV + CP2 PV
SUB:
Dual count value = CP1 PV − CP2 PV
0.5 m
Output Mode (outm) (Setting possible using DIP switch.)
25 pulses
Set the way that control output for the present value is output. The
possible settings are N, F, C, R, K-1, P, Q, A, K-2, D, L, and H. Output
modes other than N, F, C, or K-1 cannot be set using the DIP switch
and so use the operation keys if other modes are required. The output modes that can be set vary with the model. (For details on the
operation of the output modes, refer to Input/Output Mode Settings
on page 113.)
One-shot Output Time (otim) (Setting possible using DIP
switch.)
Set the one-shot output time (0.01 to 99.99 s) for control output.
One-shot output can be used only when C, R, K-1, P, Q, A, or K-2 is
selected as the output mode. Output times other than 0.5 s or 0.05 s
cannot be set with the DIP switch and so use the operation keys if
other settings are required.
One-shot Output 2 Time (otm2) (Setting possible using
DIP switch.)
When using as a 2-stage counter or batch counter, set the one-shot
output time (0.01 to 99.99 s) for control output (OUT2). One-shot output can be used only when C, R, K-1, P, Q, A, or K-2 is selected as
the output mode. Output times other than 0.5 s or 0.05 s cannot be
set with the DIP switch and so use the operation keys if other settings
are required.
One-shot Output 1 Time (otm1)
When using as a 2-stage counter, set the one-shot output time (0.01
to 99.99 s) for control output (OUT1). One-shot output can be used
only when D, L, or H is selected as the output mode. If the output
time is set to 0.00, hold is displayed, and outputs are held. HOLD
cannot be set when the output mode is K-2.
Counting Speed (cnts) (Setting possible using DIP
switch.)
Set the maximum counting speed (30 Hz/5 kHz) for CP1 and CP2
inputs together. If contacts are used for input signals, set the counting speed to 30 Hz. Processing to eliminate chattering is performed
for this setting.
Reset Input Signal Width (iflt) (Setting possible using
DIP switch.)
Encoder
NPN/PNP Input Mode (imod)
Select either NPN input (no-voltage input) or PNP input (voltage
input) as the input format. The same setting is used for all external
inputs. For details on input connections, refer to Input Connection on
page 96.
Display Color (colr)
Set the color used for the present value.
Output OFF (See note.)
Output ON (See note.)
red
Red (fixed)
grn
Green (fixed)
r-g
Red
Green
g-r
Green
Red
Note: When using as a 2-stage counter, this is the status of output 2.
Output Allocation (otst)
When using H7CX-AU@ models as a 2-stage counter, the output can
be flexibly allocated to either stage 1 or 2.
Transistor output can be allocated to SV1 and contact output for SV2
or vice verse, as in the following table.
H7CX-AU/-AUD1
OUT1
OUT2
off
Transistor (12-13)
Contact (3, 4, 5)
on
Contact (3, 4, 5)
Transistor (12-13)
H7CX-AUSD1
OUT1
OUT2
off
Transistor (12-13)
Transistor with diode
(3, 4, 5)
on
Transistor with diode
(3, 4, 5)
Transistor (12-13)
Set the reset input signal width (20 ms/1 ms) for reset/reset 1 and
total reset/reset 2 inputs together. If contacts are used for input signals, set the counting speed to 20 ms. Processing to eliminate chattering is performed for this setting.
Decimal Point Position (dp)
Decide the decimal point position for the present value, CP1/CP2
present values, set value (SV1, SV2), total count value, and dual
count set value.
Multifunction Preset Counter
H7CX (Counter Function)
C-109
Counters
Example: To display the feed distance for systems that output
25 pulses for a feed length of 0.5 m in the form @@.@@ m:
Key Protect Level (kypt)
Set the key protect level.
When the key-protect switch in set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the
key protect level (KP-1 to KP-5). The key protect indicator is lit while the key-protect switch is set to ON. Confirm the ON/OFF status of the keyprotect switch after the H7CX is mounted to the panel.
OFF
(See note)
ON
Note: Factory-set to OFF
Key protect indicator
Level
Meaning
Details
Changing mode
(See note.)
Switching display in
run mode
Reset key
Up/down key (Up key for
6-digit models)
KP-1 (default setting)
No
Yes
Yes
Yes
KP-2
No
Yes
No
Yes
KP-3
No
Yes
Yes
No
KP-4
No
Yes
No
No
KP-5
No
No
No
No
Note: Changing mode to configuration selection mode ( MODE +
C-110
Multifunction Preset Counter H7CX
1
1 s min.) or function setting mode ( MODE 3 s min.).
(Counter Function)
Operation in Run Mode
Set values for each digit as required using the
1-stage Counter
Present value
and
keys. (
key only for 6-digit models.)
Present Value
Shows the present count value.
2-stage Counter
Counters
Set Value (Set Value 1, Set Value 2)
Set the set value. When the present
value reaches the set value, signals
are output according to the specified
output mode.
Set value
Present value
Set value 1
Present value
Set value 2
Total and Preset Counter
Present value
Set value
Present Value/Set Value
Same as 1-stage counter.
Total Count Value
Shows the present total count value.
Total count value
Batch Counter
Present Value/Set Value
Same as 1-stage counter.
Present value
Batch Count Value
Shows the number of times the count has
been completed for the present value.
Set value
Batch count value
Batch count set value
Batch Count Set Value
Set the batch count set value. When the
batch count value reaches the batch count
set value, batch output (OUT1) turns ON.
Dual Counter
Dual count set value
Dual Count Value
Shows the sum of the CP1 present value and CP2 present value when the
dual count calculating mode is ADD and shows the value obtained by
subtracting the CP2 present value from the CP1 present value when the dual
count calculating mode is SUB.
CP1 present value
Dual Count Set Value
Set the dual count set value. When the dual count value reaches the dual
count set value, signals are output according to the specified output mode.
Dual count value
CP2 present value
CP1/CP2 Present Value
Show the present count values for CP1 and CP2 present values respectively.
Multifunction Preset Counter
H7CX (Counter Function)
C-111
Input Modes and Present Value
UP (Increment) Mode
DOWN (Decrement) Mode
CP1: Count input; CP2: Prohibit (gate) input
CP1: Count input; CP2: Prohibit (gate) input
H
H
CP1
CP1
L
A Prohibit
L
A
A
CP2
CP2
L
A
Prohibit
H
H
L
n
n−1
5
Present
value
n−2
4
Present
value
3
n−3
n−4
2
n−5
1
0
0
0
a must be greater than the minimum signal width. (See note 2.)
a must be greater than the minimum signal width. (See note 2.)
CP1: Prohibit (gate) input; CP2: Count input
CP1: Prohibit (gate) input; CP2: Present value
H
H
CP1
CP1
L
A
L
A
A
Prohibit
H
A
Prohibit
H
CP2
CP2
L
L
n
5
n−1
n−2
4
Present
value
3
n−3
Present
value
2
n−4
1
n−5
0
0
a must be greater than the minimum signal width. (See note 2.)
Note: 1. If the configuration selection is set to dual counter, CP1 and
CP2 input will operate in the same way as the count input
(CP1) of UP (increment) mode.
2. a must be greater than the minimum signal width and b
must be at least 1/2 the minimum signal width. If they are
less, a count error of ±1 may occur.
Minimum signal width: 16.7 ms (when maximum counting
speed = 30 Hz)
100 µs (when maximum counting
speed = 5 kHz)
3. The meaning of the H and L symbols in the tables is explained below.
UP/DOWN A
Command Input Mode
H
CP1
L
A
A
H
CP2
L
3
3
Prese nt
val ue
2
2
2
1
0
1
0
a must be greater than the minimum signal width. (See note 2.)
UP/DOWN B
Individual Input Mode
H
CP1
0
a must be greater than the minimum signal width. (See note 2.)
L
Input method
Symbol
Short-circuit
4.5 to 30 VDC
L
Open
0 to 2 VDC
L
3
Present
value
3
2
2
2
1
0
1
1
0
UP/DOWN C
Quadrature Input Mode
H
CP1
CP2
L
B B B B
H
L
3
Present
value
2
1
0
3
2
2
1
0
b must be at least 1/2 the minimum signal width. (See note 2.)
C-112
Multifunction Preset Counter H7CX
Voltage input
(PNP input)
H
H
CP2
No-voltage input
(NPN input)
(Counter Function)
One-shot output from OUT1
Operation for 1-stage models is the same as that for OUT2.
When using a 2-stage model as a 1-stage counter, total and preset
counter, or dual counter, OUT1 and OUT2 turn ON and OFF simultaneously.
Self-holding output
Self-holding output
One-shot output from OUT2
Input mode
UP
Output
mode
setting
N
DOWN
(The one-shot output time
can be set in the range 0.01
to 99.99s.)
UP/DOWN A, B, C
Operation after count
completion
The outputs and
present value display
are held until reset/reset 1 is input.
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
OUT1
OUT2
F
The present value display continues to increase/decrease. The
outputs are held until
reset/reset 1 is input.
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
OUT1
OUT2
C
As soon as the count
reaches SV, the present
value display returns to
the reset start status.
The present value display does not show the
present value upon
count-up.
The outputs repeat
one-shot operation.
OUT1 self-holding output turns OFF after the
OUT2 one-shot output
time.The OUT1 oneshot output time is independent of OUT2.
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
OUT1
OUT2
R
The present value display returns to the reset
start status after the
one-shot output time.
The outputs repeat
one-shot operation.
OUT1 self-holding output turns OFF after the
OUT2 one-shot output
time.The OUT1 oneshot output time is independent of OUT2.
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
OUT1
OUT2
The full scale (FS) for H7CX 4-digit models is 9999.
When the present value reaches 999999, it returns to 0.
Counting cannot be performed during reset/reset 1 input.
If reset/reset 1 is input while one-shot output is ON, one-shot output turns OFF.
If there is power failure while output is ON, output will turn ON again when the power supply has recovered. For one-shot output, output
will turn ON again for the duration of the output time setting once the power supply has recovered.
6. Do not use the counter function in applications where the count may be completed (again) while one-shot output is ON.
Note: 1.
2.
3.
4.
5.
Multifunction Preset Counter
H7CX (Counter Function)
C-113
Counters
Input/Output Mode Settings
Input mode
UP
Output
mode
setting
K-1
DOWN
UP/DOWN A, B, C
Operation after
count completion
The present value display continues to increase/decrease.
OUT1 self-holding
output turns OFF after
the OUT2 one-shot
output time.The
OUT1 one-shot output time is independent of OUT2.
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
OUT1
OUT2
P
The present value display does not change
during the one-shot
output time period,
but the actual count
returns to the reset
start status.
The outputs return to
the one-shot start
state and repeat oneshot operation.
OUT1 self-holding
output turns OFF after
the OUT2 one-shot
output time. The
OUT1 one-shot output time is independent of OUT2.
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
OUT1
OUT2
Q
The present value
continues to increase/
decrease for the oneshot output time, but
returns to the reset
start status after the
one-shot output time
has elapsed.
The outputs repeat
one-shot operation.
OUT1 self-holding
output turns OFF after
the OUT2 one-shot
output time. The
OUT1 one-shot output time is independent of OUT2.
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
OUT1
OUT2
A
The present value display and OUT1 selfholding output is held
until reset/reset 1 is
input. OUT1 and
OUT2 are independent.
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
OUT1
OUT2
The full scale (FS) for H7CX 4-digit models is 9999.
When the present value reaches 999999, it returns to 0.
Counting cannot be performed during reset/reset 1 input.
If reset/reset 1 is input while one-shot output is ON, one-shot output turns OFF.
If there is power failure while output is ON, output will turn ON again when the power supply has recovered. For one-shot output, output
will turn ON again for the duration of the output time setting once the power supply has recovered.
6. Do not use the counter function in applications where the count may be completed (again) while one-shot output is ON.
Note: 1.
2.
3.
4.
5.
C-114
Multifunction Preset Counter H7CX
(Counter Function)
(The one-shot output time
can be set in the range 0.01
to 99.99s.)
Self-holding Instantaneous One-shot
output
(equals) output output
Output
mode
setting
K-2
Reset/
reset 1
Operation after count
completion
The display continues to increase/decrease until the overflow or underflow value is
reached. One-shot output only.
999999
Set
value 2
Set
value 1
0
−99999
OUT1
OUT2
D
The display continues to increase/decrease until the overflow or underflow value is
reached. The outputs are ON
while the count is equal.
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
−99999
OUT1
OUT2
L
The display continues to increase/decrease until the overflow or underflow value is
reached.
OUT1 is held while the present
value is less than or equal to set
value 1. OUT2 is held while the
present value is greater than or
equal to set value 2.
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
−99999
OUT1
OUT2
H
The display continues to increase/decrease until the overflow or underflow value is
reached.
OUT1 is held while the present
value is greater than or equal to
set value 1. OUT2 is held while
the present value is greater than
or equal to set value 2.
Note:
H mode is available only when
using a 6-digit model as a 2stage counter.
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
−99999
OUT1
OUT2
Note: 1. Counting cannot be performed during reset/reset 1 input.
2. If reset/reset 1 is input while one-shot output is ON, one-shot output turns OFF.
3. If there is power failure while output is ON, output will turn ON again when the power supply has recovered. For one-shot output, output
will turn ON again for the duration of the output time setting once the power supply has recovered.
4. Do not use the counter function in applications where the count may be completed (again) while one-shot output is ON.
Multifunction Preset Counter
H7CX (Counter Function)
C-115
Counters
Input mode
UP/DOWN A, B, C
Total and Preset Counter Operation
The H7CX has a total counter, separate from the 1-stage preset counter, for counting the total accumulated value.
Reset/reset 1
Total reset/reset 2
Present value
0
999999
Total count value
0
Note: The full scale (FS) for H7CX 4-digit models is 9999.
• The total counter continues to count the
total accumulated value when the present
value is reset using reset/reset 1 input
(reset key).
• The total count value is reset when the
total reset/reset 2 input is turned ON. If the
reset key is pressed while the total count
value is displayed, the total count value is
reset. The present value is also reset at
this time.
• The counting range of the total counter is
−99,999 to 999,999 (−999 to 9,999). The
total count value returns to 0 when it
reaches the full scale limit.
Batch Counter Operation
The H7CX has a batch counter, separate from the 1-stage preset counter, for counting the number of times the count has been completed.
• The batch counter continues after count
completion.
• Batch output is held until batch counter
reset is input.
• When the batch counter reset input is
turned ON, the batch count value is reset,
and batch output turns OFF.
• If the reset key is pressed while the batch
count value is displayed, the batch count
value is reset and batch output turns OFF.
The present value is also reset at this time.
Reset 1
Reset 2 (batch
counter reset)
Set value
Present value
0
OUT2
Batch count set value
Batch count value
0
OUT1 (batch output)
Note: The above is for when the output mode is C.
Note: 1.
2.
3.
4.
5.
6.
C-116
The batch count value is held at 0 during batch counter reset input.
If the batch count set value is 0, batch count will be performed but there will be no batch output.
The batch count value returns to 0 when it reaches 999,999 (9,999 for 4-digit models).
Once batch input has been turned ON, it will return to the ON state after power interruptions.
If the batch count set value is changed from a value that is greater than the batch count value to one that is less, batch output will turn ON.
After batch output turns ON, the ON state will be held even if the batch count set value is changed to a value greater than the batch count
value.
Multifunction Preset Counter H7CX
(Counter Function)
Dual Counter Operation
Dual Count Calculating Mode = ADD
Dual count value = CP1 PV + CP2 PV
Dual Count Calculating Mode = SUB
Dual count value = CP1 PV − CP2 PV
Reset 1
(CP1 reset)
Reset 1
(CP1 reset)
Reset 2
(CP2 reset)
Reset 2
(CP2 reset)
Dual count value
Dual count set value
Dual count set value
Dual count value
0
0
CP1 present value
CP1 present value
0
0
CP2 present value
CP2 present value
• The operation after count completion for the dual counter
value is determined by the output mode.
• The CP1 present value is reset
when reset 1 input is turned
ON and the CP2 present value
is reset when reset 2 input is
turned ON.
• If the reset key is pressed while
the dual count value, CP1
present value, or CP2 present
value is displayed, all of the
present values are reset and
outputs turn OFF. At this time,
counting is not possible for
CP1 or CP2 inputs.
0
0
OUT1, 2
OUT1, 2
Note: The above is for when the output mode is N.
Note: The above is for when the output mode is
K-2. SUB mode can be used only when
K-2, D, L, or H is selected as the output
mode with 6-digit models.
Note: 1. Counting is not possible for CP1 during reset 1 input. CP2 will not be affected. The dual count value will be calculated based on a CP1
present value of 0.
2. Counting is not possible for CP2 during reset 2 input. CP1 will not be affected. The dual count value will be calculated based on a CP2
present value of 0.
3. The counting range for the dual count value is −99,999 to 999,999 (−999 to 9,999 for 4-digit models). The counting ranges for the CP1
present value and CP2 present value are 0 to 999,999 (0 to 9,999 for 4-digit models). If a present value exceeds 999,999 (9,999 for 4digit models), FFFFFF (FFFF for 4-digit models) will be displayed to indicate an overflow, and all counting will stop.
Reset Function List
Function
1-stage/2-stage
counter
Screen displayed in run
mode
Present value/
set value (1, 2)
Total and preset counter
Present value/
set value
Total count
value
Batch counter
Present value/
set value
Dual counter
Batch count
Dual count
value/batch
value/dual
count set value count set value
Present value and output reset.
CP1 present
value/CP2
present value
Reset/reset 1
Present value
Present value and output reset.
and output reset.
Only the CP1 present value is reset.
Total reset/reset 2
No effect.
Reset key
CP1 present value, CP2 present
Present value
Present value
Present value,
Present value
Present value,
and output reset. and output reset. total count value, and output reset. batch count val- value, dual count value, and output
reset.
and output reset.
ue, output and
batch output reset.
Only the total count value is reset. Batch count value and batch output Only the CP2 present value is rereset.
set.
Multifunction Preset Counter
H7CX (Counter Function)
C-117
Counters
Using the dual counter allows the count from 2 inputs to be added or subtracted and the result displayed. It is possible to specify a set value for
which output turns ON when the set value matches the added or subtracted result.
OUT1 and OUT2 turn ON and OFF simultaneously.
■ Operating Procedures (Tachometer Function)
Switching from Counter to Tachometer
The H7CX is factory-set to the 2-stage
counter (1-stage counter for H7CX-AU@
models) configuration. To switch to the
tachometer configuration, use the
procedure shown on the right. For details,
refer to page 39.
Power ON
Configuration selection mode
Run mode
MODE +
Hold down for
1 1 s min. (See note.)
Switch to 2cnt to taco (tachometer operation) using the
Note: The
MODE
key.
key must be pressed before the
1
key.
Settings for Basic Operations
Settings for basic functions can be performed with just the DIP switch.
Be sure to set pin 1 to ON.
1
2
3
4
5
6
7
8
ON
OFF
Note: All of the pins are factory-set to OFF.
Item
1
DIP switch settings enable/
disable
OFF
Disabled
ON
2
Counting speed 30 Hz
3
Tachometer out- Refer to the table on the right.
put mode
4
5
6
Average processing
7
---
8
NPN/PNP input NPN
mode
Pin 3
Enabled
OFF
10 kHz
Refer to the table on the right.
---
ON
OFF
Area
OFF
ON
Upper limit
ON
ON
Lower limit
Pin 5
PNP
Easy Confirmation of Switch Settings Using Indicators
Tachometer output mode
Upper and lower limit
OFF
---
Pin 4
OFF
Pin 6
OFF
Average processing
OFF (no average processing)
ON
OFF
2 times
OFF
ON
4 times
ON
ON
8 times
The ON/OFF status of the DIP switch pins can be
confirmed using the front display. For details, refer to page 124.
Note: 1. Be sure to set pin 1 of the DIP switch to ON. If it is set to OFF, the DIP switch settings will not be enabled.
2. Changes to DIP switch settings are enabled when the power is turned ON.
Advanced-Function Settings
After making DIP switch settings for basic operations, advanced-functions (see note) can be added using the operation keys.
For details, refer to page 34.
Note: Advanced functions consist of decimal point position, prescale value, auto-zero time, startup time, display color, output allocation, and key protect level.
C-118
Multifunction Preset Counter H7CX
(Tachometer Function)
Settings for Advanced Functions
Note: When using as a tachometer, switch to the tachometer configuration using the procedure given on page 124.
Settings that cannot be performed with the DIP switch are performed with the operation keys.
Run mode
Counters
Note: 1. If the mode is switched to the function setting mode during operation, operation will
continue.tion, operation will continue.
2. Changes made to settings in function setting mode are enabled for the first time when
the mode is changed to run mode. Also, whensettings are changed, the counter is reset (measured values initial-ized and output turned OFF) on returning to run mode.
Power ON
For details on operations in run mode, refer to page 37.
(See note 1.)
(See note 2.)
The characters displayed in reverse video are the initial values.
3s min.
When performing settings with operation keys only, set pin1 of the DIP switch to OFF (factory setting).
If pin 1 of the DIP switch is set to ON, the setting items indicated by
will not be displayed.
3s min.
Set each setting item using the
keys.
Tachometer
output
mode
(HI-LO)
(AREA)
(HI-HI)
(LO-LO)
Counting
speed
(30Hz)
(10kHz)
Decimal
point
position
(No decimal
point)
Function setting mode
Prescale
value
(0.001)
∼
(One digit
after decimal
point)
(1.000)
∼
(Two digits
after decimal
point)
(Three digits
after decimal
point)
(99.999)
Average
processing
(No average processing)
Auto-zero
time
(Average
of 2 measurements)
(0.1s)
∼
(99.9s)
(0.0s)
∼
(99.9s)
Startup
time
(Average
of 4 measurements)
(Average
of 8 measurements)
NPN/PNP
input mode
(NPN
input)
(PNP
input)
(Red)
(Green)
Display
color
(Red-green) (Green-red)
Output
allocation
Note: Displayed for H7CX-AU@ models
Key protect
level
(KP-1)
(KP-2)
(KP-3)
Multifunction Preset Counter
(KP-4)
(KP-5)
H7CX (Tachometer Function)
C-119
Explanation of Functions
Tachometer Output Mode (totm) (Setting possible using
DIP switch.)
Set the output method for control output based on the OUT1/OUT2
set value. Upper and lower limit (HI-LO), area (AREA), upper limit
(HI-HI), and lower limit (LO-LO) can be set. (For details on the operation of the output modes, refer to Output Mode Settings on
page 123.)
Counting Speed (cnts) (Setting possible using DIP
switch.)
Auto-zero Time (aut=)
It is possible to set the H7CX so that if there is no pulse for a certain
time the display is force-set to 0. This time is called the auto-zero
time. Set the auto-zero time to a time slightly longer than the estimated interval between input pulses and within the setting range (0.1
to 99.9 s). It will not be possible to make accurate measurements if
the auto-zero time is set to a time shorter than the input pulse cycle.
Setting a time that is too long may also result in problems, such as a
time-lag between rotation stopping and the alarm turning ON.
Startup Time (stmr)
Set the maximum counting speed (30 Hz/10 kHz) for CP1 input. If
contacts are used for input signals, set the counting speed to 30 Hz.
Processing to eliminate chattering is performed for this setting.
Decimal Point Position (dp)
Decide the decimal point position for the measurement value, OUT1
set value, and OUT2 set value.
In order to prevent undesired output resulting from unstable input
immediately after the power supply is turned ON, it is possible to prohibit measurement for a set time (0.0 to 99.9 s), the startup time. It
can also be used to stop measurement and disable output until the
rotating body reaches the normal rate of rotation, after the power
supply to the H7CX and rotating body are turned ON at the same
time.
Prescale Value (pscl)
Display
It is possible to display the rate of rotation or the speed of a device or
machine to which the H7CX is mounted by converting input pulses to
a desired unit. If this prescaling function is not used, the input frequency (Hz) will be displayed.
Startup time
Comparison
value
(lower limit)
The relationship between display and input is determined by the following equation. Set the prescale value according to the unit to be
displayed.
Time
Power supply
Displayed value = f × a
f: Input pulse frequency (number of pulses in 1 second)
a: Prescale value
Output
(lower limit)
1. Displaying Rotation Rate
NPN/PNP Input Mode (imod)
Display unit
Select either NPN input (no-voltage input) or PNP input (voltage
input) as the input format. The same setting is used for all external
inputs. For details on input connections, refer to The circuit shown
above is for no-voltage input (NPN input). on page 96.
Prescale value (a)
rpm
1/N × 60
rps
1/N
N: Number of pulses per revolution
Display Color (colr)
Example:In order to display the rate of rotation for a machine that
outputs 5 pulses per revolution in the form @@.@ rpm:
Set the color used for the measurement value.
Setting
1. Set the decimal point position to 1 decimal place.
2. Using the formula, set the prescale value to 1/N × 60 =
60/5 = 12.
2. Displaying Speed
Display unit
πd × 1/N × 60
m/s
πd × 1/N
Measured value displayed
in green when either control
output 1 or control output 2
is ON.
Measured value displayed Measured value displayed
(See note in green when both control in red when either control
outputs 1 and 2 are OFF.
output 1 or control output 2
2.)
is ON.
g-r
N: Number of pulses per revolution
d: Diameter of rotating body (m)
πd: Circumference (m)
d:Diameter of
rotating body
Note: 1. If the tachometer output mode is set to AREA, however, the
measured value is displayed in red when control output 1 is
OFF and in green when control output 1 is ON.
2. If the tachometer output mode is set to AREA, however, the
measured value is displayed in green when control output 1
is OFF and in red when control output 1 is ON.
Average Processing (aug) (Setting possible using DIP
switch.)
Flickering display and output chattering can be prevented using average processing (simple averaging). Average processing can be set to
one of four levels: no average processing, 2 times (i.e., the average
of 2 measurement values), 4 times, or 8 times. The measurement
cycle will be equal to the sampling cycle (200 ms) multiplied by the
average processing setting (i.e., the number of times). Average processing enables fluctuating input signals to be displayed stably. Set
the optimum number of times for the application.
C-120
Control output ON
Green (fixed)
Measured value displayed
(See note in red when both control
outputs 1 and 2 are OFF.
1.)
Prescale value (a)
m/min
red
grn
r-g
Control output OFF
Red (fixed)
Multifunction Preset Counter H7CX
(Tachometer Function)
Output Allocation (otst)
When using H7CX-AU@ models as 2-stage counter, each output can
be flexibly allocated to either stage 1 or 2.
Transistor output placed for SV1 and contact output for SV2 or vice
verse, as in the following table.
H7CX-AU/-AUD1
OUT2
Transistor (12-13)
Contact (3, 4, 5)
Contact (3, 4, 5)
Transistor (12-13)
Counters
OUT1
off
on
H7CX-AUSD1
OUT1
OUT2
off
Transistor (12-13)
Transistor with diode
(3, 4, 5)
on
Transistor with diode
(3, 4, 5)
Transistor (12-13)
Key Protect Level (kypt)
Set the key protect level.
When the key-protect switch in set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the
key protect level (KP-1 to KP-5). The key protect indicator is lit while the key-protect switch is set to ON. Confirm the ON/OFF status of the keyprotect switch after the H7CX is mounted to the panel.
(See note)
OFF
ON
Note: Factory-set to OFF
Key protect indicator
Level
Meaning
Details
Changing mode
(See note.)
Switching display
during operation
Reset key
Up/down key (Up key for
6-digit models)
KP-1 (default setting)
No
Yes
Yes
Yes
KP-2
No
Yes
No
Yes
KP-3
No
Yes
Yes
No
KP-4
No
Yes
No
No
KP-5
No
No
No
No
Note: Changing mode to configuration selection mode ( MODE +
1
1 s min.) or function setting mode ( MODE 3 s min.).
Multifunction Preset Counter
H7CX (Tachometer Function)
C-121
Operation in Run Mode
Set values for each digit as required using the
Measurement value
Measurement value
OUT1 set value
key.
Measurement Value
Displays the currently measured value.
OUT1/OUT2 Set Value
Set OUT1 set value and OUT2 set value. The
measurement value is compared to OUT1 set value
and OUT2 set value and output is made according to
the selected output mode.
Measurement value
OUT2 set value
C-122
Multifunction Preset Counter H7CX
(Tachometer Function)
Output Mode Settings
Upper
and
lower
limit
(HI-LO)
(Upper-limit) OUT2 set value
Measurement value
(Lower-limit) OUT1 set value
OUT1
Counters
Output
mode
setting
OUT2
ON condition for OUT1: measurement value ≤ OUT1 set value
ON condition for OUT2: measurement value ≥ OUT2 set value
Area
(AREA)
OUT2 set value
Measurement value
OUT1 set value
OUT1
OUT2
Condition
Upper
limit
(HI-HI)
OUT1 set value ≤ OUT2 set value
OUT1 set value > OUT2 set value
OUT1 set value ≤ measurement value ≤ OUT2 set
ON
condition value
for OUT1
OUT2 set value ≤ measurement value ≤ OUT1 set
value
measurement value < OUT1 set value
ON
condition or
for OUT2 measurement value > OUT2 set value
measurement value < OUT2 set value
or
measurement value > OUT1 set value
(Upper-limit) OUT2 set value
Measurement value
(Upper-limit) OUT1 set value
OUT1
OUT2
ON condition for OUT1: Measurement value ≥ OUT1 set value
ON condition for OUT2: Measurement value ≥ OUT2 set value
Lower
limit
(LO-LO)
(Lower-limit) OUT2 set value
Measurement value
(Lower-limit) OUT1 set value
OUT1
OUT2
ON condition for OUT1: Measurement value ≤ OUT1 set value
ON condition for OUT2: Measurement value ≤ OUT2 set value
Multifunction Preset Counter
H7CX (Tachometer Function)
C-123
■ Operation in Configuration Selection Mode
Select which H7CX configuration is used (i.e., 1-stage counter, 2-stage counter, total and preset counter, batch counter, dual counter, or tachometer) in configuration selection mode. The H7CX is also equipped with a DIP switch monitor function, a convenient function that enables the settings
of the DIP switch pins to be confirmed using the front display.
Counting stopped
Counting possible
Power ON
1
Run Mode
1
To change the mode to configuration selection mode, press
the 1 Key for 1 s min. with the
key held down. The
mode will not change if the 1 key is pressed first.
(See note 2.)
+
1
(See note 1.)
Configuration Selection Mode
1 s min.
Select the configuration using the
keys. (
key only for 6digit models)
The H7CX is factory-set to the 1-stage counter configuration (2-stage
counter configuration with H7CX-AW@/-A4W@ models).
Configuration
selection
(1-stage counter) (2-stage counter) (Total and
preset counter)
(Batch counter)
(Dual counter)
(Tachometer)
The configuration that can be selected depend on the model.
DIP switch
monitor
The status of the DIP switch pins (1 to 8) can be confirmed using the
keys.
Note: This display is possible only if DIP switch pin 1 (DIP switch settings) is set to ON (i.e., enabled).
Example
1
2
3
4
5
6
7
8
ON
OFF
Indicates that DIP switch pin 8 is ON.
Indicates that DIP switch pin 7 is OFF.
Indicates that DIP switch pin 6 is ON.
Indicates that DIP switch pin 5 is OFF.
Indicates that DIP switch pin 4 is ON.
Indicates that DIP switch pin 3 is OFF.
Indicates that DIP switch pin 2 is ON.
Indicates that DIP switch pin 1 is ON.
Note: 1. When the mode is changed to configuration selection mode, the present value is reset, outputs turns OFF, and counting (measuring)
stops.
2. Setting changes made in configuration selection mode are enabled when the mode is changed to run mode. If the configuration is
changed, the set value (or set value 1 and set value 2), OUT1 set value or OUT2 set value are initialized.
C-124
Multifunction Preset Counter H7CX
Additional Information
■ Using the Operation Keys
Counting stopped
Power ON
+
Counting possible
1
3 s min.
1 s min.
Configuration selection mode
Function setting mode
Run mode
+
1
1 s min.
1-stage counter
3 s min.
Configuration selection
Input mode
Present value, set value
DIP switch monitor
Dual count calculating mode
2-stage counter
Output mode
Present value, set value 1
One-shot output time
Present value, set value 2
One-shot output 2 time
One-shot output 1 time
Total and preset counter
Present value, set value
Counting speed
Total count value
Reset input signal width
Decimal point position
Batch counter
Prescale value
Present value, set value
NPN/PNP input mode
Batch count value,
batch count set value
Display color
Output allocation
Dual counter
Key protect level
Dual count value,
dual count set value
CP1 present value,
CP2 present value
and
keys (
key only with 6-digit models).
Note: 1. Perform settings using the
2. The above flowcharts outline the procedures for all models. For more details on each model, refer to page 107.
Multifunction Preset Counter
H7CX
C-125
Counters
Counter Operation
Tachometer Operation
Counting stopped
Power ON
+
Counting possible
1
1 s min.
3 s min.
Run mode
Configuration selection mode
+
Function setting mode
1
1 s min.
3 s min.
Configuration selection
Measurement value
Tachometer output mode
DIP switch monitor
Measurement value,
OUT1 set value
Counting speed
Measurement value,
OUT2 set value
Decimal point position
Prescale value
Average processing
Auto-zero time
Startup time
NPN/PNP input mode
Display color
Output allocation
Key protect level
Note: 1. All setting changes are performed using the
2. For details, refer to page 118.
C-126
key.
Multifunction Preset Counter H7CX
■ Lists of Settings
Fill in your set values in the set value column of the following tables and utilize the tables for quick reference.
Configuration Selection Mode
Parameter
Setting range
Default value
Unit
Configuration
selection
func
1cnt/2cnt/tcnt/bcnt/dcnt/taco (See note 1.)
1cnt
(See note 2.)
---
DIP switch
monitor
dip
on/off
off
---
Set value
Counters
Parameter
name
---
Note: 1. The setting range varies with the model.
2. The default value for H7CX-AW@/-A4W@ models is 2cnt.
Settings for Counter Operation
Run Mode
• 1-stage Counter
Parameter name
Present value,
set value
Parameter
Setting range
Default value
Unit
Present value
---
-99999 to 999999 (-999 to 9999)
0
--
Set value
---
0 to 999999 (0 to 9999) (For conditions other
than those described in note 1.)
0
---
Set value
---
-99999 to 999999 (-999 to 9999)
(See note 1.)
• 2-stage Counter
Parameter name
Present value,
set value 1
Present value,
set value 2
Parameter
Setting range
Default value
Unit
Present value
---
-99999 to 999999 (-999 to 9999)
0
---
Set value 1
---
0 to 999999 (0 to 9999) (For conditions other
than those described in note 1.)
0
---
-99999 to 999999 (-999 to 9999)
(See note 1.)
0
Present value
---
-99999 to 999999 (-999 to 9999)
0
---
Set value 2
---
0 to 999999 (0 to 9999) (For conditions other
than those described in note 1.)
0
---
-99999 to 999999 (-999 to 9999)
(See note 1.)
0
Set value
---
---
• Total and Preset Counter
Parameter name
Present value,
set value
Parameter
Setting range
Default value
Unit
Present value
---
-99999 to 999999 (-999 to 9999)
0
---
Set value
---
0 to 999999 (0 to 9999) (For conditions other
than those described in note 1.)
0
---
0
---
Set value
---
-99999 to 999999 (-999 to 9999)
(See note 1.)
Total count value
---
-99999 to 999999 (-999 to 9999)
---
• Batch Counter
Parameter name
Present value,
set value
Parameter
Setting range
Default value
Unit
Present value
---
-99999 to 999999 (-999 to 9999)
0
---
Set value
---
0 to 999999 (0 to 9999) (For conditions other
than those described in note 1.)
0
---
Set value
---
-99999 to 999999 (-999 to 9999)
(See note 1.)
Batch count
Batch count
value, batch
value
count set value Batch count
set value
---
0 to 999999 (0 to 9999)
0
---
---
0 to 999999 (0 to 9999)
0
---
Multifunction Preset Counter
---
H7CX
C-127
• Dual Counter
Parameter name
Parameter
Setting range
-99999 to 999999 (-999 to 9999)
Dual count
Dual count value --value, dual count Dual count set
--set value
value
Default value
Unit
0
---
0 to 999999 (0 to 9999) (For conditions other 0
than those described in note 2.)
---
Set value
---
-99999 to 999999 (-999 to 9999)
(See note 2.)
CP1 present
value, CP2
present value
CP1 present
value
---
0 to 999999 (0 to 9999)
0
---
---
CP2 present
value
---
0 to 999999 (0 to 9999)
0
---
---
Note: 1. The input mode is increment/decrement mode and the output mode is K-2, D, L, or H.
2. The dual count calculating mode is subtraction mode and the output mode is K-2, D, L, or H.
Function Setting Mode
Parameter name
Parameter
Setting range
Default value
Unit
Input mode
cntm
up/down/ud-a/ud-b/ud-c (See note 1.)
up
---
Dual count calculating
mode
caln
add/sub (See note 1.)
add
---
Output mode
outm
n/f/c/r/k-1/p/q/a/k-2/d/l/h (See note 2.)
n
---
One-shot output time
otim
0.01 to 99.99
0.50
s
One-shot output 2 time
otm2
0.01 to 99.99
0.50
s
One-shot output 1 time
otm1
hold/0.01 to 99.99 (See note 3.)
hold
s
Counting speed
cnts
30h=/skh=
30h=
---
Reset input signal width
iflt
20ms/1ms
20ms
---
Decimal point position
dp
------/-----.-/----.--/---.--(----/---.-/--.--/-.---)
-----(----)
Prescale value
pscl
0.001 to 99.999 (0.001 to 9.999)
1.000
---
NPN/PNP input mode
imod
npn/pnp
npn
---
Display color
colr
red/grn/r-g/g-r
red
---
Output allocation
otst
off/on
off
---
Key protect level
kypt
kp-1/kp-2/kp-3/kp-4/kp-5
kp-1
---
Note: 1. The setting range varies with the output mode.
2. The setting range varies with the model and the input mode.
3. HOLD cannot be set when the output mode is K-2.
C-128
Multifunction Preset Counter H7CX
Set value
Settings for Tachometer Operation
Run Mode
Measurement
value, OUT1 set
value
Measurement
value, OUT2 set
value
Parameter
Setting range
Default value
Unit
Set value
---
0 to 999999
0
---
---
Measurement
value
---
0 to 999999
0
---
---
OUT1 set value
---
0 to 999999
0
---
Measurement
value
---
0 to 999999
0
---
OUT2 set value
---
0 to 999999
0
---
Counters
Parameter name
Measurement value
---
Function Setting Mode
Parameter name
Parameter
Tachometer output
mode
totm
Counting speed
cnts
Setting range
Default value
Unit
hold/area/hihi/lolo
hilo
-----
30h=/10kh=
30h=
Decimal point position dp
------/-----.-/----.--/---.---
------
---
Prescale value
pscl
0.001 to 99.999
1.000
---
Average processing
aUg
off/2/4/8
off
---
Auto-zero time
aut=
0.1 to 99.9
99.9
---
Startup time
stmr
0.0 to 99.9
0.0
s
npn/pnp
npn
s
NPN/PNP input mode imod
Display color
colr
red/grn/r-g/g-r
red
---
Output allocation
otst
off/on
off
---
Key protect level
kypt
kp-1/kp-2/kp-3/kp-4/kp-5
kp-1
---
Multifunction Preset Counter
H7CX
Set value
C-129
Similar pages