ADVANTECH APAX-5001

APAX-5013
APAX-5017
APAX-5018
8-ch RTD Module
12-ch Analog Input Module
12-ch Thermocouple Input Module
NEW
NEW
RoHS
APAX-5013
APAX-5017
COMPLIANT
2002/95/EC
Specifications
APAX-5018
ƒƒ Dimensions (W x H x D) 30 x 139 x 100 mm
ƒƒ Weight
170 g
ƒƒ Power Consumption
4 W @ 24 VDC (APAX-5017)
(typical) 3.5 W @ 24 VDC (APAX-5018)
Analog Input
ƒƒ Channels
ƒƒ Input Type
Protection
ƒƒ Isolation between
2,500 VDC
Channels and Backplane
Environment
ƒƒ Operating Temperature -10 ~ 60° C (when mounted vertically)
ƒƒ Storage Temperature -40 ~ 70° C
ƒƒ Relative Humidity 5 ~ 95% (non-condensing)
Ordering Information
APAX-5013
APAX-5001
APAX-5002
APAX-5343E
Analog Input
8
>10 MW
Pt-100, Pt-200, Pt-500, Pt-1000, Balco, Ni 518 RTD
(3-wire)
Pt-100, Pt-200, Pt-500, Pt-1000:
-120 ~ 130° C, -200 ~ 850° C
Supports both IEC 60751 ITS90 (0.03851 W/W/° C)
and JIS C 1604 (0.03916 W/W/° C)
Balco 500: -30 ~ 120° C
Ni 518: -80 ~ 100° C, 0 ~ 100° C
Yes
ƒƒ Configure Different
Range for Each Channel
ƒƒ Resolution
16-bit
ƒƒ Sampling Rate
10 sample/second (total)
ƒƒ CMR @ 50/60 Hz
90 dB
ƒƒ NMR @ 50/60 Hz
60 dB
ƒƒ Noise Rejection
Hardware Filter (50/60 Hz)
ƒƒ
ƒƒ
ƒƒ
ƒƒ
2002/95/EC
General
ƒƒ Dimensions (W x H x D)30 x 139 x 100 mm
ƒƒ Weight
170 g
ƒƒ Power Consumption
2.5 W @ 24 VDC (typical)
ƒƒ Temperature Range
COMPLIANT
Specifications
General
ƒƒ Channels
ƒƒ Input Impedance
ƒƒ Input Type
RoHS
8-ch RTD Module
1-slot Backplane Module
2-slot Backplane Module
Power Supply for APAX Expansion Module
ƒƒ
ƒƒ
ƒƒ
ƒƒ
ƒƒ
ƒƒ
ƒƒ
ƒƒ
ƒƒ
ƒƒ
ƒƒ
12 (Differential)
V, mV, mA (APAX-5017)
V, mV, mA, Thermocouple (APAX-5018)
Input Impedance
Voltage: >10 MΩ (APAX-5017), >1 MΩ (APAX-5018)
Current: 120Ω (Current)
Voltage/Current Range ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA,
0 ~ 20 mA, 4 ~ 20 mA (APAX-5017)
±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V, ±20 mA,
0 ~ 20 mA, 4 ~ 20 mA (APAX-5018)
Temperature Range
Type J (-210 ~ 1200° C), Type K (-270 ~ 1372° C),
(APAX-5018 only)
Type T (-270 ~ 400° C), Type E (-270 ~ 1000° C),
Type R (0 ~ 1768° C), Type S (0 ~ 1768° C),
Type B (300 ~ 1820° C)
Configure Different
Yes
Range for Each Channel
Resolution 16-bit with accuracy ±0.1% or better of Full Scale Range
(Voltage),
±0.2% or better of Full Scale Range(Current)
Note: Refer to manual for Thermocouple accuracy
Sampling Rate
12 samples/second (total)
Conversion Time
100 ms (per channel)
CMR @ 50/60 Hz
92 dB
NMR @ 50/60 Hz
60 dB
Noise Rejection Hardware Filter (50/60 Hz)
Wire Burn-out Detection Yes (APAX-5081 only, for Thermocouple)
Protection
ƒƒ Isolation between
2,500 VDC
Channels and Backplane
ƒƒ Supports Over Voltage Protection
Environment
ƒƒ Operating Temperature -10 ~ 60° C (when mounted vertically)
ƒƒ Storage Temperature -40 ~ 70° C
ƒƒ Relative Humidity
5 ~ 95% (non-condensing)
Ordering Information
ƒƒ
ƒƒ
ƒƒ
ƒƒ
ƒƒ
APAX-5017
APAX-5018
APAX-5001
APAX-5002
APAX-5343E
12-ch Analog Input Module
12-ch Thermocouple Input Module
1-slot Backplane Module
2-slot Backplane Module
Power Supply for APAX Expansion Module
Online Download www.advantech.com/products