Cooper FRS-R-600 Frs-r 600vac/300vdc, 65-600a, dual element, time-delay fus Datasheet

FUSETRON™ 600V Class RK5
FRS-R — 600Vac/300Vdc, 65-600A, Dual Element, Time-Delay Fuses
Dimensions - in
A
B
Description: Advanced protection, energy efficient Class RK5
dual element, current-limiting, time-delay fuses. Time-delay –
10 seconds (minimum) at 500% of rated current.
Catalog Symbol: FRS-R-(amp)
Ratings:
Volts — 600Vac, 300Vdc
Amps — 65-600A
IR — 200kA Vac RMS Sym.
— 20kA Vdc
Agency Information:
CE, UL Listed, Std. 248-12, Class RK5, Guide JDDZ,
File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
Catalog Numbers (amps)
FRS-R-65
FRS-R-70
FRS-R-75
FRS-R-80
FRS-R-90
FRS-R-100
FRS-R-110
FRS-R-125
FRS-R-150
FRS-R-175
FRS-R-200
FRS-R-225
FRS-R-250
FRS-R-300
Carton Quantity and Weight
Amp Rating
65–100
101–200
201–400
401–600
Carton Qty.
1
1
1
1
FRS-R-350
FRS-R-400
FRS-R-450
FRS-R-500
FRS-R-600
Amp Ratings
65-100
110-200
225-400
450-600
A
7.88 (± 0.062)
9.63 (± 0.062)
11.63 (± 0.094)
13.38 (± 0.094)
B
1.11 (± 0.02)
1.61 (± 0.02)
2.34 (± 0.02)
2.88 (± 0.02)
Features:
• Provides motor overload, ground fault and short-circuit
protection. When used in circuits subject to surge currents
such as those caused by motors, transformers and other
inductive components, these fuses can be sized close to
full-load amps to give maximum overcurrent protection.
• The time-delay feature makes it possible to use fuse amp
ratings which are much smaller than those of non-time delay
fuses. Considerable cost saving occurs by permitting the
use of smaller size switches, panels and fuses themselves.
• Provides a good degree of short-circuit protection (greater
current-limitation) to help protect downstream components
from high fault currents.
• Gives motor running back-up protection to motors without
extra cost.
• Helps protect motors against burnout from overloads and
single-phasing when sized properly.
• Simplifies and improves blackout prevention (selective
coordination ratios).
• Dual-element fuses can be applied in circuits subject to
temporary motor overloads and surge currents to provide
both high-performance, short-circuit and overload
protection.
Recommended Fuse Blocks
Fuse Amps
70-100
110-200
225-400
450-600
1-Pole
RM60100-1CR
RM60200-1CR
RM60400-1CR
RM60600-1CR
2-Pole
RM60100-2CR
RM60200-2CR
RM60400-2CR
RM60600-2CR
3-Pole
RM60100-3CR
RM60200-3CR
RM60400-3CR
RM60100-3CR
For additional information on the RM Series of 600 volt fuse
blocks, see product brochure # 3192.
Fuse Reducers For Class R Fuses
Equipment
Fuse Clips
200A
400A
600A
Desired Fuse
(Case) Size
100A
100A
200A
100A
200A
400A
Catalog Numbers
(Pairs) 600V
NO.2621-R
NO.2641-R
NO.642-R
NO.2661-R
NO.2662-R
NO.2664-R†
† Single reducer only (pair not required).
For additional information on Class R fuse reducers, see
Data Sheet # 1118.
0713
BU-SB13729
Page 1 of 3
Data Sheet # 1018
FUSETRON™ 600V Class RK5
FRS-R — 600Vac/300Vdc, 65-600A, Dual Element, Time-Delay Fuses
600A
400A
200A
100A
60A
30A
300
15A
Time-Current Curves - Average Melt
AMP RATING
100
TIME IN SECONDS
10
1
0.1
RMS SYMMETRICAL CURRENT IN AMPS
0713
BU-SB13729
Page 2 of 3
20,000
10,000
1,000
100
20
0.01
Data Sheet # 1018
FUSETRON™ 600V Class RK5
FRS-R — 600Vac/300Vdc, 65-600A, Dual Element, Time-Delay Fuses
Current-Limitation Curves
B
400000
300000
AMP RATING
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
200000
100000
90000
80000
70000
60000
600A
400A
50000
40000
200A
30000
100A
20000
10000
9000
8000
7000
6000
5000
4000
3000
A
2000
200000
50000
60000
70000
80000
90000
100000
40000
30000
20000
5000
6000
7000
8000
9000
10000
3000
4000
2000
1000
1000
PROSPECTIVE SHORT-CIRCUIT CURRENT - SYMMETRICAL RMS AMPS
Current-Limiting Effects
Prosp.
Let-Through Current
S.C.C.
(Apparent RMS Symmetrical Vs. Fuse Rating)
100A
200A
400A
600A
5000
3000
4000
5000
5000
10,000
4000
5000
9000
10,000
15,000
4000
6000
10,000
14,000
20,000
5000
7000
11,000
15,000
25,000
5000
7000
12,000
17,000
30,000
5000
8000
13,000
18,000
35,000
5000
8000
13,000
18,000
40,000
6000
9000
14,000
19,000
50,000
6000
9000
14,000
20,000
60,000
6000
10,000
15,000
22,000
70,000
7000
11,000
17,000
23,000
80,000
7000
12,000
17,000
23,000
90,000
7000
12,000
17,000
24,000
100,000
8000
13,000
18,000
25,000
150,000
9000
14,000
21,000
27,000
200,000
9000
16,000
23,000
32,000
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
0713
BU-SB13729
Page 3 of 3
Data Sheet # 1018
Similar pages