GAMEWELL-FCI ATD-RL2F

Velociti® Series
ATD-L2F, ATD-RL2F
Description
Addressable Thermal Sensor
The Gamewell-FCI Velociti® Series, addressable plug-in
thermal sensors with integral communication provide features that surpass conventional sensors. Point ID capability allows each sensor’s address to be set, providing exact
locations for pinpointing alarm locations and for selective
maintenance. ATD thermal sensors use an innovative thermistor sensing circuit to produce 135°F/57°C fixed-temperature (ATD-L2F). The ATD-RL2F provides a combination
15°/minute rate-of-rise with 135° fixed thermal detection
that is included in a low-profile package. The ATD-HL2F
provides fixed high-temperature detection at 190°F/88°C.
These thermal sensors provide cost-effective, addressable
property protection in a variety of applications.
The Velociti® Series uses a communication protocol that
substantially increases the speed of communication
between the sensors and Gamewell-FCI analog addressable fire alarm controls. These devices operate in a
grouped fashion. If one of the devices in the group has a
status change, the panel’s microprocessor stops the group
poll and concentrates on the single device. The net effect
is response speed up to five times greater than earlier
designs.
ATD-L2F
Features
• Sleek, low-profile design
• Visual rotary switch addressing
• Built-in functional test switch activated by an external
Installation
ATD plug-in sensors use a separate base to simplify installation, service, and maintenance. A special tool allows
maintenance personnel to plug-in and remove sensors
without using a ladder.
Mount the base on a box which is at least 1.5" (3.8 cm)
deep. Suitable mounting base boxes include:
• 4.0" (10.2 cm) square box.
• 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box.
• Single-gang box (except relay or isolator base).
• With B501BH or B501BHT base, use a 4.0" (10.2 cm)
square box.
• With B224RB or B224BI base, use a 3.5" (8.9 cm)
octagonal box, or a 4.0" (10.2 cm) octagonal or square
box.
NOTE: Because of the inherent supervision provided by
the SLC, end-of-line resistors are not required. Wiring “Ttaps” or branches are permitted for Style 4 (Class “B”)
wiring.
magnet
• Bicolor LEDs flash green whenever the sensor is
addressed, and light steadily red on alarm*
• Optional relay, isolator, or sounder bases
• Low standby current
• Addressable communication
• Stable communication technique with noise immunity
• Optional remote, single-gang LED accessory
(RA-400Z)
• Suitable for installation in ducts
Note: *Only the red LED is operative in panels that do not operate
in Velociti® mode.
Velociti® and E3 Series® are registered trademarks of Honeywell
International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
An ISO 9000-2000 Company
SIGNALING
FM
S2332
MEA
Approved
3023594 219-02-E Vol.VI 07270-0694:256
APPROVED
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0620 Rev. C3 page 1 of 2
©2008 by Honeywell International Inc. All rights reserved.
Specifications
Size:
Shipping Weight:
Operating
Temperature:
ATD-L2F or
ATD-RL2F
ATD-HL2
Sensor Spacing:
Relative Humidity:
ATD-L2F
ATD-RL2F
ATD-HL2F
Specifications
2.1" (5.3 cm) high x 4.1" (10.4 cm)
diameter installed in B501 base,
6.1" (15.5 cm) diameter installed in
ADB-FLF base
4.8 oz. (137 g)
Bases and Options
ADB-FLF
B501
B501BH or
B501BHT
B224RB
Relay Base
–4° F to 100° F (–20° C to 38°C)
–4° F to 150°F (–20 C to 66°C)
UL® approved for 50 ft. (15.2 m)
center to center
FM approved for 25 x 25 ft.
(7.6 x 7.6 m) spacing
10 – 93% (non-condensing)
Fixed-temperature setpoint
135°F (57°C)
Combination 135° F fixed
temperature and 15° (8.3°c) per
minute rate-of-rise°
Fixed-temperature setpoint
190°F (88°C)
B224RB
Relay Base
Dimensions:
B224BI
Isolator Base
Dimensions:
RA-400Z
BCK-200
Electrical Specifications
6.1” (15.5 cm) diameter standard base
4.1” (10.4 cm) diameter flangeless base
Sounder base assembly (B501BHT
produces a Temporal Pattern) includes
B501 base
Up to 14 AWG (2.0 mm2)
Relay type: Form-C
Rating:
2.0A @ 30 VDC resistive
0.3 A @ 110 VDC inductive
1.0 A @ 30 VDC inductive
6.2”: (15.7 cm) x 1.2” (3.0 cm)
6.2” (15.7 cm) x 1.2” (3.0 cm)
Maximum 25 devices between isolator
bases
Remote alarm indicator, LED
Black detector covers (box of 10)
Ordering Information
Voltage Range:
15 - 32 volts DC peak
Standby Current: 200 mA @ 24 VDC
(without communication)
max. avg.)
.0003 A @ 24 VDC
(one communication every 5 seconds
with LED enabled)
LED Current
(max.)
.0065 A @ 24 VDC (LED lit)
Voltage Range
15 –32 volts DC peak
Model
Description
ATD-L2F
ATD-RL2F
Addressable thermal sensor, fixed, 135° F
Addressable thermal sensor, combination
fixed,135° F and 15°/minute rate-of-rise.
Addressable thermal sensor, fixed, 190° F
ATD-HL2F
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0620 Rev. C3 page 2 of 2
www.gamewell-fci.com