SCHURTER TA35

circuit breakers
Thermal Circuit Breaker, rotary knob actuation, 1-, 2- or 3-pole
2-pole standard version
3-pole type without front bezel/knob
standard front bezel/knob
Description
Applications
– Thermal circuit breaker 1-, 2- or 3-pole
– Supplementary protector for general industrial use
– Positively trip-free release
– Bezel/knob snap-on
– Easy actuation with gloves
– Front elements can be done by customer
– High pressure cleaners
– Floor cleaning equipment
– Power tools
– Wood and stone working machines
– Equipment for building construction
– Industrial equipment
– Commercial kitchen appliances
Standards
Weblinks
– IEC 60934
– UL 1077
– CSA C22.2 235
– GB 17701
Approvals: http://www.schurter.com/approvals
RoHS: http://www.schurter.com/rohs
Technical Data
Rated voltage Ue
1-pole
2-pole
3-pole
AC 240 V / 50/60 Hz
DC 32 V
AC 240 V / 50/60 Hz
DC 60 V
AC 415 Y/240 V / 50/60 Hz
Rated current In
1- / 2-pole
3-pole
0.05 – 20 A
0.05 – 12 A
Conditional short circuit Inc
1- / 2-pole, AC 240 V
3-pole, AC 415 V
0.05…20 A: 2000 A, SC (C1)
0.05…12 A: 2000 A
Degree of protection
Accessible range
Terminal side
IP 40
IP 00
Dielectric strength
50 Hz
Impulse 1.2/50 µs
> 2500 V
> 4000 V
Insulation resistance
DC 500 V
> 100 MOhm
Endurance (typical)
Mechanical
50’000 cycles
AC: 1 x In, cos phi 0.6
50’000 cycles
DC: 1 x In, L/R = 2…3ms 50’000 cycles
Overload
IEC 60934
UL 1077
min. 40 cycles @ 6 x In,
cos phi 0.6
min. 50 cycles @ 1.5 x In,
cos phi 0.75 (OLØ)
Admissible ambient air temperature –30 °C to +60 °C
Resistance to vibration IEC 60068-2-6, Test Tc 10…60 Hz: ±0.75 mm
60…500 Hz: 10 G
Shock resistance
IEC 60068-2-27, Test Ea 30 G / 18 ms
Type of tripping
Thermal positively trip free
Weight
45 g
60 g
75 g
1-pole
2-pole
3-pole
Max. switching capacity 1-, 2-pole
for switch only types 3-pole
(without bimetal)
circuit breakers
20 A
12 A
TA35
www.schurter.com/pg17_18_19
Tripping Characteristics
[ min ] [ sec ]
10'000
[ min ] [ sec ]
10'000
Type
Rated current
TA35
<3 A (TC-1)
1, 2 pole
60
20
Ambient temp.
1`000
10
60
3 pole
2`000
30
Type
Rated current
20
5
Ambient temp.
1`000
10
500
1,2,3 pole
2`000
30
+23 °C
TA35
>3–20A (TC-1)
(3 pole, max. 12A)
+23 C °
500
5
200
200
100
1
100
1
50
20
20
10
10
5
5
2
2
1
1
0,5
0,5
Tripping time
Tripping time
50
0,3
0,2
0,1
1,05 1,35
2
3
4
5
8
0,3
0,2
0,1
10
1,05 1,35
[ x In ]
Multiple of rated current
2
Multiple of rated current
3
4
5
8
10
[ x In ]
The above tripping characteristics apply to symmetrical overloads on all poles on the TA35 only.
At asymmetric overloads on multi-pole types, the tripping characteristic will change.
– If a 2-pole type TA35 is loaded at one pole only, the tripping current will be shifted by factor 1.05 (TC-2).
– If a 3-pole type TA35 is loaded at one pole only, the tripping current will be shifted by factor 1.10 (TC-2).
To meet the above tripping characteristic at asymmetric overloads on multi-pole types, the value of the rated current of the CBE has to be multiplied
by the factor mentioned above.
Effect of ambient temperature
The unit is calibrated for an ambient temperature of +23 °C. To
determine the rated current for lower or higher ambient temperature,
use a correction factor from the table below.
Ambient temperature [°C]
Correction factor
1-pole
2-pole
3-pole
–30
0.77
0.76
0.76
–20
0.81
0.81
0.81
0
0.90
0.90
0.90
+23
1.00
1.00
1.00
+40
1.03
1.03
1.06
+50
1.04
1.04
1.10
+60
1.06
1.06
1.14
Example for 2-pole type:
Rated current at +23 °C
Ambient temperature
Correction factor
Chosen rated current at +40 °C
ambient temperature:
5.0 A
+50 °C
1.04
5 A x 1.04 = 5.2 A
circuit breakers
circuit breakers
Standard rated currents and typical internal resistance
Code
In [A]
Ri [W]
Z05
0.05
200.0
J01
0.1
70.0
J05
0.5
2.750
J10
1.0
0.720
J15
1.5
0.340
J20
2.0
0.187
J25
2.5
0.115
J28
2.8
0.089
030
3.0
0.059
040
4.0
0.059
050
5.0
0.044
060
6.0
0.028
070
7.0
0.0142
080
8.0
0.0142
100
10.0
0.0109
120
12.0
0.0086
140
14.0
0.0072
150
15.0
0.0056
160
16.0
0.0056
180
18.0
0.0052
200
20.0
0.0052
unprotected poles (without bimetal) 2.2 mW
Approvals
# of poles
Rated currents
Rated voltage AC
Rated voltage DC
1
0.05…20 A
240 V
32 V
UL
2
0.05…20 A
240 V
60 V
3
0.05…12 A
415 Y/240 V
—
0.05…20 A
240 V
32 V
UL
2
0.05…20 A
240 V
60 V
3
0.05…12 A
415 Y/240 V
—
VDE
CSA C22.2 235 1 1
0.05…20 A
240 V
32 V
2
0.05…20 A
240 V
60 V
3
0.05…12 A
415 Y/240 V
—
UL 1077 CQC
IEC 60934
1
0.05…20 A
240 V
32 V
GB 17701
2
0.05…20 A
240 V
60 V
3
0.05…12 A
415 Y/240 V
—
Actual information about approvals can be found on: www.schurter.com/approvals.
circuit breakers
TA35
www.schurter.com/pg17_18_19
Order Code
Number of switched poles 1-pole2-pole
3-pole
Number of protected poles
0
1
0
12
0
LINE
LINE
LINE
LINE
LINE
LINE
P1
P2
P1
P2
P1
P2
P3
P1
P1
P1
Basic type
EFC
LOAD
EFT
LINE
P1
P2
P3
5
6
4
4
7
LOAD
3
P2
4
4
7
LOAD
8
EBC
5
7
LOAD
LOAD
EBT
8
8
9
LOAD
LOAD
EBD
EKC
EKD
Other versions on request
TA35-
EBT
T
F
120
C0
No other
features
Frontbezel and actuation knob
Bezel
Knob
T
N
black
without bezel
black
without knob
Without thermal overload protection: code C00
With thermal overload protection: rated current In (A)
In
Bezel marking
Surface
Symbol
F
N
relief recessed
no marking
I 0
no marking Code
0.05 Z05
0.1 J01
0.2 J02
0.3 J03
0.4 J04
0.5 J05
0.8 J08
In
Code
In
Code
In
Code
1.0
1.2
1.5
2.0
2.5
3.0
3.5
J10
J12
J15
J20
J25
030
035
4.0
5.0
6.0
7.0
8.0
10.0
12.0
040
050
060
070
080
100
120
14.0
15.0
16.0
18.0
20.0
140 *
150 *
160 *
180 *
200 *
0ther rated currents on request.
circuit breakers
* 3-pole max. 12A
circuit breakers
Dimensions
TA35 1-pole
49.6
19.2
13.7
2
39
15
40
47
LINE
55.6
ø 3.4
47
ø 24
24.5
1
2
4
P1
10.6
7
2.3
21.3
33.8
7.1
6.3 x 0.8 mm
18.2
5.9
39
Screw Type: 2 x PT WN1413 KA 35 x 12
TA35 2-pole
49.6
30.2
13.7
2
39
15
40
LINE
55.6
ø 3.4
47
ø 24
24.5
1
2
10.6
7
2.3
4
P1
5.9
7.1 11
21.3
33.8
6.3 x 0.8 mm
39
Screw Type: 2 x PT WN1413 KA 35 x 12
TA35 3-pole
49.6
41.2
13.7
2
39
15
40
LINE
2
7
10.6
2.3
21.3
4
P1
5.9
7.1 11
11
6.3 x 0.8 mm
33.8
39
Screw Type: 2 x PT WN1413 KA 35 x 12
24.5
55.6
ø 3.4
47
ø 24
1
circuit breakers
TA35
www.schurter.com/pg17_18_19
Front bezel/knob
52
Switching angle
ø 38
(38.2 - 41.2)
18
R3
35°
OFF
ON
2-3
Cut-out
40
90˚
25
20
20
ø 8.4
4
Mounting instructions
Customer specific bezels/actuator designs possible
circuit breakers