MEANWELL DR

DR-UPS40
40A DC UPS Module
Features :
Battery controller for DIN Rail UPS system
Parallel connection to DC BUS
Suitable for 24V system up to 40A
Installed on DIN Rail TS35 / 7.5 or 15
Built-in battery test function
Battery polarity protection
Relay contact signal output and LED indicator for DC BUS OK,
Battery Fail, and Battery Discharge
Cooling by free air convection
3 years warranty
SPECIFICATION
MODEL
DR-UPS40
DC INPUT / DC VOLTAGE (Typ.)
DC BUS
RATED CURRENT
24 ~ 29V
BATTERY
INPUT /
OUTPUT
40A
VOLTAGE RANGE (Typ.)
21 ~ 29V
CURRENT RANGE
0 ~ 40A
CHARGE CURRENT (Typ.)
2A
EXTERNAL BATTERY (Typ.)
4 / 7 / 12AH / 24V
RELAY CONTACT RATING (max.) 30VDC, 1A
Relay contact : Short when DC voltage between 21~29V( 3%), relay contacts
DC BUS OK
FUNCTION BATTERY FAIL
BATTERY DISCHARGE
ENVIRONMENT
LED(Green) : DC BUS OK : light ; DC BUS fail : dark
Note.2
Relay contact : Short when battery failure is observed through the battery test function, relay contacts
LED(Red) : Battery over-discharge warning or battery broken : light ; Battery OK : dark
Relay contact : Short when battery in discharge condition, relay contacts
LED(Yellow) : Battery discharging : light ; Battery is not discharging or discharging current<2.0A : dark
WORKING TEMP.
-20 ~ +70
WORKING HUMIDITY
20 ~ 90% RH
STORAGE TEMP., HUMIDITY -20 ~ +85
, 10 ~ 95% RH
VIBRATION
Component : 10 ~ 500Hz, 2G 10min./1cycle, 60min. each X, Y, Z axes ; Mounting : Compliance to IEC600068-2-6
WITHSTAND VOLTAGE
Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal :0.5KVAC
Terminal-Chassis :>100M Ohms / 500VDC / 25
SAFETY & ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
EMC
(Note 3)
OTHERS
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
NOTE
/ 70% RH
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, heavy industry level, criteria A
161.9Khrs min. MIL-HDBK-217F (25 )
55.5*125.2*100mm (W*H*D)
0.55Kg; 20pcs/12Kg/1.29CUFT
1. All parameters NOT specially mentioned are measured at rated load and 25 of ambient temperature.
2. Every 25 seconds, unit will send out test signal through "Battery Fail" relay contact and LED indicator once the battery is fail.
3. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
File Name:DR-UPS40-SPEC 2010-10-18
DR-UPS40
40A DC UPS Module
Mechanical Specification
Unit:mm
100
Case No.923D
125.2
LED
1
3
TB2
1
2
3
4
5
6
TB1
4
55.5
2
Terminal Pin No. Assignment (TB1)
35
Pin No.
1
2
3
4
Assignment
BATTERY INPUT +
BATTERY INPUT DC INPUT DC INPUT +
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Terminal Pin No. Assignment (TB2)
Pin No.
1
2
3
4
5
6
Block Diagram
Assignment
BAT DISC 1
BAT DISC 2
BAT FAIL 1
BAT FAIL 2
DC OK 1
DC OK 2
Derating Curve
25Ax2
+
100
+
CHARGE
CIRCUIT
LIMIT
INPUT
POWER
SUPPLY
BAT.
TEST
DETECTION
CIRCUIT
24V
BATTERY
80
60
LOAD (%)
LOAD
40
20
-20
DC
OK
BAT
BAT
FAIL DISCHARGE
0
10
20
30
45
50
60
70 (VERTICAL)
AMBIENT TEMPERATURE ( )
File Name:DR-UPS40-SPEC 2010-10-18
DR-UPS40
40A DC UPS Module
Suggested Application
1.Back up connection for AC interruption
DR-UPS40
24V
PSU
Battery
24V/40A max.
BAT
+ -
-
Load
DC
- +
+
+
+
-
-
2.Combine redundancy module (DR-RDN20) to back up AC interruption or failure of PSU
DR-UPS40
DR-RDN20
24V
Battery
PSU
BAT
DC
+ - - +
Vout
Load
Vin
+ - - - B+ A+
-
+
+
-
+
-
File Name:DR-UPS40-SPEC 2010-10-18