OMRON E5C4-Q40K

Temperature Controller
E5C4
DIN-sized (48 x 48 mm) Temperature
Controller With Digital Setting
Compact, low-cost Temperature Controller
Incorporates proportional adjustment and reset
adjustment function.
Incorporates a plug-in socket, thus allows to
DIN-track and flush mounting.
Ordering Information
Temperature Controllers
Setting method
Digital setting
Indication
method
Digital indication
Control
mode
ON/OFF
P
Note:
Output
Model
Thermocouple
(with sensor burnout detection
circuit)
Platinum resistance
thermometer
JPt100
Relay
E5C4-R20K
E5C4-R20J
E5C4-R20P
Voltage (for
driving SSR)
E5C4-Q20K
E5C4-Q20J
E5C4-Q20P
Relay
E5C4-R40K
E5C4-R40J
E5C4-R40P
Voltage (for
driving SSR)
E5C4-Q40K
E5C4-Q40J
E5C4-Q40P
When placing an order, specify the standard temperature range and supply voltage in addition to the model number.
(e.g., E5C4-R20K 0°C to 399°C 100/110 VAC)
Accessories (Order Separately)
Name
Model
Front Connecting Socket
P2CF-08
Back Connecting Socket (for flush mounting)
P3G-08
Watertight Cover
Y92A-48N
Temperature Ranges
Input
Thermocouple
K (CA)
Chromel vs. alumel
Range
Setting
Platinum resistance
thermometer
J (IC)
Iron vs. constantan
JPt100
°C
0 to 399
0 to 999
0 to 399
0 to 99.9
°F
32 to 799
32 to 999
32 to 999
32 to 799
32 to 199
1°C/°F
1°C/°F
1°C/°F
0.1°C/1°F
1
E5C4
E5C4
Specifications
Ratings
Supply voltage
100/110, 200/220, 110/120, 220/240 VAC, 50/60 Hz
Operating voltage range
90% to 110% of rated supply voltage
Power consumption
Approx. 2 VA
Input
Thermocouple (with sensor burnout detection circuit) or platinum resistance thermometer
Control mode
ON/OFF or P control
Setting method
Digital setting
Indication method
Digital indication
Control output
Relay output:
SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA)
Voltage output for SSR: 10 mA at 5 VDC (with short-circuit protection)
H: 5±1 V; L: 0.5 V max.
Characteristics
Setting accuracy
±2% FS max.
Indication accuracy
±2% FS max.
Indication range
Within set temperature range
Hysteresis
Approx. 0.2% FS (fixed)
Proportional band
3% FS (fixed)
Proportional period
Relay output:
Voltage output:
Reset range (see note 1)
±1.5% FS min. (variable)
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts
Vibration resistance
Malfunction: 10 to 55 Hz, 0.3-mm double amplitude for 10 min each in X, Y, and Z directions
Destruction: 16.7 Hz, 4-mm double amplitude for 2 hrs each in X, Y, and Z directions
Shock resistance
Malfunction: 147 m/s2 (15G), 3 times each in 6 directions
Destruction: 294 m/s2 (30G), 3 times each in 6 directions
Life expectancy
Mechanical: 10,000,000 operations min.
Electrical:
100,000 operations min. (3 A at 110 VAC, resistive load)
Ambient temperature
Operating:
–10°C to 55°C (with no icing)
Ambient humidity
Operating:
45% to 85%
Enclosure ratings
Front panel: IEC standard IP40 (see note 2)
Terminals:
IEC standard IP00
Weight
Approx. 200 g (with flush-mounting adapter)
Note:
Approx. 20 s
Approx. 2 s
1. The reset adjuster of any E5C4 model with ON/OFF control is used to correct any error of the set temperature that is displayed so
that the displayed temperature will coincide with the temperature that has been preset. The reset shaft of any E5C4 is used to reset
the E5C4 model with proportional control.
2. The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48N.
2
E5C4
E5C4
Nomenclature
Temperature indicator
Operation indicator
Digital switch for
temperature setting
RESET shaft
Negative Value Display (Example: –18°C)
Overflow Display
The following will be displayed if the sensor burnout detection circuit
operates or the process value exceeds the temperature range that
has been preset.
(Except models with a set temperature range from 0°C to 399°C,
32°F to 799°F and 32°F to 199°F.)
Indicates that the temperature
is below 0°C.
Note:
0°C to 999°C or 0°C to 99.9°C
or 32°F to 999°F
0°C to 399°C
The E5C4 does not have a parameter display any temperature below 0°C. Therefore, the accuracy of any temperature below 0° displayed by the E5C4 cannot be guaranteed.
32°F to 799°F
32°F to 199°F
Operation Indicator
Indicator
Red
Output
Lit
ON
Not lit
OFF
3
E5C4
E5C4
Dimensions
Note:
All units are in millimeters unless otherwise indicated.
Terminal Arrangement
(Bottom View)
48 x 48
44.8 x 44.8
Dimensions with Flush-mounting Adapter (Accessory),
and Back Connecting Socket (Sold Separately)
Panel Cutout
Flush-mounting
adapter
Panel
Y92F-30 Flush-mounting adapter
P3G-08 Back
connecting socket
60 min.
60 min.
Tightening screw
(96) (see note)
Note:
109 mm for US08 Back Connecting Socket
Side-by-side Mounting
of N Controllers
Note:
N
2
L
93 +1
0
3
4
5
6
+1
+1
141 +1
237 +1
0 189 0
0 285 0
1. Recommended panel thickness is 1 to 4 mm.
2. Close side-by-side mounting is possible (in a single direction).
Accessories (Order Separately)
P2CF-08 Front Connecting Socket
Terminal Arrangement/
Internal Connections
(Top View)
Eight, M3.5 x 7.5 sems
Mounting Holes
Two, 4.5 dia. or Two, M4
70 max.
Two,
4.5-dia.
holes
Note:
50 max.
20 max.
4
Can also be
mounted to a
DIN track.
E5C4
E5C4
P3G-08 Back Connecting Socket (for Flush Mounting)
Terminal Arrangement/
Internal Connections
(Bottom View)
27 dia.
Installation
Connections
Input
Connect a thermocouple or platinum resistance thermometer to the
E5C4 as shown in the following illustration.
Voltage output (Terminal 6 is
an NC terminal)
Platinum resistance
thermometer input
Relay output
Thermocouple input
Supply voltage
100/110, 200/220,
110/120, 220/240 VAC,
50/60 Hz
Output
If the load circuit is a heating control system, be sure to connect the
load to terminals 4 and 5. If the load circuit is a cooling control system, be sure to connect the load to terminals 4 and 6. If the heating
control system is connected to terminals 4 and 6 or the cooling control system is connected to terminals 4 and 5, the temperature of the
heating control system or cooling control system will be abnormal
and a serious accident may result.
If the E5C4 is in frequent operation, such as proportional operation,
add an appropriate external relay to the E5C4 by considering the capacity of the load and the life of the relay.
Do not ground the output of any E5C4 that has voltage output, otherwise the process temperature may not be accurate.
Power Supply
If a single power supply is used for the E5C4 and the load, the supply
voltage of the power supply may vary greatly when the load is open
or closed if the capacity of the power supply is not large enough.
Make sure that the capacity of the power supply is large enough so
that the supply voltage range will be always from 90% to 110% of the
rated supply voltage.
The E5C4 operates at either 50 or 60 Hz.
5
E5C4
E5C4
Precautions
Mounting
Dismounting
Track Mounting (E5C4 with P2CF-08)
When mounting two or more E5C4 models with track-mounting
sockets, leave a space of approximately 20 mm on both sides of the
sockets where hooks are located.
If flush mounted, loosen the screw of the adapter and disengage the
hooks for dismounting.
Hook
Duct
P2CF-08
Panel
Flush Mounting
Insert E5C4 into the square hole of the panel and insert an adapter
from the back so that there will be no space between E5C4 and the
panel. Then, secure the E5C4 with a screw.
Temperature Setting
The leftmost digit of any E5C4 that has a set temperature range
from 0°C to 399°C will increase by 1 within a range of 0 to 3 each
time the push button for the leftmost digit is pressed. The leftmost
digit indicating 3 will change to 0 when the push button is pressed.
Others
Tightening screw
The P3G-08 can be wired in the same way as the P2CF-08.
6
Do not remove the housing of the E5C4, otherwise the housing may
break.
To clean the surface of the E5C4, use a soft cloth wet with neutral
detergent or alcohol. Do not use any organic solvent, such as paint
thinner or benzine, strong acid or strong alkali to clean the surface of
the E5C4, otherwise the surface of the E5C4 will become damaged.
E5C4
E5C4
7
E5C4
E5C4
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. H82-E1-1
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Systems Components Division
28th Fl., Crystal Tower Bldg.
1-2-27, Shiromi, Chuo-ku,
Osaka 540 Japan
Phone: 06-949-6012 Fax: 06-949-6021
8
Printed in Japan
0496-1M (0496) a