MAGNETROL 801-2031-A40

Kotron® Model 801
RF Capacitance
Transmitter for
Level/Flow/Volume
D E S C R I P T I O N
The Kotron Model 801 Transmitter is a new generation
RF Capacitance multi-function transmitter that offers the
user unparalleled power. The preamplifier circuit provides installation flexibility of a 2500 feet maximum
remote distance. The Model 801 can interface with two
separate vessels, essentially making it a mini-multiplexer,
while software mathematics allow for the sum or differential of the two signals.
F E A T U R E S
• Capability for dual input of two probes from separate
vessels.
• The level signal from one vessel can be mathematically
added to or subtracted from another vessel.
• Level/Volume and Level/Flow characterization for all
standard vessels and flumes/weirs.
• Integral keypad on front panel maintains NEMA 4X
rating; no need to open the enclosure during
calibration or setup.
• Provides one 4–20 mA isolated analog output signal.
• Four 10-amp SPDT relays provide complete flexibility
from simple alarm applications to complex pump
control including lead/lag alternation of pumps.
• 16-character alphanumeric display of all parameters.
• Display may be configured in units of level, volume,
or flow.
• Continuous diagnostics check all major functions of
the device including integrity of the probe.
A P P L I C A T I O N S
• Hydrocarbons and solvents
• Slurries
• Viscous fluids
• Unit may be remote mounted up to 2500 feet (760 m)
using twisted, shielded pair cable.
• Intrinsically safe version can be remote mounted to
800 feet (240 m) and is supplied with on-board barriers.
• RS-232 for downloading of collected flow data (up to
the last 31 days).
• Open channel flow
• High temperature/pressure liquids
• Acids
T E C H N O L O G Y
The amount of capacitance developed in any vessel is
determined by the size (surface area) of the probe, the
distance from the probe to its ground reference, and the
dielectric constant of the medium being measured.
Considering that the probe’s mounting position is fixed
and the dielectric of the medium is constant, then the
amount of capacitance developed in a vessel becomes
dependent upon the amount of the probe which is
covered with media.
T Y P I C A L
As the media rises and falls in the tank, the amount of
capacitance developed between the probe and the
ground reference also rises and falls. The Pulsatel circuit
mounted on the probe changes the capacitance signal to
a digital waveform proportional to the change in level.
The amplifier then converts this digital signal into an
isolated 4–20 mA analog output signal.
A P P L I C A T I O N S
Level/Volume monitoring of two tanks
The Model 801, with its dual input capability, can
monitor the level or volume of two different tanks.
The tanks can be of different sizes and configuration and contain different materials. The display
will provide a visual indication of the level or
volume and the alarms can be set up to provide
high and low level detection on each tank.
2
P1
P2
HL
HL
LL
LL
T Y P I C A L
A P P L I C A T I O N S
Sum the volume of two tanks
P1
Using the dual input, the 801 can measure the total
volume of two tanks. For instance there may be a
main storage tank plus a smaller day tank. The 801
will display the volume of each tank plus provide a
4–20 mA signal of the total volume. Each tank can be
a different size and shape. Alarms can also be provided for high or low level detection.
P2
Level differential
The 801 is ideal for bar screen applications. Probes can be installed on
either side of the bar screen. The
801 can measure the difference in
level measured by the two probes.
This will provide an indication that
the bar screen requires cleaning.
The 4–20 mA output can be provided
on the actual level or on the level
differential between the two probes.
Alarms can also be set if the differential reaches a specific value.
P1
minus
P2
Flow
Bar Screen
Two Inputs — Differential (Bar Screen)
3
S P E C I F I C A T I O N S
Supply voltage
Output:
Analog
Digital
Range
Accuracy
Repeatability
Linearity
Data:
Entry
Indication
Relays 4 SPDT:
AC
DC
Set point range
Differential range
Time delay
Power consumption
Humidity
Response time
Ambient temperature (electronics):
Without heater and thermostat
With heater and thermostat
Temperature coefficient of set point
Maximum remote mount distance:
Standard
Intrinsically safe
4
120 VAC, 50/60 Hz (+10 / -15%)
240 VAC, 50/60 Hz (+10 / -15%)
24 VDC (±10%)
4–20 mA (isolated), reversible 1000 ohms max. loop resistance
RS-232
5 pF minimum / 50,000 pF maximum
Better than 1.0% of span
±0.1%
±0.5%
Full numeric keypad
16-character alphanumeric LCD display
10 amp @ 120/240 VAC resistive
10 amp @ 30 VDC resistive, 0.5 amp @ 125 VDC resistive
0–50,000 pF
0.50 pF minimum / 50,000 pF maximum
0–120 seconds level rising, falling, both
15 Watts maximum
65 Watts maximum with heater
99% non-condensing (electronics)
0.5 to approximately 2 seconds, depending upon probe
capacitance and damping value
-4° to +160° F (-20° to +70° C)
-40° to +160° F (-40° to +70° C)
±0.01% / degree F (±0.018% / degree C)
2500 feet (760 meters)
800 feet (240 meters)
A G E N C Y
A P P R O V A L S
Agency
Approved Model
Protection Method
FM
Electronics (with any probe)
801-X034-X4X
801-X134-X4X
801-X234-X4X
Non-incendive
Class I, II, III, Div 2, Groups A, B, C, D, F & G
NEMA 4X, IP 65
801-X334-X4X
801-X434-X4X
Non hazardous
NEMA 4X, IP 65
Probe
Intrinsically safe
Electronics
801-X031-X4X
801-X131-X4X
801-X231-X4X
Non-incendive
Class I, II, III, Div 2, Groups A, B, C, D, F & G
NEMA 4X, IP 65
801-X131-X4X
801-X131-X4X
Non hazardous
Rigid insulated probes only
Explosion proof
Class I, Div 1, Groups C & D
Class II, Div 1, Groups E, F & G
801-XX34-N4X
Electronics
Suitable for
Probe
Intrinsically safe
801-XX31-N4X
Electronics
Suitable for
Rigid insulated probes only
Explosion proof
CSA
Area Classification
Class I, Div 1, Groups A, B, C, D, E, F & G
Class II, Div 1, Groups E, F & G
Class III
NEMA 4X, IP 65
Class I, Div 1, Groups B, C & D
Class II, Div 1, Groups E, F & G
NEMA 4X, IP 65
Class I, II, III, Div 2, Groups A, B, C, D, E, F & G
bare probes not approved for Groups E & F
TYPE 4X
Class I, Div 1, Groups A, B, C, D, E, F & G
Class II, Div 1, Groups E, F & G
Class III
bare probes not approved for Groups E & F
TYPE 4X
Class I, II, III, Div 2, Groups A, B, C, D, E, F & G
TYPE 4X
Class I, Div 1, Groups C & D
Class II, Div 1, Groups E, F & G
TYPE 4X
CAUTION: Agency ratings are dependent upon probe selection.
5
M O D E L
N U M B E R
BASIC MODEL NUMBER
801
Kotron Transmitter
NUMBER OF PROBES/OUTPUT
2
4
1 probe – One 4–20 mA output with RS-232
2 probes – One 4–20 mA output with RS-232
INPUT POWER
0
1
2
3
4
120
240
24
120
240
VAC, 50/60 Hz
VAC, 50/60 Hz
VDC
VAC with heater and thermostat
VAC with heater and thermostat
REMOTE MOUNTING CONFIGURATION
1
4
NEMA 4X
NEMA 4X with intrinsically safe probe circuit
HOUSING
A
N
NEMA 4X Noryl electronics with 316 stainless steel
remote probe housing
NEMA 4X Noryl electronics with aluminum remote
probe housing
SPECIAL OPTIONS
0
1
2
3
8
6
0
1
3
4
None
Mechanical totalizer
31 day data logger (smart watch)
Mechanical totalizer and 31 day logger
P R O B E S
R E M O T E
A full range of rigid and flexible probes, for conductive
and non-conductive process media, is available in various lengths and materials of construction. For further
information on probe assemblies, refer to bulletin 50-125.
Specify remote cable by exact length between 10 and 999
feet using part number 009-7146-XXX.
D I M E N S I O N A L
I N C H E S
( m m )
For lengths from 1000 to 2500 feet, use part number
X009-7146-999. Specify total length required.
Example: X009-7146-999, X=1200 feet
S P E C I F I C A T I O N S
4.63
(118) Dia.
3.00
(76)
4.63
(118) Dia.
3.00
(76)
9.50
(241)
2.75
(70)
2.75
(70)
13.00
(330)
9.50
(241)
3/4"
NPT
3.23
(82)
Optional
Mounting
Flange
3/4" NPT
4.67
(119)
3/4" NPT
Optional
Mounting
Flange
3/4" NPT
5.50
(139)
4.87
(124)
I.L.
1.25
(31)
6.00
(152)
.50 (13)
.625 (16)
Electronics Housing
C A B L E
Remote Mount/Standard Rigid Probe
Optional Anchor
Assembly
P/N 032-8814-001
2.95
(75)
.75
(19)
Optional
Weight
P/N 004-4355-001
Remote Mount/Flexible Probe
7
Q U A L I T Y
The quality assurance system in place at
Magnetrol guarantees the highest level of
Magnetrol’s quality assurance system is registered to ISO 9001 affirming its commitment
quality throughout the company. Magnetrol
is committed to providing full customer
to known international quality standards
providing the strongest assurance of product
satisfaction both in quality products and
quality service.
and service quality available.
W A R R A N T Y
All Magnetrol electronic level and flow
controls are warranted free of defects in
materials or workmanship for one full year
from the date of original factory shipment.
If returned within the warranty period;
and, upon factory inspection of the control,
the cause of the claim is determined to be
covered under the warranty; then, Magnetrol
will repair or replace the control at no cost
to the purchaser (or owner) other than
transportation.
Magnetrol shall not be liable for misapplication, labor claims, direct or consequential
damage or expense arising from the installation or use of equipment. There are no other
warranties expressed or implied, except
special written warranties covering some
Magnetrol products.
For additional information, see Instruction Manual 50-624.
5300 Belmont Road • Downers Grove, Illinois 60515-4499 • 630-969-4000 • Fax 630-969-9489 • www.magnetrol.com
145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306
Heikensstraat 6 • B 9240 Zele, Belgium • 052 45.11.11 • Fax 052 45.09.93
Regent Business Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317
Copyright © 2009 Magnetrol International, Incorporated. All rights reserved. Printed in the USA.
Performance specifications are effective with date of issue and are subject to change without notice.
BULLETIN: 50-105.8
EFFECTIVE: July 2009
SUPERSEDES: June 2001