LINEAGEPOWER CP2000AC54PE

Data Sheet
August 2009
Compact Power Line
CP2000AC54 Front-End Power Supply
Input: 100-120/200-240 Vac; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W
Features
• Compact 1-RU form factor providing 20 W/in3
• Constant power from 52 – 58 Vdc
• 2000W from nominal 200 – 240 Vac
• 1200W from nominal 100 – 120 Vac
• Output voltage programmable from 44V – 58 Vdc;
•
•
Applications
• 48Vdc distributed power architectures
• Power over Ethernet
• Routers/Switches
• VoIP/Soft Switches
• LAN/WAN/MAN applications
• File servers
• Indoor wireless
• Telecommunications equipment
• Enterprise Networks
• SAN/NAS/iSCSI applications
• Advanced workstations
•
•
•
•
•
•
•
•
•
•
•
output defaulted to 54V
PMBus compliant dual I2C and RS485 serial bus
communications
Power factor correction (meets EN/IEC 61000-3-2
and EN 60555-2 requirements)
Tested to IEEE802.3 Compliance, 2250 output***
isolation to chassis/signals for POE applications.
(see ordering info)
DC Output over-voltage and over-current
protection
AC Input over-voltage and under-voltage protection
Over-temperature warning and protection
Redundant, parallel operation with active load
sharing and redundant +5V Aux power
Remote ON/OFF
Hot insertion/removal (hot plug)
Four front panel LED indicators
UL* Recognized to UL60950-1, CAN/ CSA† C22.2
No. 60950-1, and VDE‡ 0805-1 Licensed to
IEC60950-1
CE mark meets 2006/95/EC directive§
Internal variable-speed fan control
The CP2000AC54 Front-End Power Supplies in the Compact Power Line platform are specifically
designed to operate as an integral part of a complete distributed power system. The high-density, front-toback airflow rectifier is designed for minimal space utilization and is highly expandable for future growth. It
is provided with many features including PoE isolation, RS485 and dual-redundant I2C communications
busses that allow it to be used in a broad range of applications. The flexible feature set makes this frontend power supply an excellent choice for applications requiring modular ac-to-dc bulk intermediate
voltages, such as in distributed power.
*
†
‡
§
UL is a registered trademark of Underwriters Laboratories, Inc.
CSA is a registered trademark of Canadian Standards Association.
VDE is a trademark of Verband Deutscher Elektrotechniker e.V.
This product is intended for integration into end-user equipment. All the required procedures for CE marking of end-user
equipment should be followed. (The CE mark is placed on selected products.)
** ISO is a registered trademark of the International Organization of Standards.
*** For PoE applications, order the CP2000AC54PEZ, which is 100% factory hipot-tested per IEEE802.3.
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Specifications
Input
Parameter
Min
Typ
Max
Startup Input Voltage
1200W Operation
2000W Operation
85
175
150
Permitted Excursions
275
300
Surges
300
325
Input Frequency
47
120/200/240
200/240
275
275
175
63
13.3
11.2
11.8
9.9
Input Current
Inrush Transient
25
Input Leakage Current
1.5
Power Factor
0.98
85
88
If started within low input line range.
If started within high input line range.
Will derate to 80% of full load; will shutdown
below 150Vac.
May not meet all requirements, but will
maintain output regulation.
May shut down but will not get damaged.
Hz
At 100 Vac
At 120 Vac
At 200 Vac
At 240 Vac
Apk
Measured at 25°C for all line conditions; does
not include X-Capacitors charging.
mA
Measured at 265Vac, 60Hz
From 50% to 100% load.
90
93
%
15
Holdup Time
Vac
A
35
Notes
The power supply automatically configures its
operating mode based on the voltage level it
reads on first turn ON. (This information is
retained as long as internal bias is maintained.)
85
175
Operating Voltage Range
1200W Configuration
2000W Configuration
2000W Configuration
Efficiency
Units
ms
20
At 100 Vac with Vout > 52V and Pout > 50%.
At 230 Vac with Vout > 52V and Pout > 50%.
Measurement starts at zero crossing of the ac
voltage. Alarm issued via PFW signal going LO
5 ms prior to output voltages going out of limits.
Measurements made at 65% full load and
voltage allowed to decay to 49.5V.
For loads below 1200W.
Main Output
Parameter
Min
Typ
Maximum Output Power
Output Voltage Setpoint
Setpoint Accuracy
Overall Regulation
Output Voltage Margin
Maximum Output Current
Current Share
Lineage Power
Max
Units
1200
2000
W
At low-line input from 100-120Vac nominal.
At high-line input from 200-240Vac nominal.
Vdc
Output floats with respect to frame ground.
54
Notes
-1
+1
%
-2
+2
%
44
58
Vdc
Configured by hardware setting.
42
58
Vdc
2
Set either by I C or RS485
23
38.5
A
10
%FL
Includes all variations due to specified load
range, drift, and environmental conditions.
At 1200W, 52V and 100-120Vac.
At 2000W, 52V and 200-240Vac.
Maintains tolerance to the average of all other
rectifiers. Loads > 25%FL
2
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Specifications (continued)
Output (continued)
Parameter
Min
Typ
Max
Units
250
500
2
mVrms
mVpk-pk
mVrms
5,000
µF
2
s
ms
s
%
Output Ripple
RMS (5Hz to 20MHz)
Peak-to-Peak (5Hz to 20MHz)
Psophometric Noise
External Bulk Load Capacitance
0
Turn-On
Delay
1
Rise Time - Standard (PMBus)
2
-Telecom (RS-485)
Overshoot
5
100
5
Load Step Response
∆I
∆V
Response Time
Overload
Power Limit
3
Current Limit Inception
Over-voltage
Delayed
Immediate
Latchoff
50
2000
102
Auto-recoverable
Monotonic Turn_On from 30% to 100% of Vnom
above -5°C operation. Monotonic Turn_On from
60% to 100% of Vnom below -5°C operation.
108
W
%FL
60
65
Vdc
Vdc
∆I/∆t slew rate 1A/µs.
Settling time to within regulation requirements.
Down to -52Vdc
Hiccup current limit. (FL = 38.5A)
200msec delayed shutdown to be implemented.
Instantaneous shutdown above this point.
Three restart attempts may be implemented within a one minute window prior to a latched
shutdown
Over-temperature
Warning
Shutdown
Measured with 20MHz bandwidth under any
condition of loading. Minimum load is 1A.
External capacitance can be increased but the
power supply will not meet its turn-ON rise time
requirement.
%FL
Vdc
ms
2.0
2
Notes
5
°C
20
Implemented prior to commencement of an OT
shutdown
Below the maximum rating of the device being
protected
°C
Temperature hysteresis of approximately 10°C provided between shutdown and restart.
1. Below -5°C, the rise time is approximately 5 minutes to protect the bulk capacitors.
2. Complies with GR947 which calls for a minimum rise time proportional to output load.
3. Fold-down current limit is programmed as a default to permit system start-up when units are plugged in one at a time. Latchoff mode current limit can be activated via an I2c command.
Auxiliary Output
Parameter
Min
Typ
Output Voltage Setpoint
Output Current
Overall Regulation
Units
0.75
A
-5
+10
%
100
mVpk-pk
50
Over-voltage Clamp
110
Notes
Vdc
0.005
Ripple and Noise
Over-current Limit
Max
5
7
Vdc
175
%FL
20MHz bandwidth
Physical
Length (in./mm)
13.85 / 351.8
Width (in./mm)
4.00 / 101.6
Height (in./mm)
1.66 / 42.2
Weight (lb/kg)
4.6 / 2.1
Lineage Power
3
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Specifications (continued)
Environmental
Parameter
Min
Ambient Temperature
Operating
Ambient Derating
2
Power Derating
Storage Temperature
Humidity
Max
Units
Notes
45
1
2
°C
°C
%/°C
%/°C
Air inlet from sea level to 5,000 feet.
Per 1,000 feet above 5,000 feet.
Up to 55°C
From 55 to 75 °C
-40
85
°C
5
95
%
-5
Typ
1
1
Relative humidity, non-condensing
Shock and Vibration
Operational Test
Test Levels
Drop and Tip Over
Earthquake Rating
IEC 68-2
IEC 721-3-2
IEC 68-2-31
4
Acoustic Noise
45
Harmonic Emissions
Radiated Emissions
Zone
4
Per Telcordia GR-63-CORE, all floors, when
installed in CP Shelf.
Noise is proportional to fan speed, load and
ambient temperature.
dBA
Per EN/IEC61000-3-2
FCC and CISPR22 (EN55022) - Class B
3
Conducted Emissions - ac
FCC and CISPR22 (EN55022) Class B
Telcordia GR-1089-CORE - Class A
Conducted Emissions - dc
Telcordia GR-1089-CORE and CISPR22 (EN55022) - Class A
ESD
Error free per EN/IEC 61000-4-2 Level 4 (8 kV contact discharge, 15 kV air discharge).
Radiated Immunity
Error free per EN/IEC 61000-4-3 Level 3 (10 V/m).
Electrical Fast Transient Burst
Error free per EN/IEC 61000-4-4 Level 3 (2 kV, 5 kHz repetition rate)
Lightning Surge
Error Free
Damage Free
EN/IEC61000-4-5 Level 4 (4 kV common mode, 2 kV differential mode).
ANSI C62.41 Level A3 (6 kV common and differential mode)
Conducted Immunity
Error free per EN/IEC 61000-4-6 Level 3 (10Vrms).
Reliability (calculated)
Isolation
Input-Chassis/Signals
Input - Output
Output-Chassis/Signals
Service Life
400,000
1500
3000
2250
10
Hours
At ambient of 25°C at full load per Telcordia SR332, Reliability Prediction for Electronic Equipment,
Method I Case III.
Vrms
Vrms
Vdc
Per EN60950-1.
Consult factory for testing to this requirement
Per IEEE802.3.
Years
25°C ambient, full load excluding fans.
1. Designed to start at an ambient as low as -40°C, but may not meet operational limits until above -5°C.
2. Power derating shall consider only temperature variations at nominal line (100 – 120, 200 – 240Vrms). The unit may derate
faster if the input line is below nominal.
3. Class B radiated emmissions compliance requires the addition of a ferrite bead to each power line cord at the shelf-end of the
cable. See the figure below.
4. Radiated emissions compliance was met using a Lineage Power shelf. This shelf includes output common and differential mode
capacitors that assist in meeting compliance.
Lineage Power
4
Data Sheet
Status and Control
The rectifier provides three means for
monitor/control: analog, PMBus compliant I2C, or
RS485 for interfacing to Lineage Power controllers
or battery plants.
Details of analog controls are provided in this data
sheet under Signal Definitions. Lineage Power will
provide separate application notes on PMBus
protocol for users to interface to the CPL rectifiers.
Contact your local Lineage Power representative
for details.
Hot Plug
When rapidly extracting and reinserting modules
care should be taken to allow for discharging the
internal bias supply so that a predictable restart
could be achieved. The way to ensure that the
circuit sufficiently discharges is to observe the
spinning of the fans after an extraction. The unit
should not be reinserted until the fans stop
spinning.
Compact Power Line
CP2000AC54 Front-End Power Supply
Module Present Signal: This signal has dual
functionality. It can be used to alert the system
when a module is inserted. Has a 500Ω resistor in
series between this signal and Logic GRD. An
external pull-up should not raise the voltage on the
pin above 0.25Vdc. If raised the pin is raised to
5Vdc the write_protect feature of the EEPROM is
enabled.
Protocol Select: Establishes the communications
mode of the power supply, between analog/I2C and
RS485 modes. For RS485, connect 750 – 3.92kΩ
pull-down resistor to 54_OUT(-DC).
Enable: On/Off control when either PMBus
communications or analog functions are utilized as
configured by the Protocol pin. This pin must be
pulled low to turn ON the main output of the power
supply. The power supply will turn OFF if either the
Enable or the ON/OFF pin is released. The Enable
function does not work with the RS-485 protocol.
This signal is referenced to Logic_GRD.
All signals are referenced to Logic GRD unless
otherwise noted. See the Signal Definitions Table
at the end of this document for further description
of all the signals.
ON/OFF: This is a short pin utilized for hot-plug
applications to ensure that the power supply turns
OFF before the power pins are disengaged. It also
ensures that the power supply turns ON only after
the power pins have been engaged. Must be
connected to 54_OUT (-DC).
Input Signals
Output Signals
Control Definitions
Margining: Setpoint of the rectifier can be changed
via this input pin. Programming can be either a
voltage source or a resistance divider. The
margining pin is connected to 3.3Vdc via a 10kΩ
resistor inside the rectifier. See graphs below.
Alert #: PMBus interrupt signal.
Fault: This signal goes LO for any failure that
requires rectifier replacement. Some of these faults
may be due to:
• Fan failure
• Over-temperature condition
• Over-temperature shutdown
• Over-voltage shutdown
• Internal Rectifier Fault
Power Capacity: A HI on this pin indicates rectifier
configured for 2000W operation; a LO indicates
rectifier configured for 1200W operation.
An open circuit on this pin reverts the voltage level
back to the original setting.
Lineage Power
5
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Alarm Table
Power Supply LED State
AC OK
DC OK
Service
Fault
Green
Green
Amber
Red
1
1
0
0
Condition
OK
Thermal Alarm
(5C before shutdown)
Thermal Shutdown
Defective Fan
Blown AC Fuse in Unit
No AC <15mS (single unit)
AC Present but not within limits
AC not present1
Boost Stage Failure
Over Voltage Latched Shutdown
Over Current
Non-catastrophic Internal Failure2
1 Missing Module
Monitoring Signals
(Referenced to Logic_GRD)
Module
Fault
OTW
PFW
Present
HI
HI
HI
LO
1
1
1
0
HI
LO
HI
LO
1
1
1
0
Blinks
0
1
1
1
1
0
0
0
1
0
0
0
0
Blinks
1
1
0
0
0
0
0
0
0
0
0
1
1
1
0
0
0
1
1
0
1
LO
LO
LO
HI
HI
HI
LO
LO
HI
LO
LO
HI
HI
HI
HI
HI
HI
HI
HI
HI
LO
LO
LO
LO3
LO
LO
LO
LO
LO
HI
LO
LO
LO
LO
LO
LO
LO
LO
LO
LO
HI
1
1
1
0
1
1
0
Blinks
0
0
0
Blinks
HI
HI
HI
HI
HI
HI
LO
HI
HI
LO
LO
LO
Standby (remote)
Service Request (PMBus mode)
Communications Fault (RS485 mode)
1
This signal is correct if the rectifier is back biased from other rectifiers in the shelf .
Any detectable fault condition that does not result in the power supply shutting down. For example, ORing FET failure, boost
section out of regulation, etc.
3
Signal transition from HI to LO is output load dependent
2
Output Connector
Mating Connector: AMP 1450572-1
A6
A1
Signal
6
A SCL_0
5
4
3
LOGIC_GRD
P1
P7
Output Power
2
RS_485+
1
MOD_PRES
PFW
B SCL_1
OTW
Alert#_0 Alert#_1
RS_485-
8V_INT
C SDA_0
Margin
Enable
Reset
Ishare
Protocol
D SDA_1
Fault
5VA
Power_Cap
ON/OFF
SHELF_ADDR
P7
P6
Input Power
P5
P4
P3
P2
P1
UNIT_ADDR
54_OUT 54_OUT
(-DC)
(+DC)
Reserved
EARTH LINE-2 LINE-1
(GND) (Neutral) (Line)
Connector is viewed from the rear positioned inside the power supply.
Signal pins columns 1 and 2 are referenced to 54_OUT (-DC).
Signal pins columns 3 through 6 are referenced to Logic GRD.
Last-to-make first-to-break pins.
First-to-make last-to-break longest pin implemented in the mating connector.
Lineage Power
6
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Signal Definitions
All hardware alarm signals (Fault, PFW, OTW, Power Capacity) are open drain FETs. These signals
should be pulled HI to either 3.3V or 5V. Maximum sink current 5mA. An active LO signal (< 0.4Vdc). All
signals are referenced to Logic GRD unless otherwise stated. Contact your Lineage Power representative
for more details.
Function
Label
Type
Description
Output Enable
Enable
Input
If shorted to LOGIC_GRD, the rectifier output is enabled
when using I2C mode of operation. May also be toggled to
reset a latched OFF rectifier. Function not available in
RS485 mode.
Power Fail Warning
PFW
Output
An open drain FET; normally HI, indicating output power is
present. Changes to LO at least 5msec before the output
voltage is lost.
I2C Interrupt
Alert#_0
Alert#_1
Output
Interrupt signal via I2C lines indicating that service is
requested from the host controller. This signal pin is pulled
up to 3.3V via a 10kΩ resistor and switches to active LO
when an interrupt occurs.
Rectifier Fault
Fault
Output
Indicates that an internal fault exists. An open drain FET;
normally HI, changes to LO.
Module Present
MOD_PRES
Output
Short pin, see Status and Control description for further
information on this signal.
ON/OFF
ON/OFF
Input
Short pin, connects last and breaks first; used to activate
and deactivate output during hot-insertion and extraction,
respectively. Ref: 54_OUT (-DC)
Protocol select
Protocol
Input
See Status and Control description for further information
on this signal. Ref: 54_OUT (-DC).
Margining
Margin
Input
Allows changing of output voltage through an analog
voltage input or via resistor divider.
Over-Temperature Warning
OTW
Output
An open drain FET; normally HI, changes to LO
approximately 5°C prior to thermal shutdown.
Power Capacity
POWER_CAP
Output
An open drain FET; Used to indicate rectifier operation
mode; HI indicates 2000W operation and LO indicates
1200W operation.
Rectifier address
Unit_addr
Input
Voltage level addressing of rectifiers within a single shelf.
Ref: 54_OUT (-DC).
Shelf Address
Shelf_addr
Input
Voltage level addressing of rectifiers within multiple
shelves. Ref: 54_OUT (-DC).
Back bias
8V_INT
_
Diode OR’ed 8Vdc drain; used to back bias
microprocessors and DSP of failed rectifier from operating
rectifiers. Ref: 54_OUT (-DC).
Mux Reset
Reset
Input
Resets the I2C lines to I2C line 0.
Standby power
5VA
Output
5V at 0.75A provided for external use by either adjacent
power supplies or the using system.
Current Share
Ishare
-
A single wire interface between each of the power unit
forces them to share the load current. Ref: 54_OUT (-DC).
I2C Line 0
SCL_0, SDA_0 Input
I2C line 0.
I2C Line 1
SCL_1, SDA_1 Input
I2C line 1.
RS485 Line
RS_485+
RS_485-
RS485 line.
Lineage Power
Input
7
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Front Panel LEDs
I2C Mode
Analog Mode
RS485 Mode
ON: Input ok
Blinking: Input out of limits
ON: Output ok
Blinking: Overload
ON: Over-temperature
Warning
!
ON: Over-temperature Warning
Blinking: Service
ON: Fault
Dimensions
ON: Over-temperature
Warning
ON: Fault
Blinking: Not communicating
13.85 in.
(351.8 mm)
4.00 in.
(101.6 mm)
Rear View
1.70 in.
(43.2 mm)
Top View
Front View
Ordering Information
Item
Description
Comcode
CP2000AC54PE
Designed to IEEE802.3 POE compliance, RoHS 5/6
CC109120722
CP2000AC54PEZ
Tested to IEEE802.3 POE compliance, RoHS 6/6
CC109139408
Asia-Pacific Headquarters
Tel: +65 6593 7211
World Wide Headquarters
Lineage Power LLC
601 Shiloh Road, Plano, TX 75074, USA
+1-800-526-7819
(Outside U.S.A.: +1-972-284-2626)
www.lineagepower.com
e-mail: [email protected]
Europe, Middle-East and Africa Headquarters
Tel: +49 898 780 672 80
India Headquarters
Tel: +91 80 2841 1633
Lineage Power reserves the right to make changes to the product(s) or information contained herein without notice. No liability is assumed as a result of their use or
application. No rights under any patent accompany the sale of any such product(s) or information.
© 2009 Lineage Power LLC, (Mesquite, Texas) All International Rights Reserved.
Revision : GGS-August 2009
Lineage Power
Page 8