PROTEC 587B302LPE

05064
587B062LPE - 587B302LPE
Only One Name Means ProTek’Tion™
low profile 240v ac power line surge suppressor
Description
The 587B Low Profile (LPE) Series is designed for European applications where no line to ground or neutral to ground
suppression is allowed. These modules employ a three stage technology proven to be the most cost effective and reliable method in protecting sensitive electronic equipment from over voltage transients.
This series is designed to protect AC powered equipment from the 6,000 Volt peak open circuit voltage and 3,000 Amp
short circuit current as defined in ANSI/IEEE C62.41, Category CI.
The 587BxxxLPE Series offers a high degree of protection against 240 VAC EMI line noise. It is ideal for protecting 800
Volt components because the solid state TVS technology assures that the line-to-neutral voltage will not exceed 800
Volts. While the modules are designed for transient voltage protection, the advanced circuitry will also attenuate the
amplitude and slow the rate of rise of high frequency noise acting as an EMI filter. The 587BxxxLPE Series includes
common mode protection, which are effective in reducing interference from line to equipment and are effective in
reducing equipment generated noise to meet FCC, VDE and CSA interference requirements.
low profile
Features
applications
• Compatible with IEC 61000-4-5 (Surge): 1kA, 8/20µs, Level 4 (LineGnd) & 333A, Level 4 (Line-Line)
• Meets ANSI/IEEE C62.41 Outdoor Requirements
• Listed to CSA, File LR65240 (Except 587B302LPE)
• Differential Mode Protection
• Low Clamping Voltage
• Nanosecond Response Time
• Long Life and Maintenance Free
• Finger Safe Connections
• Hard Wired Equipment AC Power Protection
• Load Side Distribution Systems
• Secondary Protection for Light Industrail AC Power
Mechanical characteristics
• Low Profile Plastic Package
• Approximate Weight: 360 grams
• Flammability Rating UL 94V-0
figure 2
typical clamping action of a 15a module
8
6
6
4
Kilovolts
Kilovolts
figure 1
transient voltage threat condition
4
2
0
2
0
0
10
20
30
40
50
60
0
t - Time - µs
10
20
30
40
50
60
t - Time - µs
Figures 1 and 2 are photographs of digitized waveforms showing the typical clamping action of a 15A module. A 12 Ohm resistor is used to represent a 10A equipment load. The load is then subjected to the ANSI/IEEE C62.41 Catagory CI test conditions (6000V/3000A). These photographes
contrast the effect on equipment with and without the protector.
05064.R6 2/11
Page 1
www.protekdevices.com
05064
587B062LPE - 587B302LPE
Only One Name Means ProTek’Tion™
typical device characteristics
MAXIMUM RATINGS @ 25°C Unless Otherwise Specified
PARAMETER
Operating Line Voltage: +10%
SYMBOL
VALUE
UNITS
VO
240
Volts AC
Line Current: 587B062LPE/587B102LPE/587B162LPE/587B302LPE
-
6/10/16/30
Amps
Peak Transient Voltage
-
6000
Volts
Peak Transient Current
-
3000
Amps
Current Leakage @ 2400 Volts AC: Line-to-Neutral
-
1
mA
Operating Temperature - Note 1
TA
-40 to 85
°C
TSTG
-40 to 85
°C
Storage Temperature - Note 1
Notes
1. Measured at the center of the mounting surface.
ELECTRICAL CHARACTERISTICS @ 25°C Unless Otherwise Specified
Protection
mode
(Note 1)
maximum
clamping voltage
(Note 2)
open circuit
voltage
(Note 2)
short circuit
current
(Note 2)
volts
@1.2/50µs
volts
@ 8/20µs
amps
800
6000
3000
Line to Neutral
Notes
1. Differential Mode Protection: Line to Neutral.
2. Test condition responses to transient voltages.
arrestor definitions
Clamping Voltage: The clamping voltage of an arrester is the voltage that appears across its terminals during conduction of a transient current.
Standard Wave Form: The waveform of a surge current or voltage is designated by a combination of two numbers. The first number is for the time of the wave front
expressed in microseconds from zero to the peak of the wave. The second number is for the time of the wavetail also expressed in microseconds from zero to the
instant that the wavetail reaches one half of the crest or peak value, i.e., 8/20 µs waveform.
Transient Current: The transient current of an arrestor is the peak surge current which flows through the arrester when voltage clamping occurs.
operation
For maximum effectiveness, the protector should be installed directly after the AC line on/off switch and fuse. This will protect the electronics from the AC line switch
arcing and the severe transients caused by a fuse clearing.
Some heat is produced when operating at full current load, and heat sinking may be required to maintain case temperature below 85°C. The case temperature is
measured at the center of the mounting surface. The unit should not be mounted to a low combusting temperature material such as wood.
High energy transients will cause a large circulating current in the AC input line (2,500A is possible). To prevent electromagnetic coupling, the AC line on the input side
of the protector must be dressed away from other wiring, magnetic shielding may be required. In addition, the electrical service must be connected to a low impedance earth ground.
05064.R6 2/11
Page 2
www.protekdevices.com
05064
587B062LPE - 587B302LPE
Only One Name Means ProTek’Tion™
package information
outline dimensions
dim
millimeters
min
max
inches
min
max
A
96.8
3.81
B
88.9
3.50
C
110.92
D
E
111.68
14.43
4.40
0.586
43.89
F
G
4.37
44.39
1.62
27.9
1.72
1.10
58.04
58.80
2.29
2.32
A
E
D
B
F
C
G
Line 1 Out
Line In
Dia. 0.181”
Line 2 Out
DEVICE
MARKING
Neutral 1 Out
Neutral In
Neutral 2 Out
Ground In
Ground Out
ORDERING INFORMATION
base PART NUMBER
(xx = Voltage)
MARKING
587BxxxLPE
Part Number, Date Code, Voltage, Logo, Current Rating, CSA Logo
05064.R6 2/11
Page 3
www.protekdevices.com
05064
587B062LPE - 587B302LPE
Only One Name Means ProTek’Tion™
company information
COMPANY PROFILE
ProTek Devices, based in Tempe, Arizona USA, is a manufacturer of Transient Voltage Suppression (TVS) products designed specifically for
the protection of electronic systems from the effects of lightning, Electrostatic Discharge (ESD), Nuclear Electromagnetic Pulse (NEMP), inductive switching and EMI/RFI. With over 25 years of engineering and manufacturing experience, ProTek designs TVS devices that provide
application specific protection solutions for all electronic equipment/systems.
ProTek Devices Analog Products Division, also manufactures analog interface, control, RF and power management products.
CONTACT US
Corporate Headquarters
2929 South Fair Lane
Tempe, Arizona 85282
USA
By Telephone
General: 602-431-8101
Sales: 602-414-5109
Customer Service: 602-414-5114
By Fax
General: 602-431-2288
By E-mail:
Sales: [email protected]
Customer Service: [email protected]
Technical Support: [email protected]
Web
www.protekdevices.com
www.protekanalog.com
COPYRIGHT © ProTek Devices 1998 - This literature is subject to all applicable copyright laws and is not for resale in any manner.
SPECIFICATIONS: ProTek reserves the right to change the electrical and or mechanical characteristics described herein without notice.
DESIGN CHANGES: ProTek reserves the right to discontinue product lines without notice and that the final judgement concerning selection and specifications is the buyer’s and that in furnishing engineering
and technical assistance. ProTek assumes no responsibility with respect to the selection or specifications of such products. ProTek makes no warranty, representation or guarantee regarding the suitability of
its products for any particular purpose, nor does ProTek assume any liability arising out of the application or use of any product or circuit and specifically disclaims any and all liability without limitation special,
consequential or incidental damages.
LIFE SUPPORT POLICY: ProTek Devices products are not authorized for use in life support systems without written consent from the factory.
PATENT INFORMATION: This device is patented under U.S. Patent No. 4,563,720
05064.R6 2/11
Page 4
www.protekdevices.com