EPCOS B84143B0180S081

EMC filters
3-line filters
for converters and power electronics
Rated current 180 to 1600 A
Series/Type:
B84143B*S080, S081
Date:
January 2006
 EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the
information contained therein without EPCOS’ prior express consent is prohibited.
3-line filters
B84143B*S080, S081
for converters and power electronics
Power line filters for 3-phase systems
Rated voltage 520/300 and 760/440 V AC
Rated current 180 to 1600 A
Construction
■ 3-line filter
■ Metal case
Features
■
■
■
■
■
■
Optimized leakage current
Easy to install
Very compact design
Optimized for operation under full load
Low weight
Design complies with
EN 133200, UL 1283, CSA C22.2 No.8
■ UL, cUL approval
Applications
■ Frequency converters for motor drives
■ Wind farms
■ Power supplies
Terminals
■ Busbars
Marking
Marking on component:
Manufacturer’s logo, ordering code, frequency,
rated voltage, rated current, rated temperature,
climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
Please read Cautions and warnings and
Important notes at the end of this document.
2
01/06
3-line filters
B84143B*S080, S081
for converters and power electronics
Typical circuit diagram
LINE
LOAD
L1
L1’
L2
L2’
L3
L3’
SSB2008-L
Technical data and measuring conditions
Rated voltage VR
Type S080:
Type S081:
Rated current IR
Referred to 40 °C ambient temperature
(180 A filter at 60 °C)
Test voltage Vtest
Type …S080: 2240 V DC, 2 s (line/line)
2720 V DC, 2 s (lines/case)
520/300 V AC, 50/60 Hz
760/440 V AC, 50/60 Hz (Suitable for IT mains
supply up to 560/320 V.
See also Chapter “General”, section 7.4)
Type …S081: 3270 V DC, 2 s (line/line)
2890 V DC, 2 s (lines/case)
Overload capability (thermal)
1.5 · IR for 3 min per hour or
2.5 · IR for 30 s per hour
Leakage current lleak
Type …S080: at 520 V AC, 50 Hz
Type …S081: at 760 V AC, 50 Hz
Climatic category (IEC 60068-1) 25/100/21 (–25 °C/+100 °C/21 days damp heat test)
Approvals
UL 1283; CSA C22.2 No.8
(Type S080: 500/290 V; Type S081: 600/350 V)
Please read Cautions and warnings and
Important notes at the end of this document.
3
01/06
3-line filters
B84143B*S080, S081
for converters and power electronics
Characteristics and ordering codes
VR
AC
V
IR
Ileak
Rtyp
A
mA
µΩ
1801)
< 21
110
250
< 21
320
Approx.
weight
kg
Ordering code
Approvals
5.0
B84143B0180S080
×
×
110
5.0
B84143B0250S080
×
×
< 21
51
7.2
B84143B0320S080
×
×
400
< 21
48
7.5
B84143B0400S080
×
×
600
< 21
43
7.8
B84143B0600S080
×
×
1000
< 40
29
18.5
B84143B1000S080
×
×
1600
< 40
22
24.5
B84143B1600S080
–
–
1801)
< 31
110
5.0
B84143B0180S081
×
×
250
< 31
110
5.0
B84143B0250S081
×
×
320
< 31
51
7.2
B84143B0320S081
×
×
400
< 31
48
7.5
B84143B0400S081
×
×
600
< 31
43
7.8
B84143B0600S081
×
×
1000
< 58
29
18.5
B84143B1000S081
×
×
1600
< 58
22
24.5
B84143B1600S081
–
–
Type S080
500/290 V
520/300
Type
S0812)
760/440
600/350 V
× = approval granted
1) B84143B0180S080 and B84143B0180S081 referred to 60 °C ambient temperature
Please read Cautions and warnings and
Important notes at the end of this document.
4
01/06
3-line filters
B84143B*S080, S081
for converters and power electronics
Dimensional drawings
B84143B0180S08*, B84143B0250S08* (180 A, 250 A)
140
30±3
30±3
90
2
76
110
20
ø9
10
10
250±2
145±0.5
L1’
Marking
LINE LOAD
L2
L2’
170
L1
155±1
3
6.6
L3’
L3
200
SSB2147-D
B84143B0320S08*, B84143B0400S08* (320 A, 400 A)
140
40±3
40±3
90
15
2
15
290±2
L1
L2
L1’
Marking
LINE LOAD
L3
L2’
190
170±0.5
165±1
5
ø12
L3’
230
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2148-L
5
01/06
78.2
116
25
ø11
3-line filters
B84143B*S080, S081
for converters and power electronics
B84143B0600S08* (600 A)
140
40±3
40±3
90
78.2
116
30
ø11
2
15
15
290±2
L1
L1’
Marking
LINE LOAD
L2
L2’
L3
190
170±0.5
165±1
5
ø12
L3’
230
SSB2149-U
B84143B1000S08* (1000 A)
210
52±3
52±3
142
20
2.5
20
89.7
140
40
ø14
370±2.5
240±1
L1
Marking
LINE
L2’
LOAD
260
L2
L1’
235±1
8
ø12
L3’
L3
300
Please read Cautions and warnings and
Important notes at the end of this document.
SSB2150-X
6
01/06
3-line filters
B84143B*S080, S081
for converters and power electronics
B84143B1600S08* (1600 A)
92±3
92±3
50
ø14
40
40
20
450±3
20
89,7
L1
L1’
Marking
L2
LINE
L3’
L3
140
Please read Cautions and warnings and
Important notes at the end of this document.
L2’
LOAD
260
10
210
142
240±1
ø12
235±1
2,5
300±1,5
7
01/06
SSB2013-M
3-line filters
B84143B*S080, S081
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 180 A and 250 A
100
α
Filters for 320 A and 400 A
SSB2003-F
B84143B0180S08*
dB B84143B0250S08*
α
B84143B0320S08*
dB B84143B0400S08*
80
80
60
60
40
40
20
20
0
10 4
10 5
10 6
10 7
10 5
10 6
10 7
Hz 10 8
f
Filters for 1000 A
SSB2005-W
100
dB
0
10 4
Hz 10 8
f
Filters for 600 A
SSB2004-N
100
SSB2006-5
100
B84143B0600S08*
dB
B84143B1000S08*
α
α
80
80
60
60
40
40
20
20
0
10 4
10 5
10 6
10 7
0
10 4
Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
8
01/06
10 5
10 6
10 7
Hz 10 8
f
3-line filters
B84143B*S080, S081
for converters and power electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 1600 A
SSB2007-D
100
dB B84143B1600S08*
α
80
60
40
20
0
10 4
10 5
10 6
10 7
Hz 10 8
f
Please read Cautions and warnings and
Important notes at the end of this document.
9
01/06
EMC filters
Cautions and warnings
Important information
Please read all safety and warning notes carefully before installing the EMC filter and putting it into
operation (see
). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appro­
priate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in low­
voltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warnings
■ It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
■
■
■
■
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Danger­
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed and
the last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen­
cies that may cause resonances etc. can lead to destruction of the filter housing.
EMC filters must be protected in the application against impermissible exceeding of the rated
currents by suitable overcurrent protective.
10
01/06
EMC filters
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As
a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in which
the malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of
suitable design of the customer application or other action taken by the customer (e.g.
installation of protective circuitry or redundancy) that no injury or damage is sustained by third
parties in the event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as “hazardous”). Useful information on this will be found in our
Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more
detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products.
Consequently, we cannot guarantee that all products named in this publication will always be
available.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap,
PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are
trademarks registered or pending in Europe and in other countries. Further information will be
found on the Internet at www.epcos.com/trademarks.
11
01/06